Activity for hugo63880

  • hugo63880 hugo63880 posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    We found a way to solve that problem. On the PFC200 both Ethernet port are bridged by default so you aren't able to use Ethercat in this configuration. To remove this bridge you need to connect to the WBM of your PFC200 or you can do it with the linux command: cbm. I hope that can be helpful. Hugo.

  • hugo63880 hugo63880 posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello, I am working on SP17.1 with a PFC200 from WAGO and I am trying to add an Ethercat Master but as you can see below it doesn't work. I have already tried with others version (SP16.3 and SP16.4) and I have checked all my hardware connections without success. Also, I have already worked with Ethercat Master without any problem. Do you have a solution to solve that problem ? Thank you in advance, Hugo.

  • hugo63880 hugo63880 posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello, We are working on Codesys SP16.30 and we want to automatically change parameters of an IO-Link device. The on-line change of the parameters is working properly with Codesys interface (see attached image) by using the "write" button (manually). Now we want to write a new value automatically (for example SP1 on the image) by using the method: "IoDrvWriteParameter" but we don't know how to deal with it. Have you any example or advise to automatically write a new parameter's value ? Thank you...

1