Post by eschwellinger on Beckhoff CX9240 : Using Internal EtherCAT Bus
CODESYS Forge
talk
(Post)
you need just out of this windows rte cx package the internal EthercatMaster device description
Last updated: 2026-07-10
Post by timvh on Codesys Installation problem
CODESYS Forge
talk
(Post)
Instead of complete VM's, you could also create a sandbox installation using the CODESYS installer.
Last updated: 2026-08-10
Post by manuknecht on Persistence Manager does not save alphabetically first value
CODESYS Forge
talk
(Post)
Update: As of now (CODESYS V3.5 SP21 Patch 6) this Bug was fixed.
Last updated: 2026-08-12
Post by antonio011 on Request a dark mode for CODESYS
CODESYS Forge
talk
(Post)
Any updates on this? A dark mode is in most IDE state of the art already.
Last updated: 2026-01-21
Post by kambel on information security of CDS IDE 3.5.15.30
CODESYS Forge
talk
(Post)
Hello Please tell me if it is possible to hide information about devices in the Scan device window on pic.
Last updated: 2026-01-29
Post by nano on CODESYS and Github Copilot
CODESYS Forge
talk
(Post)
your Project is allways written in st? then have a look at the FBS from PDE. schould solve parts of the job
Last updated: 2026-02-11
Post by pernockham on Unable to deploy "Control for Linux SL 4.18.0.0"
CODESYS Forge
talk
(Post)
Thanks! Out of office, will check on Monday.
Last updated: 2026-02-19
Post by arj3090 on Linux ARM64 Deploy Fail - Index out of range
CODESYS Forge
talk
(Post)
This is the version shown in the CodeSys Installer.
Last updated: 2026-07-01
Post by dmb-fan on Attemp Convert old V2.3 projects : Error HRESULT: 0x80010105 (RPC_E_SERVERFAULT))
CODESYS Forge
talk
(Post)
Oldest possible Sandbox is not working (Converter blacklistet) Install of SP17 sucessfull. But Same error. And now?
Last updated: 2026-08-11
Post by gseidel on Mismatch between coordinate monitor and actual motion using SMC_GroupJog2, MC_MoveLinearAbsolute (6DOF)
CODESYS Forge
talk
(Post)
Hi darwin03, as can bee seen at the end of your video, the direction of rotation now seems correct for all axes. I can only guess, but the most likely reason are different denavit hartenberg parameters in the SoftMotion axis group editors and the robot used in the simulation tool. Maybe some arm lengths differ, maybe some offsets are given with opposite sign. I would again refer you to https://content.helpme-codesys.com/en/libs/SM3_Transformation/Current/SM3_Transformation/Function-Blocks/Standalone-Kinematics/Articulated-Robots/6AxisArticulated/Kin_ArticulatedRobot_6DOF.html. Please double check all parameters and the table of the DH parameters given there and compare that against the robot in the simulation tool. Also: did you configure any tool in CODESYS? I would suggest to simplify and remove any tools for finding the source of the wrong movements. Best regards, Georg
Last updated: 2026-10-16
Post by poliautomacao on Block the program upload
CODESYS Forge
talk
(Post)
Hello, how can I block the upload of my project so that no one can download my PLC program?
Last updated: 2026-10-21
Post by dantheman on Connecting to SoftPLC Only Works By Turning Off Modbus Ethernet Port
CODESYS Forge
talk
(Post)
I have an IPC with 2 ethernet ports and 1 Wi-Fi. I'm using ModbusTCP with the ethernet port named "enp2s0" connected to my remote I/O. This works fine when testing with Python and also works with CODESYS, but CODESYS is only able to scan for the Linux SoftPLC when I turn off the "enp2s0" interface. In other words, I can't get online with the IDE if I want my ModbusTCP comms to run with CODESYS. I'm using a Linux SoftPLC that has the following entry in CODESYSControl.cfg, hoping that this will allow me to connect with "enp1s0" or "wlp3s0", and leave "enp2s0" for field comms, but this seems to only make the source IP of the ModbusTCP comms to be bound to "enp2s0". That last point is the case only if I don't restart the service, but if I do restart the service after changing the config file, the source IP for the ModbusTCP comms then becomes the one for "enp1s0", which is very confusing to me: [SysSocket] Adapter.0.Name="enp2s0" Adapter.0.EnableSetIpAndMask=1 On the device list, I only have "enp2s0" given as the ethernet device that has the ModbusTCP master & slave beneath it, shown in Screenshot 1. On the IPC, I can ping the ModbusTCP client (remote I/O) from "enp2s0", and I've attached a Wireshark capture of running ModbusTCP from the CODESYS runtime as Screenshot 2, 3 & 4 (again, I can't get online when this is running, I have to turn off "enp2s0" to connect even when it's idle and I don't have an active TCP session with my Python tests). Like I explained above, the source IP is "enp1s0", even though the ethernet device on the project is "enp2s0". I was lucky to catch the red message that showed the source IP that makes sense to me (the one for "enp2s0"), but for some reason that connection was reset and I never saw that packet again. I've also tried this with Auto-reconnect both enabled & disabled, for the ModbusTCP Master device. I also have to turn off "enp1s0" and then turn it on, just so that I can have the ModbusTCP comms running from "enp2s0" (which is not intuitive in any way to me, I'd love some help understanding that phenomenon as well) in the weird manner that I've described above. I would be very appreciative if someone can help me figure out this pickle. I'd love to just connect to CODESYS through my Wi-Fi interface and leave my ethernet ports for field comms.
