Post by spoun on Problem with edge gateway config mode
CODESYS Forge
talk
(Post)
Hello, i want to connect my automation server and i follow the steps as desribed in the video series(https://www.youtube.com/watch?v=iiPKyyO4M00&list=PLaws15OZmd7Uu2W23zX2w424aI3TrOfHf) and also that guide (https://content.helpme-codesys.com/en/CODESYS%20Automation%20Server/_cas_add_plc_to_server.html). When i go to "Allow Edge Gateway configuration.." from the Codesys gateway Systray running i get the message in the attached picture, so i open the Gateway.cgf but the file doesn't contain an cmpedgegateway section as mentioned in the message. I have installed all the latest versions codesys and of the components mentioned in the guides. How can i solve that problem?
Last updated: 2024-10-21
Post by richard-wang on Codesys recipe manager - what does it do?
CODESYS Forge
talk
(Post)
Hi All Thanks for sharing this information. For whom may not know why always get error code 16#4000 or 16#4002 while performing Recipe commands, the root cause is There is a line need to be inserted in CODESYSControl.cfg file, which is PlaceholderFilePath.1=/var/opt/codesys/PlcLogic/ I am using Pi, therefore the above path is set to my pi unit, after adding above line to my cfg file, all the Recipe commands work fine. But I still do not know how and when this file got modified though.
Last updated: 2024-04-29
Post by micik on How to generate an "ENI" file
CODESYS Forge
talk
(Post)
That really depends on this third party software you want to use. It is possible that .xml file generated with "Generate EtherCAT XML" will not be recognized as valid ENI file. Anyway, "Generate EtherCAT XML" command is not available through standard menus and needs to be added via Tools->Customize and then Add Command. You'll find it under "Devices" section. If you provide more info, we might be able to help you further.
Last updated: 2024-08-09
Post by jst69 on Python script: Launch Codesys, Execute Script, Exit Codesys
CODESYS Forge
talk
(Post)
Dear all: Question about scripting: I am creating a .NET program that is supposed to Open codesys, open template project, export a bunch of pou, then exit codesys. Launch works, Open project works, Export works, But how do i tell codesys to close itself? I can tell windows to terminate codesys, but i would prefer to do it properly. from __future__ import print_function import sys import System proj = projects.primary # We're interested in POU nodes: POUGuid = Guid("6f9dac99-8de1-4efc-8465-68ac443b7d08") # We collect all POU nodes in that list. pous = [] # From the parent node on, we recursively add POU nodes: def CollectPous(node): if node.type == POUGuid: pous.append(node) else: for child in node.get_children(): CollectPous(child) # Now we collect all the leaf nodes. for node in proj.get_children(): CollectPous(node) # We print everything just to know what's going on. for i in pous: print("found: ", i.type, i.guid, i.get_name()) # And now we export the files. for candidate in pous: # We create a list of objects to export: # The object itsself objects = [candidate] # And sub-objects (POUs can have actions, properties, ...) objects.extend(candidate.get_children()) # And the parent folders. parent = candidate.parent while ((not parent.is_root) and parent.is_folder): objects.append(parent) parent = parent.parent # Create an unique file name: if len(sys.argv) == 1: filename = "parent\\%s.export" % (candidate.get_name()) else: filename = "%s\\%s.export" % (sys.argv[1],candidate.get_name()) # print some user information print("exporting ", len(objects), " objects to: ", filename) # and actually export the project. proj.export_xml(objects, filename) proj.close() print ("script finished.") System.exit(0) // Dont work .NET: public static void Export(string path,string proj) { if (checkSettings()) { var p = new System.Diagnostics.Process(); p.StartInfo.FileName = Properties.Settings.Default.CSVersion +"\\CODESYS\\Common\\CODESYS.exe"; p.StartInfo.Arguments = " --Profile=" + qoute(Properties.Settings.Default.CSProfile) + " --culture=en" + " --project=" + qoute(path + "\\" + proj) + " --runscript=" + Properties.Settings.Default.LastOpenProjectPath + "\\INPUT_DATA\\SCRIPT\\Export.py" + " --scriptargs:" + qoute(path) ; p.StartInfo.RedirectStandardOutput = true; p.StartInfo.UseShellExecute = false; p.StartInfo.CreateNoWindow = false; p.Start(); p.StandardOutput.ReadToEnd(); p.CloseMainWindow(); p.Close(); } }
Last updated: 2024-01-16
Post by toby on Ethernet/IP communication with Omron NX1P2
CODESYS Forge
talk
(Post)
Hey guys, I'm very much a noob with networking, it's my achillies heel, and this is my first networking project using Ethernet/IP. Any help offered is GREATLY appreciated. I'm trying to network a Codesys Project with an Omron NX1P2 PLC. I'm using EIP due to hardware restrains. I've added the fieldbus, EIP scanner (as the master), and made a Network Variable List. On the Sysmac Studio end, I've made the variables and set them to network inputs/outputs, registered them in EIP settings, but when I try to set the target device (the Codesys project), I suspect I need to import an EDS file for the EIP mapping. Back in the Codesys project, I'm not sure how to: - Make an EDS file to share with Sysmac Studio - How to link the target device (Omron PLC) to the EIP fieldbus - How to map the inputs from the Omron PLC. Im sorry for my very open request for help, i'm kind of lost looking through the various forums/video/tutorials as many of them dont match what im trying to do. Any help, or sample programs would be so so greatly appreciated. If you need any further clarifications, please feel free to ask. Thanks in advance, Toby
Last updated: 2024-01-24
Post by aott33 on Webvisu NO load
CODESYS Forge
talk
(Post)
Should I be looking for anything in particular in the PLC Log? Attached is the xml file from the PLC logger.
