Activity for nikgind

  • nikgind nikgind posted a comment on discussion Engineering 🇬🇧

    Hi, yes i did solve it. You have to change the namespace 0 model in the UaModeler. Open the modeler --> Settings --> Edit Settings --> scroll down to the last option "External Model Support" --> Check "Allow replacing built-in..." Now create a new project in the UaModeler. If you have to choose your base models, you can see the option "Find another Opc.Ua.NodeSet2". I have attached the .xml i am using.

  • nikgind nikgind posted a comment on discussion Engineering 🇬🇧

    Hi I am trying to import a custom information model that I created using UA Modeler. I have only added two new methods and two new object types. It is possible to add the information model to the Communication Manager and the two new object types are shown in the Information Model tab. After compiling i get the following error: Communication Manager [Device: PLC Logic: Application]: The information model http://opcfoundation.org/UA/ is required by http://yourorganisation.org/Bsp_3.1/ with a minimal...

1