Post by mubeta on Some 'pathetic' errors in SoftMotion program
CODESYS Forge
talk
(Post)
Yes, this is the error the sometimes show up. What make me crazy is the fact that it happens randomly and not each times. I know very well where the problem is, in wich one program row it's located. For each actions of the state machine I have all events recorded with log on text file. it is not problematic for me to find the application point of the fault, but I need to understand why occasionally and for no apparent reason, switching the state machine and thus changing the motion FB, sends the axis into failure (but only occasionally). For example, one case that is often problematic is the execution of the Axis Halt instruction. When, after a MoveAbosulte instruction this returns the event as 'done' and indeed the axis is in standstill, the state machine first sets the move instruction to FALSE, and the next cycle sets the Halt request to TRUE. Some of the time everything works out fine. Occasionally, however, in this exchange, the axis goes into fault, also losing the OPERATIONAL state. Meanwhile, I would like to understand why the motion FB instances must still be called even after the Execute is set to FALSE, especially in view of the fact that the next instruction is programmed to abort the previous one, with BufferMode set to 'Aborting'. All these unnecessary FB calls are an unnecessary overhead on the CPU anyway. Is there any precise rule about when to cease calling the various instances? (It should precisely be the 'done' status that says this one has finished its work).
Last updated: 2024-07-18
Post by rmarco on Generic Variables and FDB
CODESYS Forge
talk
(Post)
Hello everyone, I am running into a highly frustrating issue in the FBD editor regarding a Function Block with generic constants (VAR_GENERIC CONSTANT). I created a FB using ST, with a generic var, useful for having a variable sized array, as follows: FUNCTION_BLOCK Coil VAR_GENERIC CONSTANT maxEvents: USINT := 5; END_VAR VAR events: ARRAY[0..maxEvents-1] OF IEvent; END_VAR These FBs have also several methods. I declare them as follows in code: VAR coil1: CDL.Coil<(maxEvents:=1)>; END_VAR and when using them in ST, I have no problems. However, when trying to use them in FDB, I do not know how to do that, as some strange misalignment happens. Here's what happens: When I add the block to my FBD canvas and assign coil1 as the instance name, the compiler throws this error: 'coil1' is not an instance of 'CDL.Coil<(maxEvents:=1)>'. Same occurs when I try to instantiate blocks such as 'coil1.turnOn' or similar. Here is what I have already tried, none of which worked: - Deleting the <(maxEvents:=1)> parameter from the text inside the FBD box. - Deleting the block entirely, dropping an "Empty Box", and typing coil1 above it to let the IDE auto-complete and format the block. - Running a full "Clean All" and rebuilding the code. I am aware that I could bypass the graphical editor by calling it in Structured Text. However, I need to keep this logic compatible to FBD. Has anyone encountered this specific FBD parsing bug with generic variables? Thanks in advance for any insights. Best regards, Marco
Last updated: 2026-06-29
Post by oymyakon on Modbus Lockup
CODESYS Forge
talk
(Post)
Hi i have a project where i am communicating with many modbus devices using TCP to serial. This is all working extremely well except when i turn one of the remote devices off. If i leave the auto reconnect on it still doesn't talk to the rmianing devices and if i turn Auto reconnect off it locks up. Any help would be appreciated. Paul.
Last updated: 2024-08-07
Post by oymyakon on Modbus Lockup
CODESYS Forge
talk
(Post)
Hi i have a project where i am communicating with many modbus devices using TCP to serial. This is all working extremely well except when i turn one of the remote devices off. If i leave the auto reconnect on it still doesn't talk to the rmianing devices and if i turn Auto reconnect off it locks up. Any help would be appreciated. Paul.
Last updated: 2024-08-07
Post by lbartik on MPC predictive control
CODESYS Forge
talk
(Post)
Would this work? https://www.mathworks.com/hardware-support/codesys.html I'm also interested in real-world MPC and have no idea where to start. There is an exciting Python library that is also beyond my grasp: https://www.do-mpc.com/en/latest/index.html Step 1, get PhD(s). Step 2, get job in aerospace/robotics. Step 3, return 15 years later to share this knowledge?
Last updated: 2024-10-19
Post by timvh on Colors look different when logged in and running
CODESYS Forge
talk
(Post)
At the top of the Visualisation Properties View, you can enable the "Advanced" options. This will give you access to more properties than what you currently see. There might be a variable linked to the "advanced" colour property where the fill colour is determined by the value of this variable (dword).