Last updated: 2023-09-26
Post by ronald-de-jonge on Codesys StructType in Device Description File
CODESYS Forge
talk
(Post)
We have the same issue when using CODESYS V3.5 SP18 Patch 2. Is there a solution for this issue?
Last updated: 2023-10-30
Post by kumareasu on Runtime System Update
CODESYS Forge
talk
(Post)
When I change the hardware Do I need to buy licence After three years ? Please refer the jpg file.
Last updated: 2023-11-26
Post by snhatton on Saving variable values on power cycle (RevPi Connect)
CODESYS Forge
talk
(Post)
Have you tried using the persistence manager which uses the file system of the controller to store persistent variables?
Last updated: 2023-12-04
Post by eschwellinger on Softmotion axis to CANopen Maxon IDX drive
CODESYS Forge
talk
(Post)
I would try to use the EDS file of the maxon drive.
Last updated: 2024-01-06
Post by h4sanb on Load (or Read) File from PLC
CODESYS Forge
talk
(Post)
I want to download program from existing PLC and upload to new PLC. How to do it?
Last updated: 2024-01-09
Post by eschwellinger on Edge Gateway online, but PLC is not online
CODESYS Forge
talk
(Post)
need the log file - or you write/send it in the CODESYS store my question
Last updated: 2024-01-10
Post by jeffersonhui on External file with relative path
CODESYS Forge
talk
(Post)
I have the same question as well, anyone have any ideas? Thanks
Last updated: 2024-01-15
Post by saugat10 on Problem installing Multicore codesys control in raspberry pi 4
CODESYS Forge
talk
(Post)
I found the solution. I had to add the following line in /boot/config.txt file arm_64bit = 0
Last updated: 2024-02-07
Post by eschwellinger on File transfer via visu and codesys automation server
CODESYS Forge
talk
(Post)
Hi, this will be possible with 1.33.0.0 release! Regards Edwin
Last updated: 2024-03-07
Post by eschwellinger on Raspberry PI4 Serial Port
CODESYS Forge
talk
(Post)
no config file is ok, the feedback is: your hardware must support this send/receive switching
Last updated: 2024-03-19
Post by jglueck on Create a package with EDS file
CODESYS Forge
talk
(Post)
I have the same question. I am starting to think no one uses CAN on PLCs anymore.
Last updated: 2024-04-16
Post by wollvieh on Launch a *.exe file from codesys
CODESYS Forge
talk
(Post)
https://faq.codesys.com/plugins/servlet/mobile?contentId=106889218#content/view/106889218
Last updated: 2024-04-19
Post by wollvieh on Launch a *.exe file from codesys
CODESYS Forge
talk
(Post)
https://faq.codesys.com/plugins/servlet/mobile?contentId=106889218#content/view/106889218
Last updated: 2024-04-19
Post by peterned on CNC - system goes to X=0 Y=0 before CNC file execution starts, how to avoid that?
CODESYS Forge
talk
(Post)
Hi, I have a XY system and use a CNC file to move it. Everything works OK, except for the following: when CNC execution starts, the system rushes at high speed to (X=0, Y=0) point, and only then goes to the first line of the CNC file. If one of the axes is near 0, the system jumps and immediately stops with an error. In the CNC file settings (screenshot attached) I specified low default values for speed/acceleration and a start position different from 0,0 - but all that is ignored. Any idea how to avoid that move to 0,0 ? Thanks.
Last updated: 2024-04-26
Post by peterned on CNC - system goes to X=0 Y=0 before CNC file execution starts, how to avoid that?
CODESYS Forge
talk
(Post)
Thanks Georg, that fixed it.
Last updated: 2024-05-07
Post by simonep on new version of CODESYS have problem to load GSDML files
CODESYS Forge
talk
(Post)
I am trying to load a GSDML file of a PROFINET gateway device
Last updated: 2024-05-20
Post by simonep on new version of CODESYS have problem to load GSDML files
CODESYS Forge
talk
(Post)
I am trying to load a GSDML file of a PROFINET gateway device
Last updated: 2024-05-20
Post by simonep on new version of CODESYS have problem to load GSDML files
CODESYS Forge
talk
(Post)
I am trying to load a GSDML file of a PROFINET gateway device
Last updated: 2024-05-20
Post by simonep on new version of CODESYS have problem to load GSDML files
CODESYS Forge
talk
(Post)
I am trying to load a GSDML file of a PROFINET gateway device
Last updated: 2024-05-20