Post by dkugler on Management of a PLC network from a remote station CODESYS Forge talk (Post)
I would figure out, how to create a simple html webpage with 2 frames. One frame with buttons to select the plc. A second frame with hyperlink to the webvisu of the plc ("XXX.XXX.XXX.XXX:8080/webvisu.htm"). Selecting other PLC Button has to change the hyperlink in 2. frame. Costs only some time to figure out :-) Or setup a raspberry Pi with small visualization. Set up a button for each plc and add one browser element. Each button writes the URL of the depending plc to the URL setting of the browserelement. Costs 55€ for runtime licence and a Raspberry Pi.
Last updated: 2023-12-04

Post by pernockham on Linking to IO during runtime with hot swap? CODESYS Forge talk (Post)
I have a project where a single PLC shall control multiple nodes (up to 10 units?) with IO connected through profinet. Ideally each node should be identical however with time I see situations were different setups/configurations will be used. Codesys PLC (GVLs) |Profinet | |--PNIO-node-1--| | | AIO, | | DIO, | | CNT etc. | |--PNIO-node-2--| | | AIO, | | DIO, | | CNT etc. Ideally I think of a configuration through yaml/xml-files (the assignment/linking of the profinet nodes towards GVL-variables in the PLC as well as scaling, channel configration etc.). Would be grateful if someone could suggest library/-ies that can handle the following: - Verify what IO is connected to a device/node. - Hot-swap/assign link for IO towards GVLs, either automatically or through a HMI.
Last updated: 2024-10-11

Post by gediminas on Datasource OPC UA client system failure CODESYS Forge talk (Post)
I am using CODESYS v3.5 SP20 Patch 3 / Control for BeagleboneBlack SL v4.13 and after some time the OPC UA Server crashes. However, Runtime still works without any issues. The events leading up to the OPC server crash are the most suspicious: 1) Mutex deadlock detected - owner thread died, and 2) Runtime received SIGABRT. And it seems very similar with this topic except used versions - issues should be fixed with previous SP's. I can't seem to find any information about these events. Need some pointers in the right direction on how I can fix this problem.
Last updated: 2024-10-25

Post by sigurdrb on Codesys and error messages, warnings exceptions etc. CODESYS Forge talk (Post)
Hi, I tried some different libraries (CmpApp etc.) to find some global variables that I could read out as a variable in the codesys environment. Do any one of you know which libraries are best suited for this, and how I can read it out? My goal is to send messages, warnings etc. to the system that communicates to the PLC. Currently if something goes wrong I need to see the logfiles, or go online with the controller. I think I could save a lot of time if I could read the errors from our user interface that is connected to the PLC by TCP/IP.
Last updated: 2024-11-06

Post by dkugler on Project loses 'Download time' information CODESYS Forge talk (Post)
and if you copy or transfer a project to another place, copy not only the .project, copy .compileinfo .bootinfo and .bootinfo_guids then we figured out it is more often possible to go online without full download. If you build an archiv and extract it, some of this files are missing and login isn't possible without download. I work with V3.5 SP16 Patch 4. I don't know if this problem of the archiv is solved in newer Versions/SP's and I don't know what the problem of Codesys is to help out a lot of programers of this very annoying problem or at least help with a workaround
Last updated: 2025-09-18

Post by i-campbell on What does CODESYS expect to do when I get such an error message CODESYS Forge talk (Post)
you need to get the addons that the person that programmed it used. I always store an .installation-config file alongside the project. If you have lost that, then it gets a bit of a headache: I think even with SP18 you can hit yes to open it anyway, and it will suggest which addons it thinks are missing, if you double click the yellow "missing-addons" in the status bar. If you know you have the right addons, you can do a "Save As.." and it will write your current addon list to the file, and you wont get the error next time.
Last updated: 2024-01-08