Last updated: 2024-08-01
Post by fless on No source code available for profinet library
CODESYS Forge
talk
(Post)
looks like you are running in a bug in the newest version 4.4.0 of the profinet library or the new library triggers a bug in your code. did you update your profinet device too? you could try to downgrade to an older version of the library. via library manager - placeholders, double click Profinet 4.4.0 in the library column and choose an older version.
Last updated: 2023-08-23
Post by fefefede on Error C0521 - unknow compiler
CODESYS Forge
talk
(Post)
Hello, i'm a new user of Codesys and student of ST program for PLC. Since today for a few new projects i have two error code C0521 and i can't solve. I also just try to update device and search library but nothign resolve. How can i fix this? Thanks
Last updated: 2023-09-02
Post by snhatton on Retain memory change to ZERO
CODESYS Forge
talk
(Post)
I think more information is needed to help solve the issue. Can you list the exact steps to reproduce the issue? What version of Codesys are you using? Did you add a persistentVars object to your project? I would recommend browsing all instances of the retain variable to see all possible writes to the variable in question.
Last updated: 2023-09-18
Post by snhatton on Alarm Management - latched variable represented as Text list
CODESYS Forge
talk
(Post)
Hi There, For my understanding: are you trying to display the contents of a text list in an alarm message based on the id? For example, you could maintain a text list of common alarm messages, and then display based on which message is true?
Last updated: 2023-09-18
Post by tk096 on Motion FB Error
CODESYS Forge
talk
(Post)
Hi, Softmotion Robotics does not support tracking in/out to dynamic coordinate systems with relative movements. Is MC_MoveLinearAbsolute an option? See SMC_RELATIVE_MOVEMENT_TRACKING_CS in https://content.helpme-codesys.com/en/libs/SM3_Error/Current/SM3_Error/SMC_ERROR.html Concerning the other error: Do you use any motion function blocks of SM3_Basic to move a single axis of the robot in your application?
Last updated: 2023-10-20
Post by rickj on Defining local variables that can be independent with several users.
CODESYS Forge
talk
(Post)
You need to create an array with one element for each possible user. I usually define these arrays in the root screen. FrameIndex : Array [0..MaxUsers] OF INT; Then use the global CurrentClientId (defined by one of the VISU libraries) to index the array element used to select the frame. FrameIndex[CurrentClientId]
Last updated: 2023-10-21
Post by sonnh on How to use more 4 instances of CANopen/Profibus/Modbus with The application-based license CODESYS Control
CODESYS Forge
talk
(Post)
The codesys application license allows the use of up to 4 fieldbus instances (eg Modbus). I need to use more instances than that. Can I use the Modbus library instead? Does this usage require a license? Similar to other libraries such as CanOpen, Modbus TCP...
Last updated: 2023-11-02
Post by talhaali on Adding a variable from text list into ST code
CODESYS Forge
talk
(Post)
Hi, can I use a entry of a text list as variable in structured text? for example in attach picture, if i use want to use data of first row. I am trying to write: A : STRING := TextList.Default.0; but it is not workings
Last updated: 2023-12-07
Post by talhaali on Adding a variable from text list into ST code
CODESYS Forge
talk
(Post)
Hi, can I use a entry of a text list as variable in structured text? for example in attach picture, if i want to use data of first row. I am trying to write: A : STRING := TextList.Default.0; but it is not workings
Last updated: 2023-12-07
Post by tk096 on Some 'pathetic' errors in SoftMotion program
CODESYS Forge
talk
(Post)
Hi, I suppose that you are referring to the error code "SMC_FB_WASNT_CALLED_DURING_MOTION"? Starting of Softmotion version 4.15.0.0 the instance path of the function block that has not been called is logged into the device log. This might help you to identify why it has not been called.
Last updated: 2024-07-18
Post by timvh on Array to String
CODESYS Forge
talk
(Post)
The new (UTF8) string library is faster and can handle large strings. https://content.helpme-codesys.com/en/CODESYS%20String%20Libraries/_strlib_start_page.html PS, in CODESYS, the maximum string length is not 255 characters. The String functions of the standard library are limited to strings of 255 characters. But you can use other (memory) functions to handle strings larger than 255 characters.
Last updated: 2024-07-22
Post by dantheman on Connecting to SoftPLC Only Works By Turning Off Modbus Ethernet Port
CODESYS Forge
talk
(Post)
I've also noticed that when I turn off "enp1s0", suddenly the source IP for the ModbusTCP changes to that of "enp2s0", which is what makes sense to me. When I turn it back on, the source IP remains that of "enp2s0".
Last updated: 2024-08-01
Post by tk096 on gear over gear (2 masters,1 slave) - how to do it?
CODESYS Forge
talk
(Post)
Hi, you could calculate the position/dynamics of the slave axis yourself and use one of the function blocks SMC_FollowPosition/SMC_FollowSetValues to move the slave axis. https://content.helpme-codesys.com/en/libs/SM3_Basic/Current/SM3_Basic/POUs/Movement/Direct/SMC_FollowPosition.html https://content.helpme-codesys.com/en/libs/SM3_Basic/Current/SM3_Basic/POUs/Movement/Direct/SMC_FollowSetValues.html
Last updated: 2024-08-19
To search for an exact phrase, put it in quotes. Example: "getting started docs"
To exclude a word or phrase, put a dash in front of it. Example: docs -help
To search on specific fields, use these field names instead of a general text search. You can group with AND or OR.