Post by julianramirez on Visu 4.9.1 auto-logon/login
CODESYS Forge
talk
(Post)
Hello everyone, I have been trying to test the auto-login feature that is advertised on the Release Notes since Visu 4.8: *Version: 4.8.0.0 Besides some bug fixes and improvements this version contains the following new functionality: Alarmmanagement: Possibility to raise alarms programmatically Use real time clock of IEC context Automatic login for WebVisu using Chrome "Sign in automatically"* I am using a personalized login Visualization, the User Management works, however, when ticking the checkbox that keeps the credentials stored, after I reload the page I still see that the user and password details are not filled in. I tried with the default Login Visu (Blue one), and still see the same behavior - VisuUserManagement.VUM_LoginVisualization - I've tried with Chrome and Edge. Thanks for your help
Last updated: 2026-01-12
Post by infinitetool on No connection could be made because the target machine actively refused it
CODESYS Forge
talk
(Post)
Hi! I'm having trouble connecting to a device in Deploy Control SL. I'm able to see the device is available during a scan, and I can ping the device as well, but when I try to connect I get the message "No connection could be made because the target machine actively refused it". I've worked on this for hours including turning off the firewall on the device PC but nothing seems to work. The device is running a fresh install of Windows 11 IoT Enterprise 2024 and the Development System is 3.5.21.50 running on Windows 11. Thank you in advance for any ideas!
Last updated: 2026-03-10
Post by mascara on JOG continues in WCS ( SMC_GroupJog2 )
CODESYS Forge
talk
(Post)
I'm using the SMC_GroupJog2 block from the SM3_Robotics library for manual movement of an AxisGroup in WCS coordinates. The observed behavior is: When pressing X+, the X-axis starts moving correctly. If I press Y+ during the movement, the block interrupts the current movement and starts a new movement in X and Y. If I release any button, all axes stop, even if another button is still pressed. Example: Pressing X+ → X moves Pressing X+ and Y+ → X stops momentarily and starts XY movement Releasing X+ while holding Y+ → all axes stop The expected behavior would be: to allow simultaneous continuous movement on multiple axes to not interrupt movement when another axis is added or removed. Is there a correct configuration of SMC_GroupJog2 to achieve this behavior, or is there another block more suitable for continuous manual jog in AxisGroup (WCS)?
Last updated: 2026-03-11
Post by darwin03 on Mismatch between coordinate monitor and actual motion using SMC_GroupJog2, MC_MoveLinearAbsolute (6DOF)
CODESYS Forge
talk
(Post)
Dear Georg, Thank you for your explanation about the axis scaling. I checked the scaling of Joint6 and corrected it so that one technical unit equals one angular degree. However, I am now facing another issue. When I move all axes to zero position and then try to use SMC_GroupJog2 and MC_MoveLinearAbsolute, I receive the error SMC_CP_CONFIGS_DIFFER I already tried moving each joint manually to different positions before executing the motion command, but the error still appears. Could you please explain: What exactly causes SMC_CP_CONFIGS_DIFFER Thank you very much for your support. Best regards, darwin03
Last updated: 2026-05-04
Post by baotthitawat on SCADA Systems Are Becoming Easier to Integrate With Modern Applications
CODESYS Forge
talk
(Post)
One thing I’ve been seeing recently is that more industrial systems are starting to expose realtime SCADA data through APIs instead of keeping everything isolated inside the local monitoring software. This makes integration much easier for cloud platforms, mobile dashboards, AI analytics, and enterprise applications that need realtime industrial data. Instead of exporting reports manually or building complicated middleware, APIs allow external systems to access SCADA data directly in realtime. I think this becomes especially useful for applications like wastewater treatment monitoring, where operators need better visibility into alarms, equipment status, and operational conditions across different locations. Feels like modern SCADA is slowly evolving from a standalone monitoring platform into part of a larger connected industrial ecosystem.
