Anyway, any idea how to get command byte 0x22 for sdo write if I use codesys cia405 canopen library?
Thank you for an answer. Unfortunatelly, it doesn't work. The slave needs command byte as follows 0x22. It means expedited transfer where s-bit is not set, therefore data length is not specified. If I use segmented mode by CiA405.SDO_WRITE_DATA it produce command byte as follows 0x21 which is unfortunately supported by the slave and it returns with error 0x05040001 - SDO Abort Code -Client/server command specifier not valid or unknown. I can use CAN API low level to overcome this problem where it...
Hi,is there any canopen library where is implemented sdo write with unspecified datalength (command byte 0x22)? I tried caa cia405 canopen library but it doesnt support this, but my slave device accept only 0x22. Thank you for any help.
Hi,is there any canopen library where is implemented sdo write with unspecified datalength (command byte 0x22)? I tried caa cia405 canopen library but it doesnt support this, but my slave device accept only 0x22. Thank you for any help.