  • hyplcmotion hyplcmotion modified a comment on discussion Engineering 🇬🇧

    Found out how! Needed to connect to PFC200 via Putty, and open CodesysControl.cfg with “sudo nano /etc/CODESYSControl.cfg”. Then adding following command to the end of file, and use the name you want, save/close CODESYSControl.cfg, and reboot your PLC. [CmpOPCUAProviderIecVarAccess] CustomNodeName= PFC200

  • hyplcmotion hyplcmotion modified a comment on discussion Engineering 🇬🇧

    Hello, I am wondering how to change the default OPC/UA Server Topic name "CODESYS Control for PFC200 SL" in Codesys when using codesys OPC UA Server? For example have a tag with following node Id ns=4;s=|var|PFC200.Application.Tag.Me instead of ns=4;s=|var|CODESYS Control for PFC20 SL.0Application.Tag.Me Thanks Codesys Version 3.5.18 SP3

  • hyplcmotion hyplcmotion modified a comment on discussion Engineering 🇬🇧

    Found out how to do this. Needed to connect to PFC200 via Putty, and open CodesysControl.cfg with “sudo nano /etc/CODESYSControl.cfg”. Then adding following command to the end of file, and use the name you want, save/close CODESYSControl.cfg, and reboot your PLC. [CmpOPCUAProviderIecVarAccess] CustomNodeName= PFC200

  • hyplcmotion hyplcmotion modified a comment on discussion Engineering 🇬🇧

    Found out how to do this. Needed to connect to PFC200 via Putty, and open CodesysControl.cfg with “sudo nano /etc/CODESYSControl.cfg”. Then adding following command and use the name you want: [CmpOPCUAProviderIecVarAccess] CustomNodeName= PFC200

  • hyplcmotion hyplcmotion posted a comment on discussion Engineering 🇬🇧

    Found out how to do this. I needed to connect to PFC200 via Putty, and open CodesysControl.cfg with “sudo nano /etc/CODESYSControl.cfg” adding following: [CmpOPCUAProviderIecVarAccess] CustomNodeName= OPCUA_WAGO

  • hyplcmotion hyplcmotion posted a comment on discussion Engineering 🇬🇧

    Hello, I am wondering if anyone can explain how to change the default OPC/UA Server Topic name "CODESYS Control for PFC200 SL" in Codesys when using codesys OPC UA Server? For example have a tag with following node Id ns=4;s=|var|PFC200.Application.Tage.Me instead of ns=4;s=|var|CODESYS Control for PFC20 SL.0Application.Tage.Me Thanks Codesys Version 3.5.18 SP3