Thanks Georg, that fixed it.
This worked for me. I had four identical PLC's. Three of them worked just fine with 255.255.255.255 as the broadcasting address but the 4th would not update the variables. Changed it to 192.168.x.255 and everything worked.
Vijeo doesn't support TIME variables, so the easiest thing to do is convert to a STRING in your program, and use that variable. You could use TimeAsString:= TIME_TO_STRING(TimeVar) to get a string that looks like this: T#5h10m45s200ms
Hi. I'm trying to show in Vijeo Designer a timer countdown. But I want to display the data in hour, minutes and seconds. I tried to change the data by converting in the Machine Expert but not able to succeed. Can you help me to find a solution? Regards, FG
Since version 19 they changed how file access is handle. There are two solutions: 1. You change where the file is stored (need to go to: /PlcLogic/) 2. You can, if you don´t want to store at PlcLogic, add the following line in the CODESYSControl.cfg under [SysFile]: ForceIecFilePath=0 The CodesysControl.cfg is at C:\ProgramData\CODESYS\CODESYSControlWinV3x64\xxPROJECT_NUMBERxx\ Here the email they sent me: "with the 3.5.19 Version we changed how files are handled. See following issue: CDS-81506 -...