<feed xml:lang="en" xmlns="http://www.w3.org/2005/Atom"><title>Activity for neapolitaner1</title><link href="https://forge.codesys.com/u/neapolitaner1/activity/" rel="alternate"/><id>https://forge.codesys.com/u/neapolitaner1/activity/</id><updated>2022-02-09T13:01:45.786000Z</updated><subtitle>Recent activity for neapolitaner1</subtitle><entry><title>neapolitaner1 posted a comment on discussion Engineering 🇬🇧</title><link href="https://forge.codesys.com/forge/talk/Engineering/thread/7bb669969b/?limit=25#caa6" rel="alternate"/><published>2022-02-09T13:01:45.786000Z</published><updated>2022-02-09T13:01:45.786000Z</updated><author><name>neapolitaner1</name><uri>https://forge.codesys.com/u/neapolitaner1/profile/</uri></author><id>https://forge.codesys.com/forge/talk/Engineering/thread/7bb669969b/?limit=25#caa6</id><summary type="html">hi, finally i found the issue ... on my CAN-bus there are several CanOpen and J1939 devices. To keep the busload as low as possible i set the CanOpen PDO's to different interval-times. Therefore every few minutes/hours (depending on the chosen timings) all PDO's need to get handled at the same time. This "spike" in bus-load and especially cpu-load required way too much processing-time and exceeded the cycletime of the CPU. means: i've chosen 10ms as minimum CPU taskcycle during "spike": the CPU taskcycle-time...</summary></entry></feed>