Searching in the way you show doesn't work even with default ip address (192.168.1.10) only "scan network" works with default ip..
Yes I've added the two Ip and also search by ip address in codesys but still not working. I tried to add a ethernet interface and set a new ip, but still not working, the ip changes and i can ping but in codesys i am not able to find the plc anymore.
The PLC is INVT AX71-C-1608P i use function described in the invt manual, this one: Then searching the device with gateway localhost and port 1217 i can't find the plc, sometimes changing the ip to 192.168.0.x i am able to find it but with 192.168.250.x or whatever it won't show. My pc is in the new address class and also it pings correctly even other devices connected with it using ethernet TCP like a Weintek touch panel works correctly and sees the plc but only Codesys searching function can't...
The PLC is INVT AX71-C-1608P i use function described in the invt manual, this one: Then searching the device with gateway localhost and port 1217 i can't find the plc, sometimes changing the ip to 192.168.0.x i am able to find it but with 192.168.250.x or whatever it won't show. My pc is in the new address class and also it pings correctly even other devices connected with it using ethernet TCP like a Weintek touch panel work correctly and sees the plc but only Codesys searching function can't find...
Hello, I can't find the plc when its IP has been changed, for example default ip is 192.168.1.10 and with search function i can find it and connect online but if i change its ip to 192.168.3.x or whatever then it's impossible to find the devide in the network..maybe do I have to access by devide ID? the problem is that i don't know it because changes every time...