Search talk: deploy control sl

 
<< < 1 .. 44 45 46 47 48 .. 67 > >> (Page 46 of 67)

Post by eschwellinger on CODESYS Control for Linux ARM SL (32 bit) on Moxa UC-3100 IPC CODESYS Forge talk (Post)
I would recommend to ask Moxa for a newer version of Debian. Debian 9 ("Stretch") has reached its end of life and is no longer receiving security updates from the official Debian Security Team as of June 30, 2022. This means any systems still running Debian 9 are vulnerable to security risks and should be upgraded to a newer, supported version of Debian like Debian 10 ("Buster") or Debian 11 ("Bullseye").
Last updated: 2025-07-14

Post by dhumphries on Control for Linux SL on Ubuntu Core CODESYS Forge talk (Post)
Try using a password instead of a public key to log into the controller. I have a video showing how to do this on a default installation of Ubuntu server, it should work the same for Ubuntu Core. https://youtu.be/rj0dOhgnGjs?si=352PmveEP7JXZnO- I sign in to the controller at about 6:40 in the video. I have never tried to remove the public key and revert to signing in using a password, but it looks pretty straightforward https://askubuntu.com/questions/745423/how-to-turn-off-password-less-login-for-ssh
Last updated: 2024-02-28

Post by schnepper on Error building Extension SDK Linux code CODESYS Forge talk (Post)
I'm installed the CODESYS Control for Linux SL package and am trying to use the Extension API to call a simple C function. When I get to the step to run "make all" on the Linux machine, I get the error: build interface header: out/CmpFirstTestItf.h from CmpFirstTestItf.m4 ERROR: This functionname does not contain _cext (this is mandatory, see help for details): DEF_API(void',CDECL',external_struct__fb_init',(external_struct_fb_init_struct *p)',1,0x1F77E075,0x00000001) Why does "Generate Runtime System Files" create a function that does not have cext in the name? What am I missing?
Last updated: 2024-04-01

Post by rabaggett on CODESYS control for Raspberry Pi 64 SL errors CODESYS Forge talk (Post)
Update: I started over. I saved progress at each step. all compiled zero errors, zero warnings. Pre-processor messages remain, but I can make progress. Until I try to re- load the project file in Codesys. Re-loaded files error as above when compiled, even though they compiled error-free immediately before saving. Is my installation borked? (Not easy to re-install due to IT madness...)
Last updated: 2024-05-03

Post by jvfred on CodesysHMI.exe: Start Error CODESYS Forge talk (Post)
I have used Codesys HMI SL on several projects. Today I turned my PC on to start building another project and received the following error message when I tried to start my device: "CodesysHMI.exe: Start Error One of the following licenses is required: CodeMeter 101597:13 Failure reason: CmContainer Entry not found, Error 200 CodeMeterAct 5000304:13 Failure reasons: CmContainer Entry not found, Error 200" I have tried reloading HMI SL and even updated to the current version with no success. I am using HMI SL version V3.5.20.10. Any help would be greatly appreciated.
Last updated: 2024-11-01

Post by jvfred on CodesysHMI.exe: Start Error CODESYS Forge talk (Post)
I have used Codesys HMI SL on several projects. Today I turned my PC on to start building another project and received the following error message when I tried to start my device: "CodesysHMI.exe: Start Error One of the following licenses is required: CodeMeter 101597:13 Failure reason: CmContainer Entry not found, Error 200 CodeMeterAct 5000304:13 Failure reasons: CmContainer Entry not found, Error 200" I have tried reloading HMI SL and even updated to the current version with no success. I am using HMI SL version V3.5.20.10. Any help would be greatly appreciated.
Last updated: 2024-11-01