Last updated: 2026-05-28
Post by baotthitawat on SCADA Systems Are Becoming Easier to Integrate With Modern Applications
CODESYS Forge
talk
(Post)
One thing I’ve been seeing recently is that more industrial systems are starting to expose realtime SCADA data through APIs instead of keeping everything isolated inside the local monitoring software. This makes integration much easier for cloud platforms, mobile dashboards, AI analytics, and enterprise applications that need realtime industrial data. Instead of exporting reports manually or building complicated middleware, APIs allow external systems to access SCADA data directly in realtime. I think this becomes especially useful for applications like wastewater treatment monitoring, where operators need better visibility into alarms, equipment status, and operational conditions across different locations. Feels like modern SCADA is slowly evolving from a standalone monitoring platform into part of a larger connected industrial ecosystem.
Last updated: 2026-05-28
Post by baotthitawat on SCADA Systems Are Becoming Easier to Integrate With Modern Applications
CODESYS Forge
talk
(Post)
One thing I’ve been seeing recently is that more industrial systems are starting to expose realtime SCADA data through APIs instead of keeping everything isolated inside the local monitoring software. This makes integration much easier for cloud platforms, mobile dashboards, AI analytics, and enterprise applications that need realtime industrial data. Instead of exporting reports manually or building complicated middleware, APIs allow external systems to access SCADA data directly in realtime. I think this becomes especially useful for applications like wastewater treatment monitoring, where operators need better visibility into alarms, equipment status, and operational conditions across different locations. Feels like modern SCADA is slowly evolving from a standalone monitoring platform into part of a larger connected industrial ecosystem.
Last updated: 2026-05-28
Post by baotthitawat on SCADA Systems Are Becoming Easier to Integrate With Modern Applications
CODESYS Forge
talk
(Post)
One thing I’ve been seeing recently is that more industrial systems are starting to expose realtime SCADA data through APIs instead of keeping everything isolated inside the local monitoring software. This makes integration much easier for cloud platforms, mobile dashboards, AI analytics, and enterprise applications that need realtime industrial data. Instead of exporting reports manually or building complicated middleware, APIs allow external systems to access SCADA data directly in realtime. I think this becomes especially useful for applications like wastewater treatment monitoring, where operators need better visibility into alarms, equipment status, and operational conditions across different locations. Feels like modern SCADA is slowly evolving from a standalone monitoring platform into part of a larger connected industrial ecosystem.
Last updated: 2026-05-28
Post by baotthitawat on SCADA Systems Are Becoming Easier to Integrate With Modern Applications
CODESYS Forge
talk
(Post)
One thing I’ve been seeing recently is that more industrial systems are starting to expose realtime SCADA data through APIs instead of keeping everything isolated inside the local monitoring software. This makes integration much easier for cloud platforms, mobile dashboards, AI analytics, and enterprise applications that need realtime industrial data. Instead of exporting reports manually or building complicated middleware, APIs allow external systems to access SCADA data directly in realtime. I think this becomes especially useful for applications like wastewater treatment monitoring, where operators need better visibility into alarms, equipment status, and operational conditions across different locations. Feels like modern SCADA is slowly evolving from a standalone monitoring platform into part of a larger connected industrial ecosystem.
Last updated: 2026-05-28
Post by baotthitawat on SCADA Systems Are Becoming Easier to Integrate With Modern Applications
CODESYS Forge
talk
(Post)
One thing I’ve been seeing recently is that more industrial systems are starting to expose realtime SCADA data through APIs instead of keeping everything isolated inside the local monitoring software. This makes integration much easier for cloud platforms, mobile dashboards, AI analytics, and enterprise applications that need realtime industrial data. Instead of exporting reports manually or building complicated middleware, APIs allow external systems to access SCADA data directly in realtime. I think this becomes especially useful for applications like wastewater treatment monitoring, where operators need better visibility into alarms, equipment status, and operational conditions across different locations. Feels like modern SCADA is slowly evolving from a standalone monitoring platform into part of a larger connected industrial ecosystem.
