Using PEAK CAN PCIe card (IPEH-004040) with Codesys Control RTE V3
CODESYS Forge
talk
(Thread)
Using PEAK CAN PCIe card (IPEH-004040) with Codesys Control RTE V3
Last updated: 2024-12-20
Post by dom4u on Using PEAK CAN PCIe card (IPEH-004040) with Codesys Control RTE V3
CODESYS Forge
talk
(Post)
Some findings on this issue: PEAK CAN Driver is the same as in every PCI card from PEAK. I updated the inf file. Here are my steps: 1. Include right VendorID into the *.inf file 2. Disable Windows driver check (Disable WHQL check). This you need because 3S driver is not certified. You will find steps via google or ask chatgpt :) 3. Select: Select driver from a list and navigate to the folder. Say yes to install an uncertified driver. 4. Driver installed and device without errors I did the same with CAN Card from ESD, but here you dont need to include the vendor ID. In ANY CASE it was not successful. The RTIOwdmgeneric is not available in Codesys or anyhow accassable :( I wonder that it fails in two cases, two suppliers, two driver in the same way. How can RTIOwdmgeneric implemented into the project?
Last updated: 2024-12-20
Post by dagi89 on CAA File open Problems
CODESYS Forge
talk
(Post)
Dear All, i am using Runtime CODESYS Control Win V3 - X64 Version 3.5.20.40, by using CAA file library (3.5.19.0) seems not fasible to open a file n 'C:\ciao.txt' or others absolute path. The error on File Open is 5114 File Operation Danied.. here below the implemented code and the windows file's properties. I use to implement codesys in RPI and this operation is immediate... Can someone help me in it?? Thanks in advance Dagi89
Last updated: 2024-12-21
Post by gatto on CAA File open Problems
CODESYS Forge
talk
(Post)
Ciao, here same question https://forge.codesys.com/forge/talk/Engineering/thread/2538729618/ in this post https://forge.codesys.com/forge/talk/Engineering/thread/4586a90290/?limit=25#d531 i find : keep in mind that all files which are generated / or read should be exist in the iecfilepath this means: for Windows (Control Win as example) c:\ProgramData\CODESYS\CODESYSControlWinV3x64\268E8ADF\PlcLogic for Linux /var/opt/codesys/PlcLogic I never use codesys on windows but im sure on linux we can manipulate file only inside /var/opt/codesys/Plc Logic. Or you need to modify the file codesyscontrol.cfg for change path permission, but this is another history Buone feste !
Last updated: 2024-12-21
Post by gseidel on Beckhoff EL7037 softmotion
CODESYS Forge
talk
(Post)
Hi Stefan, we will update our driver to support the EL7037 in our next release of SoftMotion. In case you are interested to test a pre-release, please contact our support and mention this forum post. Best regards, Georg
Last updated: 2024-12-23
CAA File open Problems
CODESYS Forge
talk
(Thread)
CAA File open Problems
Last updated: 2024-12-21
Beckhoff EL7037 softmotion
CODESYS Forge
talk
(Thread)
Beckhoff EL7037 softmotion
Last updated: 2024-12-23
Post by gseidel on Beckhoff AS1060 and EL7041 configuration
CODESYS Forge
talk
(Post)
Hi pmanuele, while I don't have firsthand experience with the EL7041 and the step motor AS1060, there are two things you can check: If you use an external encoder, please make sure you use the alternative device description calles "EL7041 1Ch. Stepper motor output stage (50V, 5A) Rev24 with external Encoder". The SoftMotion driver will set the feedback type automatically, and use the correct object for the actual position (16#6010:21 instead of 16#6010:20) If you have problems with changing the controller mode, I assume to velocity, please make sure you change the PDO mapping so that the actual velocity (16#6020:33) and set velocity (16#7010:33) are mapped by PDO. Hope this helps, Georg
Last updated: 2024-12-23
Beckhoff AS1060 and EL7041 configuration
CODESYS Forge
talk
(Thread)
Beckhoff AS1060 and EL7041 configuration
Last updated: 2024-12-23
Post by arcadium on Library ENUM text representation in visualization
CODESYS Forge
talk
(Post)
Hello, Maybe someone could help with this. When I add ENUM to a text field I get the number instead of the text. For my own ENUM variable I have declared and enabled text list value is displayed as text, but I need enum text displayed from softMotion and other internal FB's. In the picture I have one of desired ENUM variable setup, but in the visu I have number, but in the watch window it's text. There is probably some checkbox to tick, but was looking for an hour, can't find a solution. Would apreciate some help
Last updated: 2024-12-24
Post by arcadium on Library ENUM text representation in visualization
CODESYS Forge
talk
(Post)
Hello, Maybe someone could help with this. When I add ENUM to a text field I get the number instead of the text. For my own ENUM variable I have declared and enabled text list value is displayed as text, but I need enum text displayed from softMotion and other internal FB's. In the picture I have one of desired ENUM variable setup, but in the visu I have number, but in the watch window it's text. There is probably some checkbox to tick, but was looking for an hour, can't find a solution. Would apreciate some help
Last updated: 2024-12-24
Library ENUM text representation in visualization
CODESYS Forge
talk
(Thread)
Library ENUM text representation in visualization
Last updated: 2024-12-24
Post by mtnkyr on Runtime Problem connecting to Keyence IV-500MA Camera
CODESYS Forge
talk
(Post)
I have to use Keyence IV-500MA Camera for a project. Actually I can use physical connection but I tried to connect using Ethernet protocol so I added its EDS file but I took a lot of errors. Could you help me to solve this problem?
