  • Posted a comment on discussion Engineering πŸ‡¬πŸ‡§ on CODESYS Forge

    The Control RTE is 3.5.18.20, using the symbol configuration for exposure of variables.

  • Posted a comment on discussion Engineering πŸ‡¬πŸ‡§ on CODESYS Forge

    Hi there, An "OPC Expert" client software is connecting to a Codesys Control RTE (x64) OPC UA Server. It reads only about 25 variables every 5 minutes. The OPC UA Server seems to shut down on the Codesys runtime. Is there any way to get information about the Codesys OPC UA Server status? Restart it? There is nothing in the PLC Logs after the OPC UA Server has started. It works for a while, then it doesn't. Any ideas? Any way of getting more info out of the Codesys OPC UA Server? -Bjarne

  • Posted a comment on discussion Engineering πŸ‡¬πŸ‡§ on CODESYS Forge

    Thanks for this - I have now been looking in to just having an extra (non-RTE) runtime on the same machine, as you suggest. I will probably proceed this way. Even though it still seems very odd to me, that variable exchange to a different runtime is easier than between applications on the same controller. There will be some fun with the licensing, it seems. Does anyone know if it is possible to specify which license container/specific license the runtime is going to use at runtime. Let's say I have...

  • Posted a comment on discussion Engineering πŸ‡¬πŸ‡§ on CODESYS Forge

    Hi, I would like to divide a project into multiple applications - as a minimum: one handling visualization and Alarm Manager, one handling I/O and plant control logic. But how to exchange variables between the applications? What have you done to get such a solution? In versions 3.5.19 and earlier, you can have Child applications, where the children can access a GVL in the Parent application. Children apps is no longer possible in 3.5.20 - but you can have 'sibling' apps - Several apps directly under...

  • Posted a comment on discussion Engineering πŸ‡¬πŸ‡§ on CODESYS Forge

    I believe it should be available. It may be the case, that your device does not support the alarm configuration. Some smaller PLCs sometimes do not support it. You can try changing to a different device, like a Codesys Control Win, in your project, and see if then allows you to add the alarm configuration.

  • Posted a comment on discussion Engineering πŸ‡¬πŸ‡§ on CODESYS Forge

    Hi A SINT is a short (signed) integer. It is already only 1 byte - so you should have no problem casting it to a byte like so: bMyByte := TO_BYTE(sintMyShortInt); If you have a regular INT you want to put in 2 bytes - there are a lot of ways you can do this. A Union is certainly one of them. You could have a union with 2 memebers: An array of 2 bytes as one member, and an integer value as another member. Another way would be to look at MEMCPY to put the value into your CAN-message. .. or create a...

  • Modified a comment on discussion Visualization πŸ‡¬πŸ‡§ on CODESYS Forge

    Hi, With the new Runtime Based User Management, is there any way for WebVisu clients to be logged in to a default user automatically - no login prompt? I would like for the default user to be able to perform normal operation of the machine, without logging in to the WebVisu. This is possible with the Legacy User Management. For the Runtime based user management, there seems to be a default user for the TargetVisu - but not for the WebVisu. -Bjarne

  • Posted a comment on discussion Visualization πŸ‡¬πŸ‡§ on CODESYS Forge

    Hi, With the new Runtime Based User Management, is there any way for WebVisu clients to be logged in to a default user automatically - no login prompt? I would like for the default user to be able to perform normal operation of the machine, without logging in to the WebVisu. This is possible with the Legacy User Management. -Bjarne