  • oproulx oproulx posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Hi, I'm running CODESYS Control RTE SL 3.5.18.30 on a new Siemens IPC and I'm not able to update the network driver to CmpEt1000MPD. It says it's not compatible. I contacted Siemens about it, they said that their new IPC linup use Intel EC1000R 1.0 Gbe , and some driver a not compatbile with that yet. I was running another CODESYS Runtime and EtherCAT communication with an older Siemens IPC without any problem. The older IPC was using Intel(R) I210 Gigabit Network. So is there a patch from Codesys...

  • oproulx oproulx posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    To follow up and close this post, if anybody get that similar problem. Simply go in the root folder of the PLC Runtime on the Device and delete the CSV files.

  • oproulx oproulx posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Hi, I installed CODESYS Control RTE SL 3.5.18.30 on a Siemens IPC to do some tests and when I try to Login using the IP address of the IPC, it ask me a user name and password for the Device. I don't remember setting that up when I installed the runtime (unless I miss it) and there is no user in my project either. I tried some classic administrator password but it's not working out. Any idea what that user could be or how to login/download without it. Thanks