Post by sumit on Not able to see input data coming from eip adapter on codesys CODESYS Forge talk (Post)
dhumphries, I changed the datatype this time from BYTE to USINT (because that's what my adapter is sending: array of uint8_t). The text "New Help String" you saw in previous screenshots is just the description of the input/s (it can be anything). I also looked into the logs (see attached) for that ! sign next to the device, I found that connection is being timeout. I tried some suggestions from online such as increase the RPI but still got connection timeout issue, also by changing the datatype, I still don't see incoming data from the adapter, although its visible on wireshark. thanks,
Last updated: 2024-03-07

Post by jrsantab on Remote connection to ifm PLC & HMI CODESYS Forge talk (Post)
Hello, We are trying to access remotely a PLC (ifm 711S) and a HMI (ifm CR1077). Both are connected to a Teltonika RUT200 router. We establish the connection with OpenVPN Connect and can ping both controllers. We have a laptop that, most of the time, will allow Codesys connection to the controllers, but we have several other computers that are unable to connect, although all of them can ping successfully. We cannot find any difference in the configuration or software installed from one PC to another. If we connect to the router by WIFI, instead of VPN, all the computers work fine. We know that scanning the network will not work over a remote connection, so we input the controller IP directly. Has anyone had a simlar problem and can offer any hint on what to check to meke the connection run?
Last updated: 2024-04-11

Post by jrsantab on Remote connection to ifm PLC & HMI CODESYS Forge talk (Post)
Hello, We are trying to access remotely a PLC (ifm 711S) and a HMI (ifm CR1077). Both are connected to a Teltonika RUT200 router. We establish the connection with OpenVPN Connect and can ping both controllers. We have a laptop that, most of the time, will allow Codesys connection to the controllers, but we have several other computers that are unable to connect, although all of them can ping successfully. We cannot find any difference in the configuration or software installed from one PC to another. If we connect to the router by WIFI, instead of VPN, all the computers work fine. We know that scanning the network will not work over a remote connection, so we input the controller IP directly. Has anyone had a similar problem and can offer any hint on what to check to make the connection run?
Last updated: 2024-04-11

Post by danwoodlock on Rpi zero w lost license after 4.11 update CODESYS Forge talk (Post)
Hello all, Encountered an issue with my zero which seems to have happened after the 4.11 update. It now runs in demo mode (2hr) and I am trying to see what the appropriate steps are prior to contacting codesys directly. Background: I recently did a fresh install of w11 on my pc, so it seems "c:\ProgramData\CODESYS\Licenses\" only has information related to my pi5, which I licensed just this past Friday. I have all my license documentation about my rpi zero as far as the emails received, but when I try to claim using the ticket number it says its already been used, or something to that effect, which it was. Currently trying to perform device license reader, which is taking some time.
Last updated: 2024-04-14

Post by k2saki on CNC / G-Code streaming processing ( to start quickly in long G-Code File ) CODESYS Forge talk (Post)
Is it possible like G-Code streaming processing (like FANUC or SIEMENS DNC Function )? Or Does anyone know the tips for CODESYS Motion to start moving long Long G-Code File quickly? I have to wait long time after "Start" button to start moving, I have to wait finishing interpreting whole G-Code file, ( and I have to prepare huge buffer to store. ) Now, I'm working on my CNC Project using SMC_ReadNCFile2, and SMC_NcInterpreter to preprocess G-Code. I tried to set SMC_Interpolator.xExecute to true to Start while after SMC_NcInterpreter processed more 50-line of G-Code, but that not worked, I had to wait SMC_NcInterpreter processed all lines to start SMC_Interpolator. G-Code have about 2000 lines of XY of G01 (or more over.. ) of short segment that a CAM software has exploded from NURBS Curve.
Last updated: 2024-05-03

Post by jens on Modbus tcp - channel CODESYS Forge talk (Post)
Help wanted This is the first time i'm doing a Modbus Tcp project. I have some VLT with a extension module MCA-122. i'm currently unable to write to the VLT slave, but i can read from status word parameter=1603 and address := 16029 where the address is calculated from parameter is ((id x 10)-1). in the manual the functions that are supported are 3 hex, 6 hex, 10 hex, b hex and 11 hex. read holdin registers, write single register, write multiple registers, get comm. event counter, report slave id. i'm only using the Modbus Slave Channel is this wrong when trying to write to the vlt ?
Last updated: 2024-06-13

