I actually just found the solution maybe. If anyone else is running into this, go to your Project Settings > Visualization > Advanced (check 'Visible' to see advanced settings) > UNCHECK 'Activate property handling in all element properties.' I am not sure what else unchecking this might affect but it seems to allow the alarm table to be filtered as expected.
I actually just found the solution maybe. If anyone else is running into this, go to your Project Settings > Visualization > Advanced (check 'Visible' to see advanced settings) > UNCHECK 'Activate property handling in all element properties.' I am not sure what else unchecking this might affect but it seems to allow the alarm table to be filtered as expected.
I am having the exact same issue and was wondering if you ever found the problem? The sample program does exactly what it's supposed to with filtering but when I implement it the exact same way in my program, the alarm list just goes blank when I attempt to apply a filter.
I am having the exact same issue and was wondering if you ever found the issue? The sample program does exactly what it's supposed to with filtering but when I implement it the exact same way in my program, the alarm list just goes blank when I attempt to apply a filter.
I am having trouble getting the alarm table filtering to work. I downloaded the alarm filter latch example project and ran it on the local Codesys Control Win and the filters worked fine. I am trying to replicate it in my project and everything seems to be set up the exact same way and every time I turn on the filter, it shows no alarms. I even started a blank project and just copied in elements from the example project so that it is exactly the same and when I attempt to filter, it again shows no...
I have noticed on the standard numpad dialog, if a user enters a purely decimal number (ie '.6'), the numpad will not accept the value but gives no indication. One must type a leading zero (ie '0.6') in order for it to work. Is there a way to correct this so that a user can just type the decimal value?
I am trying to create an icon on an overview screen that depicts if an alarm group has active alarms, active acknowledged alarms, or inactive unacknowledged alarms (waiting for confirmation). I've attempted to set up Notification Actions in the Alarm Class to set variables based on state changes but have been unable to find a clean and effective way to do this. Because an action on any alarm will trigger the variable to be set as instructed, I'm struggling to find a way to configure it for what I...
I am relatively new to Codesys and I'm trying to develop an HMI that displays what mode a particular device is in based on an integer value. I am currently using dynamic texts with a text list which works fine but I am looking for a way to display a particular string (ie 'Unknown') when the index doesn't match any of of the indices in the text list. I can enter 'Unknown' in the text property of the text field element which works as expected but it displays the single quotes on the visualization....