Last updated: 2025-01-09
Post by secundino on License
CODESYS Forge
talk
(Post)
Good morning, I need to activate a CODESYS license on your website, as the computer where it was originally installed has been formatted. I have already sent two emails to store-support@codesys.com, but I have not received a response yet. Could you please assist me with this issue as soon as possible?
Last updated: 2025-02-20
Post by secundino on License
CODESYS Forge
talk
(Post)
Good morning, I need to activate a CODESYS license on your website, as the computer where it was originally installed has been formatted. I have already sent two emails to store-support@codesys.com, but I have not received a response yet. Could you please assist me with this issue as soon as possible?
Last updated: 2025-02-20
Post by benemenn on Type mappings in Datasource
CODESYS Forge
talk
(Post)
Hi! I am trying to achieve the same issue. Has there been a solution? I can create the mapping, and map the local variable, but somehow the object does not update. Furthermore, i have an issue where codesys doesn't let me set ReadWrite accesses to the variables in the "Type Mapping" place. The access will simply not be set. Has anyone ran int that issue?
Last updated: 2025-04-02
Post by williamjmak1 on Current Visu name without Current Visu Variable
CODESYS Forge
talk
(Post)
Hello everyone, I was just wondering if anybody knows if there's a way to pull the string name of the current visualization without using the current visu variable. I'm working on a project where we don't want web clients to change the current visualization on the HMI of the machine. Thanks!!
Last updated: 2025-08-07
Post by sandro66 on Application-based license Modbus Channels
CODESYS Forge
talk
(Post)
Hi, I imported an old project created with version 3.51.20.50 into the new version 3.51.21.20. I'm using ModbusFB.ClientTCP v4.5.0.0. Strangely, I can no longer download the project due to a licensing issue I didn't have before. The number of Modbus channels has gone from 1 to 54!, and there's no license that would work. Can anyone tell me where I'm going wrong? Thanks Sandro
Last updated: 2025-08-27
Post by leandroct on Creating Boot Application not working
CODESYS Forge
talk
(Post)
I did these steps and it worked: - Copied Application.app and Application.crc to the Folder C:\ProgramData\CODESYS\CODESYSControlWinV3x64\ID_of_CPU\PlcLogic\Application\ copied the visu folder content to the folder C:\ProgramData\CODESYS\CODESYSControlWinV3x64\ID_of_CPU\PlcLogic\Application\visu\ Changed by Notepad the CODESYSControl.cfg at the folder C:\ProgramData\CODESYS\CODESYSControlWinV3x64\ID_ of_CPU\ Where is [CmpApp], adding a line with: Application.1=Application
Last updated: 2025-09-04
Post by felixal on Codesys automatic Data transfer to USB on rasberry pi
CODESYS Forge
talk
(Post)
Hi all, I am currently working on a project where I need to save data automatically on many diffrent USB-Sticks, which are always plugged in the same USB-Port on a Rasberry PI, but I do not get how I can automatically detect the USB devices Folder Name and save a file there on Linux. Thanks!
Last updated: 2024-01-03
Post by blitz on Can't get SMC_SmoothPath to work
CODESYS Forge
talk
(Post)
Hi @bertus I have a similar situation: just like in your case I can see that rounding works correctly only for the first element, additionally in my case on a path made of lines where I am testing this every second line is skipped. The interpolator jumps to every second iActObjectSourceNo.
Last updated: 2026-01-07
Post by davidbo on Two licenses have to be installed forgot to enable one license
CODESYS Forge
talk
(Post)
Raspberry Pi MC Application based license: CODESYS Control Standard M CODESYS Visualization M (Could not be installed) CODESYS Control Standard M pops up with a dialog window where I can select 3 bundled licenses one of which is "Visu S" which I didn't select
Last updated: 2026-02-03
Post by ph0010421 on Deploy Codesys Control SL to a 'secure' device
CODESYS Forge
talk
(Post)
Hello I'm trying to get Codesys onto a 'Secure' edge device (Linux) The device doesn't support 'sudo' so the connection doesn't complete properly. Is this the same as not allowing root access? Anyway, the screen shot shows where I am. What options do I have?
