Post by micik on Reverse bytes in an array
CODESYS Forge
talk
(Post)
Hello, I'm getting the data in Codesys that is an array of 8 bytes. From this array, I need to foram LREAL number, however, because of different endiannes I need to reverse bytes in this array and then copy to a LREAL variable. For this I'm using a loop and it works OK. I wonder if there is a built in function to do this. I have found CAA Memory library but it has functions like reverse bytes in DWORD. But it seems it doesn't have what I need. https://content.helpme-codesys.com/en/libs/CAA%20Memory/Current/CAA_Memory/Reverse-Bit-Swap-ByteWord-order/ReverseBYTEsInDWORD.html What I need is a function to reverse bytes in an 8 byte array, or something similar.
Last updated: 2024-08-22
Post by micik on Reverse bytes in an array
CODESYS Forge
talk
(Post)
Hello, I'm getting the data in Codesys that is an array of 8 bytes. From this array, I need to foram LREAL number, however, because of different endiannes I need to reverse bytes in this array and then copy to a LREAL variable. For this I'm using a loop and it works OK. I wonder if there is a built in function to do this. I have found CAA Memory library but it has functions like reverse bytes in DWORD. But it seems it doesn't have what I need. https://content.helpme-codesys.com/en/libs/CAA%20Memory/Current/CAA_Memory/Reverse-Bit-Swap-ByteWord-order/ReverseBYTEsInDWORD.html What I need is a function to reverse bytes in an 8 byte array, or something similar.
Last updated: 2024-08-22
Post by fless on FB having single input but initialized with Array
CODESYS Forge
talk
(Post)
Why will it retain the sum value from the last call? This is how PLC work. Usually variables only get initialized after a download or a reset (i.e. power loss). RETAIN variables are saved in a special kind of RAM and keep their value after a power loss. To initialize variables on every call of your FB use the VAR TEMP block. VAR_TEMP sum : INT; END_VAR
Last updated: 2024-05-07
Post by timvh on Limiting Memory Access of an Array to Within its Bounds
CODESYS Forge
talk
(Post)
Add the object "POU for Implicit Checks" to your application, then select "Bounds check". This will create a function which is automatically called each time an array is write accessed. In the function you can handle "out of bounds" situations. By default it will be limited to its lower or upper bound.
Last updated: 2024-03-06
Post by wiresplus on INT_TO_WORD function not working
CODESYS Forge
talk
(Post)
Hello, I need to take an INT input, and convert it to a WORD value. VAR DRV2Speed : WORD; //IO card takes a WORD where 16000 = full 10V output (equivalent to 50Hz) PumpFillSpeed : INT; //Users enter a value between 0 and 50 END_VAR IF <conditions> THEN DRV2Speed :=INT_TO_WORD((PumpFillSpeed/50)*16000); END_IF </conditions> According to me this should work - but it stays at 0, no matter what. What am I doing wrong?
Last updated: 2024-01-26
Post by leon78 on Codesys 3.5 SP17 Patch 2 CheckBounds (POUs for Implicit Checks)
CODESYS Forge
talk
(Post)
Hello! I use CheckBounds (POUs for Implicit Checks). But I have a problem. I use an array as an VAR_IN_OUT of Function Block. If I try to monitor the array of variable length ([* ]), its does't work. The CheckBounds POU isn't called. If I use the array of fixed lenght ([lower..upper]), the CheckBounds POU is called. Why?
Last updated: 2023-11-14
Post by leon78 on Codesys 3.5 SP17 Patch 2 CheckBounds (POUs for Implicit Checks)
CODESYS Forge
talk
(Post)
Hello! I use CheckBounds (POUs for Implicit Checks). But I have a problem. I use an array as an VAR_IN_OUT of Function Block. If I try to monitor the array of variable length ([* ]), its does't work. The CheckBounds POU isn't called. If I use the array of fixed lenght ([lower..upper]), the CheckBounds POU is called. Why?
Last updated: 2023-11-14
Post by gurkan on OPCUA array max length?
CODESYS Forge
talk
(Post)
We are using codesys 3.5.16.30 and we have a array with strings of length 5000. We are having issues subscribing to this variable from an OPCUA client. Is there any limit in the OPCUA Server in codesys for how long an array can be on the opcua server?
Last updated: 2024-02-16
Post by alexgooi on Init Array input on a method
CODESYS Forge
talk
(Post)
Dear Forum, I would like to initialize an array input on a method. When I do this, I get the following error: "The type of ARRAY [1..2] OF BOOL cannot have a default value in this context." I attached a picture for more clarity. Is this simply not possible or is there a different way of tackling this problem? Thank you in advance
Last updated: 2024-02-26
Post by gurkan on OPCUA array max length?
CODESYS Forge
talk
(Post)
2000 works. When testing with UA Expert there is a timeout from the OPCUA Server when trying to subscribe to the variable CPU do not seems to be to affected. The memory(RAM) however is building up
Last updated: 2024-02-19
Post by hazarath on How extract JSONElement containing Array data
CODESYS Forge
talk
(Post)
I want to extract each element of an Array. Can someone help me with this. When I use JSONElementToString (part of JSON Utilities SL), I am seeing output as "ARRAY" instead of actual data. Here is the JSON content that I want to read : { "value1Unit": { "units": "M" }, "data": { "stepSize": 300.23, "points": [6,8] } } I would like to read each item of the element "points" i.e. 6 and 8. Here is the code I used, // Reading the content as JSON reader ( xExecute := execute , pwData := ADR ( converted_value ), jsonData := jsonDataStorage ); // Get the JSON Element jsonDataStorage.FindFirstValueByKey( wsKey := fidKeyVar, diStartIndex := searchElem, jsonElement => jsonElement ); JSON.JSONElementToString ( element := jsonElement , wsResult := valueWstring ); The content of the output of valueWstring is shown as "ARRAY" instead of the array items i.e. 6 and 8 Please can someone help me.