Post by ranadheer on Request to share documents about SoftPLC Extension SL CODESYS Forge talk (Post)
Hello Everyone Our team is planning to begin an industrial automation project and we are currently evaluating the use of SoftPLC Extension SL as a potential solution. As we are in the early stages and have yet to start the implementation, we kindly request access to official reference documents, technical manuals, and datasheets relating to SoftPLC Extension SL. Thank you very much for your assistance. We look forward to your response.
Last updated: 2025-10-18

Post by rossanoparis on After un upgrade of "CODESYS Control for Raspberry Pi MC SL" from v4.7 to v4.9 SysFileOpen function stopped working CODESYS Forge talk (Post)
Hello at all. After un upgrade of "CODESYS Control for Raspberry Pi MC SL" from v4.7 to v4.9 SysFileOpen function stopped working. I'm not able to read or write files from the PLC application. Before this upgrade all worked fine. I've read this thread [ https://forge.codesys.com/forge/talk/Engineering/thread/3da9ded84e/ ] Despite I followed that indications I couldn't get my code working again. Perhaps I'm missing something or I didn't understand how to use placeholders at all. Is there a different syntax to use for "SysFileOpen" in order to use placeholders? Thanks in advance for your help. Information Compiler: CODESYS V3.5 SP19 Patch 2 Runtime: codesyscontrol 4.9.0 HW: KUNBUS RevPi Connect S Below the paths I want to access (The entire CODESYSControl_User.cfg file is attached) [SysFile] PlaceholderFilePath.1=/home/pi/hpca/bin, $hpcabin$ PlaceholderFilePath.2=/home/pi/hpca/cfg, $hpcacfg$ PlaceholderFilePath.3=/home/pi/hpca/logs, $hpcalogs$ PlaceholderFilePath.4=/home/pi/hpca/resources, $hpcares$
Last updated: 2023-08-22

Post by peterkcontrols on Codesys Network driver install for Codesys Control RTE x64 CODESYS Forge talk (Post)
Hello I am trying to download my project onto my Codesys Control RTE x64 soft PLC. and I have had an issue when downloading. [FATAL ERROR] Unresolved reference: 'SYSETHERNETADAPTEROPEN' [FATAL ERROR] Unresolved reference: 'SYSETHERNETADAPTERCLOSE' [FATAL ERROR] Unresolved reference: 'GETNUMBEROFADAPTERS' [FATAL ERROR] Unresolved reference: 'GETADAPTERINFO' [FATAL ERROR] Unresolved reference: 'SYSETHERNETIPFRAMERECEIVE' [FATAL ERROR] Unresolved reference: 'SYSETHERNETETHFRAMESEND' [FATAL ERROR] Unresolved reference: 'SYSETHERNETETHFRAMERECEIVE' [FATAL ERROR] Unresolved reference: 'SYSETHERNETIPFRAMESEND' [FATAL ERROR] Unresolved reference: 'SYSETHERNETFRAMERELEASE' Looking on the forum I have found other people had to install the network driver, which I have done following this youtube video by codesysGroup: https://youtu.be/10oj4wABaKc?si=664l83JXUGQSDlAe I have added the network driver, please see attached image. I have checked my BIOS to make sure my secure boot status is disabled, see attached image. when I go to component manager, the drop down menu doesnt have the new network adapter, see attached image. I have not yet purchased or installed any licenses is that what I am missing? What other reason is there that I can't download to the runtime. Thanks
Last updated: 2025-03-18

Post by fizzy-bubblech on 3.5 P20 hangs - no response CODESYS Forge talk (Post)
Colleagues, i have the same problems. At the current time, I have to use the new version of the Codesys (3.5.20.10) + Control for Linux SL 4.11.0.0, but it works unstable : theree are a lot of freezes and not-respondings. I tested this on different projects: those that were created in the current version of the project, and those that were migrated from other versions of the development environment. Compiling a project without connecting to a controller is fast enough. The first downloading of the code into the controller, too. But as soon as you need to make edits and download a new code problems begin. Codesys "freezes" at the "Generation code" stage for 15-20 minutes. And only after that time loads the code into the controller. Previously, we used version 3.5.17.60 + Control for Linux SL 4.7.0.0. The process took 1-2 minutes. Do you have any ideas how can i fix it? I will be grateful for your answers.
Last updated: 2024-06-27

