Ok, for the sake of completeness in case anyone else has this problem. I can tell you that what finally worked for me was to change the line: // create an ExtensionObject to wrap the value to be written ExtensionObject extensionObject = new ExtensionObject( new ExpandedNodeId("GVL_StructA", 5), structAData ); to: // create an ExtensionObject to wrap the value to be written ExtensionObject extensionObject = new ExtensionObject( new ExpandedNodeId("GVL_StructA|defaultbinary", 5), structAData ); I'm...
Ok, I have a simple test environment. From C#, using OPC UA, I can read DINTs, write DINTs, read Structs, but when I try to write a struct I get BadNotWritable. I am using Communication Manager, OPC UA Server, and IEC Symbol Publishing. I have a struct defined with one single DINT in it. The instance of the struct is in GVL. The struct is marked read/write in IEC Symbol Publishing. Any ideas? Pointers are welcome. public static async Task WriteStructA(byte[] structAData) { if (_session == null) throw...
mainak, sorry, just saw your post. I have done that and I still get the same exception. the innerResult says "BadSecureChannelClosed 'Remote side closed connection'". Any other tips? Pointers are welcome.
sadly, no
Noob alert! I’m just getting my feet wet with CODESYS. I have a “Hello World” project in the CODESYS IDE. I’m using the Win SoftPLC on the same computer. I’ve added a Communication Manager under the Application node. Under that is “OPC UA Server -> IEC Symbol Publishing 01”. I also added “OPC_UA_Symbols -> Information Model”. I’m not sure I need the second thing. I was grasping at straws. I also set up several dummy symbols in the IEC Symbol Publishing 01 node. In my C# application, I am trying to...