Last updated: 2024-07-30
Post by voffi on Converting UINT into bytes and converting 2Bytes into UINT
CODESYS Forge
talk
(Post)
There are some ways. One is to use SHR and SHL and it depends on your byte order in the data array. For Motorola byte order: PROGRAM PLC_PRG VAR u : UINT; byte_array_in : ARRAY [1..8] OF BYTE := [16#11, 16#12, 16#13, 16#14, 16#15, 16#16, 16#17]; byte_array_out : ARRAY [1..8] OF BYTE; END_VAR u := SHL(TO_UINT(byte_array_in[2]), 8) + TO_UINT(byte_array_in[1]); byte_array_out[1] := TO_BYTE(u); byte_array_out[2] := TO_BYTE(SHR(u, 8)); If it's Intel byte order just change 1 and 2 in the array indexes.
Last updated: 2023-12-07
Post by kislov on Table How to set row number from 1 ( not from 0)
CODESYS Forge
talk
(Post)
Use declaration with ARRRAY [1..x] instead of ARRAY [0..x]
Last updated: 2024-05-27
Post by duvanmoreno24 on Modbus writing on value change
CODESYS Forge
talk
(Post)
Yes, I tried to do what you put in the first code. However, I have a problem with that and that is that the inputs must be declared with the type. I have many data types running in my code (real, int, uint, bool) and I can't put them in the same function, another thing is that I need to instantiate that function for everything I want to write to the slave. You put a for to 200 but it means that it has to be the same data type and inside the array, but I want to get them individually. I'm struggling to do it in a good and efficient way like wago's E-cockpit does. in the first screenshot you can see, you simply type in value, change the package of things you want to write in value change and it does everything by itself automatically, without comparing any old and new values and even less having the need to activate a bool. , it is perfect.
Last updated: 2024-04-03
Post by bjarne-pagaard on Multiple WebVisu
CODESYS Forge
talk
(Post)
You can use the switch frame variable, but there should be a variable for each active visu user. You can put the switch frame variable in an array, and use CURRENTCLIENTID as index into the array to get what you want. The CURRENTCLIENTID is assigned to new users automagically by the Visu Management.
Last updated: 2024-03-14
Post by tvm on Function block method default arguments
CODESYS Forge
talk
(Post)
This works for me in Schneider Machine Expert 2.2, which is based on Codesys 3.5.19. It did not work in Machine Expert 2.1, which was based on Codesys 3.5.16. METHOD PUBLIC Method1 : INT VAR_INPUT TestVar: INT:= 5; END_VAR Method1:= TestVar; PROGRAM SR_Main VAR TestFB: TEST_FB; Var1: INT; END_VAR Var1:= TestFB.Method1();
Last updated: 2024-01-04
Post by rodberna on Library for arrays
CODESYS Forge
talk
(Post)
Hi, I'm creating a program where I need to handle arrays, like: - Declare lenght variable arrays - [array(1..var) of "sometype"]. This is not possible in pure codesys, right? - Know array lenght, min, max, avg values in runtime - append/delete itens in an array - and so on Is there a library know for this in codesys. Is it possible to build our own libraries using some high level language like python or java script?
Last updated: 2024-01-10
Post by szotyi on Array of Program
CODESYS Forge
talk
(Post)
Hi! What is the proper and the easiest way to call programs through looping of array of programs, or pointer of program? instead of calling the programs one by one: prog1(inputX: 11); prog2(inputY: 12); prog3(inputZ: 13); similar like: VAR programsToCall : ARRAY [1..3] OF PROGRAM; END_VAR programsToCall[1] := prog1(inputX: 11); programsToCall[2] := prog2(inputY: 12); programsToCall[3] := prog3(inputZ: 13); FOR i := 1 TO 3 DO programsToCall[i] (); END_FOR Thanks.
Last updated: 2024-08-28
Using a method called from opcua fill an specific array position
CODESYS Forge
talk
(Thread)
Using a method called from opcua fill an specific array position
Last updated: 2022-02-18
addressin an array of byte containing bits of type bool
CODESYS Forge
talk
(Thread)
addressin an array of byte containing bits of type bool
Last updated: 2018-11-14
How I should define a huge size byte array in CoDeSys V3?
CODESYS Forge
talk
(Thread)
How I should define a huge size byte array in CoDeSys V3?
Last updated: 2013-05-09
Pass the second array dimension into a function as a parameter
CODESYS Forge
talk
(Thread)
Pass the second array dimension into a function as a parameter
Last updated: 2022-05-10
Targetvisu: Einem als Frame eingebundenem Visuelement ein array als In_out übergeben
CODESYS Forge
talk
(Thread)
Targetvisu: Einem als Frame eingebundenem Visuelement ein array als In_out übergeben
Last updated: 2020-05-11
Bug found? Weird behaviour of Combobox (Array and Integer) in CodeSys 3.5SP16 Patch 2 (64bit) Visu
CODESYS Forge
talk
(Thread)
Bug found? Weird behaviour of Combobox (Array and Integer) in CodeSys 3.5SP16 Patch 2 (64bit) Visu
Last updated: 2021-11-02
[SOLVED] Install ESI file: Index was outside the bounds of the array
CODESYS Forge
talk
(Thread)
[SOLVED] Install ESI file: Index was outside the bounds of the array
Last updated: 2017-12-15
To search for an exact phrase, put it in quotes. Example: "getting started docs"
To exclude a word or phrase, put a dash in front of it. Example: docs -help
To search on specific fields, use these field names instead of a general text search. You can group with AND
or OR
.