Post by rmaas on Fieldbus has lost synchronicity CODESYS Forge talk (Post)
Hi, On a gantry system with 2 axis i am getting the following error: SMC_DI_FIELDBUS_LOST_SYNCRONICITY This happens random, sometimes it happens every 5 minutes and sometimes no error for 2 hours... The Setup: - Using codesys 3.5 SP20 with all latest libs... - Kontron AL Pi-Tron CM4 with Preempt realtime patch (Raspberry Pi 4) - Codesys runtime 4.11.0.0 (single core) - CODESYS Control for Raspberry Pi SL licensed - Softmotion + CNC + Robotics licensed - 2x Leadshine EL8-EC400 servo drives - Axis group for a 2-axis T-Gantry Ethercat network wiring: Ethercat master softmotion -> Beckhoff EK1100 -> Servo drive #1 -> Servo drive #2 Ethercat Cycle time = 4ms Max Jitter = 140~150 What i have tried so far: - changed the sync offset from 20% to 30% - changed ethercat task priority from 1 to 0 Running tasks: - Ethercat tast: Prio = 0, Interval = 4ms - Main task: Prio = 1, Interval = 8ms - Visu task: Prio = 31, Interval = 100ms - Softmotion planning task: Prio = 15, Freewheeling - 3 other default tasks that were created by AC_Persist Motion fb's are called in the ethercat task... Does anyone have an idea how to fix this? Any help is greatly appreciated!
Last updated: 2024-04-11

Post by atcprojectteam on Modbus Function Code 15, writing multiple coils CODESYS Forge talk (Post)
Hi all, I am using an RSTI-EP I/O card along with the EPXMBE101 Modbus/TCP network adapter. I have a Control Standard L license. I successfully connected to the I/O card via Modbus and can read inputs without any issues. However, when I try to write to the digital output modules using function code 15, I am unable to make any changes. Here’s what I have done so far: I created a small project using Structured Text. I set up Modbus channels (as shown in the attached image) and mapped the pins. When I use cyclic mode, the connection results in an error. However, when I use the rising edge, the connection works, but I don’t see any changes on the I/O card. For the output module, I assigned one bit to high. After that, I ran CODESYS Control Win V3. (Should I be running the PLC as well?) I built the program, but I am not receiving any response from the I/O card. Could you please advise on what might be causing this issue?
Last updated: 2025-02-26

Post by atcprojectteam on Modbus Function Code 15, writing multiple coils CODESYS Forge talk (Post)
Hi all, I am using an RSTI-EP I/O card along with the EPXMBE101 Modbus/TCP network adapter. I have a Control Standard L license. I successfully connected to the I/O card via Modbus and can read inputs without any issues. However, when I try to write to the digital output modules using function code 15, I am unable to make any changes. Here’s what I have done so far: I created a small project using Structured Text. I set up Modbus channels (as shown in the attached image) and mapped the pins. When I use cyclic mode, the connection results in an error. However, when I use the rising edge, the connection works, but I don’t see any changes on the I/O card. For the output module, I assigned one bit to high. After that, I ran CODESYS Control Win V3. (Should I be running the PLC as well?) I built the program, but I am not receiving any response from the I/O card. Could you please advise on what might be causing this issue?
Last updated: 2025-02-26

Post by eschwellinger on OPCUA Ctrl-Node fehlt CODESYS Forge talk (Post)
.. du schreibst Runtime 4.10 damit meinst du die PFC200 SL Runtime aus dem CODESYS Store?
Last updated: 2023-12-04

Post by eschwellinger on Raspberry Pi 5 CODESYS Forge talk (Post)
you could use either the PI package or Arm / Arm 64 SL packages on the PI
Last updated: 2025-01-27