Last updated: 2026-05-01
Post by jrsantab on Remote connection to ifm PLC & HMI
CODESYS Forge
talk
(Post)
Hello, We are trying to access remotely a PLC (ifm 711S) and a HMI (ifm CR1077). Both are connected to a Teltonika RUT200 router. We establish the connection with OpenVPN Connect and can ping both controllers. We have a laptop that, most of the time, will allow Codesys connection to the controllers, but we have several other computers that are unable to connect, although all of them can ping successfully. We cannot find any difference in the configuration or software installed from one PC to another. If we connect to the router by WIFI, instead of VPN, all the computers work fine. We know that scanning the network will not work over a remote connection, so we input the controller IP directly. Has anyone had a simlar problem and can offer any hint on what to check to meke the connection run?
Last updated: 2024-04-11
Post by jrsantab on Remote connection to ifm PLC & HMI
CODESYS Forge
talk
(Post)
Hello, We are trying to access remotely a PLC (ifm 711S) and a HMI (ifm CR1077). Both are connected to a Teltonika RUT200 router. We establish the connection with OpenVPN Connect and can ping both controllers. We have a laptop that, most of the time, will allow Codesys connection to the controllers, but we have several other computers that are unable to connect, although all of them can ping successfully. We cannot find any difference in the configuration or software installed from one PC to another. If we connect to the router by WIFI, instead of VPN, all the computers work fine. We know that scanning the network will not work over a remote connection, so we input the controller IP directly. Has anyone had a similar problem and can offer any hint on what to check to make the connection run?
Last updated: 2024-04-11
Post by timvh on CANbus issue
CODESYS Forge
talk
(Post)
On a PC with the Control Win, this is probably related to the fact that the CAN drivers are not loaded. Go to the folder where your Control Win Configuration file is: - E.g. C:\ProgramData\CODESYS\CODESYSControlWinV3x64\E1FA7ABE - Open the CODESYSControl.cfg - Remove the semi-colon in front of the CAN driver you want to use (section ComponentManager). - Set the component ID to the next number in the list (e.g. Component.8) - Save this file and restart the Control Win.
Last updated: 2023-09-14
Post by selim on Need help to get RS-485 signal in Cosesys .
CODESYS Forge
talk
(Post)
Hello Mr./Ms., I invested Raspberry Pi lot of time to get the output from the raspberry PI5. But, i did not get the signal. I use a raspberry pi 5> RS485 can hat > Modbus RTU, Industrial 8-ch analog acquisition module >weight transmitter jy-s60> S-load cell. I did not able to receive the signal from Modbus RTU to Raspberry PI5 where I use the RS 485 serial connection.
Last updated: 2024-12-01
Post by wiresplus on INT_TO_WORD function not working
CODESYS Forge
talk
(Post)
Hello, I need to take an INT input, and convert it to a WORD value. VAR DRV2Speed : WORD; //IO card takes a WORD where 16000 = full 10V output (equivalent to 50Hz) PumpFillSpeed : INT; //Users enter a value between 0 and 50 END_VAR IF <conditions> THEN DRV2Speed :=INT_TO_WORD((PumpFillSpeed/50)*16000); END_IF </conditions> According to me this should work - but it stays at 0, no matter what. What am I doing wrong?
Last updated: 2024-01-26
Post by kmax365 on ModbusTCP_FunctionCode06
CODESYS Forge
talk
(Post)
Hey Guys, I am trying to create a ModbusTCP_FunctionCode06 which i will use as a single write register for programming a test code for Power Meter(PQM_1000) I have tried to reserach how to add it it from the libraray manager and have largely been unsuccessful. Does anyone know where I should Look? And by the way, I am i wam using Codesys V3.5 Vs 21 Patch 4 I look forward to something positive. Best, Kmax365.
Last updated: 2026-05-14
Post by kmax365 on ModbusTCP_FunctionCode06
CODESYS Forge
talk
(Post)
Hey Guys, I am trying to create a ModbusTCP_FunctionCode06 which i will use as a single write register for programming a test code for Power Meter(PQM_1000) I have tried to reserach how to add it it from the libraray manager and have largely been unsuccessful. Does anyone know where I should Look? And by the way, I am i wam using Codesys V3.5 Vs 21 Patch 4 I look forward to something positive. Best, Kmax365.
Last updated: 2026-05-14
Post by robbudge on Data Source Error 418
CODESYS Forge
talk
(Post)
Same ? Did you find the Solution??
Last updated: 2024-10-11
Post by benmatchless on CODESYS Gateway is not running
CODESYS Forge
talk
(Post)
same issue here, did you find anything?
Last updated: 2024-10-24