  • IonCoder IonCoder posted a comment on discussion Engineering 🇬🇧

    Get a different sensor that is 0-10V and 0-350 Bar. There is nothing you can reasonably do to boost the range of the sensor, and the PLC will only ever be 0-10V. Take away is to always be careful to match the sensor and PLC input ranges in the future.

  • IonCoder IonCoder posted a comment on discussion Engineering 🇬🇧

    Using Codesys 3.5 SP11 32bit to program a pair of IFM CR711S controllers. They each have an NVL sender and are set up to receive each others messages. One is transmitting properly but not receiving, the other is receiving the first's messages just fine. When I look at the traffic in wireshark, I can see the one transmitting properly as UDP packets on the subnet and port I had specified. The Second is transmitting on the right subnet and port, but is sending 'ADwin Config' packets. Has anyone run...