Post by tayhim on WAGO HMI Device not found CODESYS Forge talk (Post)
Hello, I'm trying to connect with a Wago TP600 HMI but without success. I'm using codysis 3.5 SP19 patch 7 (SP20 block all the time) and the official wago package is installed. However, when I scan and select my device, I get a message saying that the device doesn't match the project's device object with the possibility to update the device (as shown in the attached picture). however, after choosing to update i got a message that the device is not found. I've tried with a new empty project but the same results. do you have any ideas? Thanks.
Last updated: 2024-06-25

Post by timvh on CPU + EtherCAT redundancy CODESYS Forge talk (Post)
It works well with two Wago 750-8210's. I helped a few customers setting this up. But it should work with any device which can control EtherCAT I/O, is real-time and has sufficient network interfaces. Two network adapters can be used to create a redundant EtherCAT network (you need 2 additional switches for this). The other network adapters can be used to interconnect the 2 PLC's (synchronization). We noticed that if you exchange variable lists that there could be some issues if you have long lists. So what we did is use a SoftPLC on a server that contains all the settings which continuously sends network packages (GVL sender) and which is received by both PLC's (network receiver). Switching over is done in milliseconds. The bus doesn't notice the change-over. EtherCAT communication works flawlessly.
Last updated: 2026-01-30

Edgelogix-rpi-1000-cm4102032 SPI port connection to PiFace I/O Driver in CodeSys. CODESYS Forge talk (Thread)
Edgelogix-rpi-1000-cm4102032 SPI port connection to PiFace I/O Driver in CodeSys.
Last updated: 2023-08-21

How to configure CODESYSControl_User.cfg in order to use a specific network card for OPCUA Server CODESYS Forge talk (Thread)
How to configure CODESYSControl_User.cfg in order to use a specific network card for OPCUA Server
Last updated: 2023-08-28

When Keyboard Key is in Hold, then Webvisu is extreme slow and latent CODESYS Forge talk (Thread)
When Keyboard Key is in Hold, then Webvisu is extreme slow and latent
Last updated: 2023-09-20

Bug in LD/FBD editor - ModbusFB.ClientRequest does not show ETrigTo-inherited variables CODESYS Forge talk (Thread)
Bug in LD/FBD editor - ModbusFB.ClientRequest does not show ETrigTo-inherited variables
Last updated: 2022-12-04

Linie mit einem variablen P. sowie Rechteck nur in x-wachchs CODESYS Forge talk (Thread)
Linie mit einem variablen P. sowie Rechteck nur in x-wachchs
Last updated: 2013-10-11

How do I list the folder names found in a PLC Directory? CODESYS Forge talk (Thread)
How do I list the folder names found in a PLC Directory?
Last updated: 2015-05-07

how to run the machine using CNC editor in codesys CODESYS Forge talk (Thread)
how to run the machine using CNC editor in codesys
Last updated: 2007-10-24

Aufrufen von Scripten (Python) aus CODESYS. Beschreiben von globalen Variablen in Codesys durch Script CODESYS Forge talk (Thread)
Aufrufen von Scripten (Python) aus CODESYS. Beschreiben von globalen Variablen in Codesys durch Script
Last updated: 2017-09-10

Read values in V3.5 SP9 Patch 5 vs V3.5 SP13 Patch 2 CODESYS Forge talk (Thread)
Read values in V3.5 SP9 Patch 5 vs V3.5 SP13 Patch 2
Last updated: 2019-02-11

How to intercept a variation in the RetainPerstist variables (for saving to file) CODESYS Forge talk (Thread)
How to intercept a variation in the RetainPerstist variables (for saving to file)
Last updated: 2018-08-03

Is it possible to replace a table row header for a text in a text list? CODESYS Forge talk (Thread)
Is it possible to replace a table row header for a text in a text list?
Last updated: 2021-10-21