Last updated: 2026-05-28
Post by baotthitawat on SCADA Systems Are Becoming Easier to Integrate With Modern Applications
CODESYS Forge
talk
(Post)
One thing I’ve been seeing recently is that more industrial systems are starting to expose realtime SCADA data through APIs instead of keeping everything isolated inside the local monitoring software. This makes integration much easier for cloud platforms, mobile dashboards, AI analytics, and enterprise applications that need realtime industrial data. Instead of exporting reports manually or building complicated middleware, APIs allow external systems to access SCADA data directly in realtime. I think this becomes especially useful for applications like wastewater treatment monitoring, where operators need better visibility into alarms, equipment status, and operational conditions across different locations. Feels like modern SCADA is slowly evolving from a standalone monitoring platform into part of a larger connected industrial ecosystem.
Last updated: 2026-05-28
Post by alex-n on Problem with keeping up the distance between two axes
CODESYS Forge
talk
(Post)
Hello. I have a task to synchronize the movement of two axes and maintain the distance between them. First axe makes equal steps by trigger using MC_MoveRelative function. The second one is standstill and after another signal should catch up the first one from its position to a specified distance and keep it. I've tried to use MC_Phasing and mostly it works. Second axis catches up the first and starts make step with it. But in one moment this axis can crash into the first and there is no clear connection as to why this is happening. It can work correct for a day or for a week.
Last updated: 2026-06-04
Post by timl on BacNet "Unaufgelöste Referenz"
CODESYS Forge
talk
(Post)
Hallo, ich habe Probleme beim nachbauen des BacNet2 Tutorials "Erste Schritte" aus der CODESYS Online Help. https://content.helpme-codesys.com/de/CODESYS%20BACnet/_bacnet_first_steps.html Das Anlegen des BacNet2 Servers und der danach folgenden BacNet Datenpunkte erfolgt ohne Probleme. Der Code lässt sich mit F11 auch Fehlerfrei generieren. Beim Download auf die SPS tritt dann der Fehler auf dem Bild auf. Anbei auch ein Bild des Logs nach dem Download. CODESYS BACnet 2.0.0.0 ist über den Installer runtergeladen. Device: CODESYS Control Win V3 x64 Version 3.5.19.40 CODESYS 3.5.19.40 Im Bibliotheksverwalter ist BACnet2 2.0.0.0 aufgeführt Die Konfigurationsdatei habe ich mit folgenden anpassungen abgespeichert: [ComponentManager] Component.1=CmpTargetVisuStub Component.2=CmpWebServer Component.3=CmpWebServerHandlerV3 Component.4=SysCpuMultiCore Component.5=SysReadWriteLock Component.6=SysCpuBreakpoints Component.7=SysPipeWindows ;Component.8=CmpHilscherCIFX ;Component.9=CmpPCANBasicDrv ;Component.10=CmpCANFoxDrv ;Component.11=CmpIxxatCANDrv ;Component.12=CmpBlkDrvCanServer ;Component.13=CmpBACnet Component.14=CmpBACnet2 [CmpBACnet2] ;configuration file of the BACnet stack IniFile=$PlcLogic$/bacstac2.ini ;task priority of the BACstack process task, default: TASKPRIO_NORMAL_END (159) TaskPrio=128 ;name of the named pipe for the communication with the BACstack AppName=/tmp/BACnetServer Habe ich etwas vergessen?
Last updated: 2024-02-16
web visu on IFM
CODESYS Forge
talk
(Thread)
web visu on IFM
Last updated: 2023-08-18
Project size increasing continuously
CODESYS Forge
talk
(Thread)
Project size increasing continuously
Last updated: 2023-08-23
Function block not autofilling
CODESYS Forge
talk
(Thread)
Function block not autofilling
Last updated: 2023-08-24
Connection to device closed
CODESYS Forge
talk
(Thread)
Connection to device closed
Last updated: 2023-08-25
Modbus Extended Registers
CODESYS Forge
talk
(Thread)
Modbus Extended Registers
Last updated: 2023-08-26
Ping By Name
CODESYS Forge
talk
(Thread)
Ping By Name
Last updated: 2023-08-29
XY Chart
CODESYS Forge
talk
(Thread)
XY Chart
Last updated: 2023-08-30
gateway problem
CODESYS Forge
talk
(Thread)
gateway problem
Last updated: 2023-08-31