Post by peterkcontrols on TargetVisu started in windowed or not full screen CODESYS Forge talk (Post)
Hello, I am using Codesys on an industrial pc with a single monitor. I would also like to have a separate vision software running on the PC and would like to display it half screen. When I run the soft PLC the my visualization screen appears full screen, I would like to be able to set the size of the visualization screen so I can display other software on the monitor. Is it possible to set the width/height of the targetVisu? Anyone try something similar? I would like to avoid having to put it on a Virtual Machine. Thank you
Last updated: 2025-02-26

Post by anooyoung on OpC UA server on Raspberry Pi MC SL - Certificate Issue CODESYS Forge talk (Post)
hi, having the same issue, did you find a resolution?
Last updated: 2025-05-23

Post by user0815 on Web Socket Client SL -Bibliothek Fehler CODESYS Forge talk (Post)
Sobald ich probiere eine Nachricht von Node-RED an Codesys zusenden.
Last updated: 2023-12-18

Post by eschwellinger on Web Socket Client SL -Bibliothek Fehler CODESYS Forge talk (Post)
bei welcher Aktion kommt dieses Fenster mit dem Source Code?
Last updated: 2023-12-18

Post by eschwellinger on Web Socket Client SL -Bibliothek Fehler CODESYS Forge talk (Post)
aber sind dann nicht auch exceptions im Log zu sehen?
Last updated: 2023-12-18

Post by user0815 on Web Socket Client SL -Bibliothek Fehler CODESYS Forge talk (Post)
So ich habe das Problem gelöst. Ich habe pData nicht mit einer Variabele vom Typ XWORD verbunden. Jetzt funktioniert die Kommunikation
Last updated: 2024-01-03

Post by eschwellinger on Zielsystem stimmt nicht mit dem verbundenen Gerät überein CODESYS Forge talk (Post)
na ja es gibt halt einfach die Möglichkeiten: 1. Man installiert Raspberry PI OS 32Bit -> dann geht PI SL und PI MC Multicore als Target 2. Man installiert Raspberry PI OS 64Bit dann muss es PI64Bit sein falls der Übersetzungsfehler nicht in einer Bibliothek ist (die du vielleicht nicht ändern kannst) https://faq.codesys.com/pages/viewpage.action?pageId=128253958 Hier der Hinweis was man tun muss das dein IEC Code für 32Bit als auch 64Bit Targets funktioniert Also entweder zurück auf Raspberry PI OS 32 Bit: nur zur Info noch was im Config file steht für welche Plattform/Produkt [CmpRasPi] Architecture=aarch64 (-> 64Bit PI) oder Architecture=armv7l (-> PI MC Multicore) oder Architecture=armv6l (-> PI SL Single Core)
Last updated: 2024-03-11

Post by mehmetembedded on Linux ARM64 SL, GPIO Access CODESYS Forge talk (Post)
Can you give more details about how i can make it happen please ? Thanks
Last updated: 2024-05-09

Post by eschwellinger on Codesyscontrol.service stoppt nach 30s CODESYS Forge talk (Post)
...du könntest Arm SL verwenden, falls es keine anderen Hardware Abhängigkeiten gibt.
Last updated: 2024-06-21

Post by tk096 on Motion FB Error CODESYS Forge talk (Post)
Hi, Softmotion Robotics does not support tracking in/out to dynamic coordinate systems with relative movements. Is MC_MoveLinearAbsolute an option? See SMC_RELATIVE_MOVEMENT_TRACKING_CS in https://content.helpme-codesys.com/en/libs/SM3_Error/Current/SM3_Error/SMC_ERROR.html Concerning the other error: Do you use any motion function blocks of SM3_Basic to move a single axis of the robot in your application?
Last updated: 2023-10-20

<< < 1 .. 44 45 46 47 48 .. 67 > >> (Page 46 of 67)

Showing results of 1657