Last updated: 2024-12-26
Axis references in visualization
CODESYS Forge
talk
(Thread)
Axis references in visualization
Last updated: 2024-12-26
Post by mtnkyr on Runtime Problem connecting to Keyence IV-500MA Camera
CODESYS Forge
talk
(Post)
I have to use Keyence IV-500MA Camera for a project. Actually I can use physical connection but I tried to connect using Ethernet protocol so I added its EDS file but I took a lot of errors. Could you help me to solve this problem?
Last updated: 2024-12-26
Runtime Problem connecting to Keyence IV-500MA Camera
CODESYS Forge
talk
(Thread)
Runtime Problem connecting to Keyence IV-500MA Camera
Last updated: 2024-12-26
Post by eschwellinger on Runtime Problem connecting to Keyence IV-500MA Camera
CODESYS Forge
talk
(Post)
which plc in which version do you use?
Last updated: 2024-12-27
Post by nz-dave on Ethernet/IP Scanner Exception
CODESYS Forge
talk
(Post)
Its Running on a Weintek CMT HMI. the program is not huge, just controlling a few pumps. plc is at 1%
Last updated: 2024-12-27
Post by nz-dave on Ethernet/IP Scanner Exception
CODESYS Forge
talk
(Post)
see attached I don't have watchdog enabled in tasks?
Last updated: 2024-12-27
Post by nz-dave on Ethernet/IP Scanner Exception
CODESYS Forge
talk
(Post)
3.5,18,30 The Weintek HMI Runs a dual core CPU.. one for the HMI and one "real time OS" for Running Codesys.
Last updated: 2024-12-28
Post by eschwellinger on Ethernet/IP Scanner Exception
CODESYS Forge
talk
(Post)
which runtime version and dies this device has an realtime kernel?
Last updated: 2024-12-28
Post by dogulas on OPC UA C# client connecting to OPC UA CODESYS server
CODESYS Forge
talk
(Post)
Ok, for the sake of completeness in case anyone else has this problem. I can tell you that what finally worked for me was to change the line: // create an ExtensionObject to wrap the value to be written ExtensionObject extensionObject = new ExtensionObject( new ExpandedNodeId("GVL_StructA", 5), structAData ); to: // create an ExtensionObject to wrap the value to be written ExtensionObject extensionObject = new ExtensionObject( new ExpandedNodeId("GVL_StructA|defaultbinary", 5), structAData ); I'm sure there are many other problems that could cause this very generic error, but this was my problem.
Last updated: 2024-12-30
Post by durallymax on Cannot Start Application ControlWin
CODESYS Forge
talk
(Post)
Uninstalling and deleting all ProgramData manually, then re-installing appears to have fixed it.
Last updated: 2024-12-30
OPC UA C# client connecting to OPC UA CODESYS server
CODESYS Forge
talk
(Thread)
OPC UA C# client connecting to OPC UA CODESYS server
Last updated: 2024-12-30
Cannot Start Application ControlWin
CODESYS Forge
talk
(Thread)
Cannot Start Application ControlWin
Last updated: 2024-12-30
To search for an exact phrase, put it in quotes. Example: "getting started docs"
To exclude a word or phrase, put a dash in front of it. Example: docs -help
To search on specific fields, use these field names instead of a general text search. You can group with AND or OR.