We have finally solved the problem. The version of the Gateway in the computer that worked (3.5.11.0) and the one that didn't (3.5.17.30) was different. We have three different Codesys 3.5 versions installed because we work with different controllers. I believe that, depending on the sequence you follow to install the versions you get a different Gateway version. To solve the problem you first have to disable the "obsolete" services. Open services, serach for (in our case) CODESYS Gateway V3 Version...
We have finally solved the problem. The version of the Gateway in the computer that worked (3.5.11.0) and the one that didn't (3.5.17.30) was different. We have three different Codesys 3.5 versions installed because we work with different controllers. I believe that, depending on the sequence you follow to install the versions you get a different Gateway version. To solve the problem you first have to disable the "obsolete" services. Open services, serach for (in our case) CODESYS Gateway V3 Version...
Hello, We are trying to access remotely a PLC (ifm 711S) and a HMI (ifm CR1077). Both are connected to a Teltonika RUT200 router. We establish the connection with OpenVPN Connect and can ping both controllers. We have a laptop that, most of the time, will allow Codesys connection to the controllers, but we have several other computers that are unable to connect, although all of them can ping successfully. We cannot find any difference in the configuration or software installed from one PC to another....
Hello, We are trying to access remotely a PLC (ifm 711S) and a HMI (ifm CR1077). Both are connected to a Teltonika RUT200 router. We establish the connection with OpenVPN Connect and can ping both controllers. We have a laptop that, most of the time, will allow Codesys connection to the controllers, but we have several other computers that are unable to connect, although all of them can ping successfully. We cannot find any difference in the configuration or software installed from one PC to another....
Hello, We are trying to access remotely a PLC (ifm 711S) and a HMI (ifm CR1077). Both are connected to a Teltonika RUT200 router. We establish the connection with OpenVPN Connect and can ping both controllers. We have a laptop that, most of the time, will allow Codesys connection to the controllers, but we have several other computers that are unable to connect, although all of them can ping successfully. We cannot find any difference in the configuration or software installed from one PC to another....