Post by eschwellinger on Edge Gateway online, but PLC is not online CODESYS Forge talk (Post)
we need some logfiles from the edge gateway /etc/Gateway.cfg [CmpLog] CmpEdgeGateway.Filter=0xFFFFFFFF Logger.0.Name=/tmp/codesysedge.log Logger.0.Filter=0x0000000F Logger.0.Enable=1 Logger.0.MaxEntries=100000 Logger.0.MaxFileSize=5000000 Logger.0.MaxFiles=1 Logger.0.Backend.0.ClassId=0x00000104 ;writes logger messages in a file Logger.0.Type=0x314 ;Set the timestamp to RTC and does the scan via Automation Server show the plc?
Last updated: 2024-01-09

Post by felipemsgarcia on Edge Gateway online, but PLC is not online CODESYS Forge talk (Post)
Hello, I couldn't figure what/where the issue was, so I deleted everything from automation server and reinstalled the edge gateway and did the process again. It worked for about a month and then it stopped working again. It presents the same symptom, edge gateway is online but I can't connect to the PLC. Any idea of what could be the issue? Thank you!
Last updated: 2024-01-09

Post by felipemsgarcia on Edge Gateway online, but PLC is not online CODESYS Forge talk (Post)
Hi Edwin, The PLC is already in the automation server so nothing happens when I scan the network, however the PLC show offline (not connected). Please see logs below. [CmpLog] Logger.0.Name=codesysedge.log Logger.0.Filter=0x0000000F Logger.0.Enable=1 Logger.0.MaxEntries=100000 Logger.0.MaxFileSize=1000000 Logger.0.MaxFiles=1 Logger.0.Backend.0.ClassId=0x00000104 ;writes logger messages in a file Logger.0.Type=0x314 ;Set the timestamp to RTC Thank you!
Last updated: 2024-01-09

Post by toby on SM Drive license error CODESYS Forge talk (Post)
Hi albert1999 and forest, I hope you are well. I too am wondering if you have found any solutions? Im working with a RPi and a Omron R88D-ETH servo amplifier. The SoftMotion is timing out after 30min without the license, but I cant figure out how to license it, and I seem to have some compatibility issues between my RPi license and any SoftMotion licenses. Did you guys have any luck? Thank you very much for any assistance offered. Toby
Last updated: 2024-01-10

Post by sturmghost on Visualization using methods and cyclic ST-calls CODESYS Forge talk (Post)
I found a way to do it: You can use, for example, the text variable property of any visualization element and call a function in it. Example: Write a test POU as a function (FUN), like MyTestFun which need a boolean Variable as an input value. Now write into the text variable property: MyTestFun(bBooleanValue) Thats it. The function is called at each visu_task cycle.
Last updated: 2024-01-22

Post by haydermsalih on OSCAT Network LIBRARY: FTP_CLIENT CODESYS Forge talk (Post)
Hello I am using FTP_CLIENT to donwnload/Upload a text or CSV file from FTP server. UpLoading from PLC to FTP server is working without any problem but when I try to download from FTP server I get an error. The FTP_CLIENT Block allows me to add URL but I do not where I can specify the direcory to save the downloaded file... is there anyone has an experience with downloading from FTP server using FTP_CLIENT block. Thanks in advance Hayder
Last updated: 2024-01-24

Post by jinlee on Multiple WebVisu CODESYS Forge talk (Post)
Hi guys, I am new to the Visualization. I am having a problem. I have multiple web-panel to use webvisu. I have my software dowwloaded into the one PFC200. There are 3 screens connected to it. I noticed that if I switch page/visualisation on one of the screens, the others will change as well. Three screens are with different URLs that I set in the software. Is there any method to make them independently ? Kind regards, Jin.
Last updated: 2024-01-25

Post by jaspergain on Access to the path *** is denied CODESYS Forge talk (Post)
Hello, Recently I upgraded to 3.5.19.50 and have been having errors/issues when doing a download/online change. The message as seen in the attachment pops up. The file in the path is different every time. However when I login again afterwards all works fine. This issue does not happen on older versions. Any clue what the issue could be? I did an reinstall/repair but the issue reappeared again... Thanks in advance!
Last updated: 2024-01-25

Post by wiresplus on INT_TO_WORD function not working CODESYS Forge talk (Post)
Hello, I need to take an INT input, and convert it to a WORD value. VAR DRV2Speed : WORD; //IO card takes a WORD where 16000 = full 10V output (equivalent to 50Hz) PumpFillSpeed : INT; //Users enter a value between 0 and 50 END_VAR IF <conditions> THEN DRV2Speed :=INT_TO_WORD((PumpFillSpeed/50)*16000); END_IF </conditions> According to me this should work - but it stays at 0, no matter what. What am I doing wrong?
Last updated: 2024-01-26

Post by wiresplus on Cannot get INT_TO_TIME working CODESYS Forge talk (Post)
Hello, I have a simple TON timer. It is watching prime loss for a pump. The operator can set the delay via the HMI, it is an integer (seconds) As the TON uses milliseconds, we then multiply the entry by 1000 to get seconds. Seems simple, but... VAR PrimeTimer : TON; primetime : INT; END_VAR PrimeTimer(in:=State>0 AND FlowRate<MinimumFlow,pt:=INT_TO_TIME(primetime *1000)); For an entered 15 seconds (VAR primetime:=15;) the timer reads 49d17h2m26s760ms !!!! What am I doing wrong?
Last updated: 2024-01-26

Post by ojz0r on INT_TO_WORD function not working CODESYS Forge talk (Post)
That calculation will not work the way you expect it to. If PumpFillSpeed is limitied to 0-50 then the only whole number would be 50/50 = 1 everything else is 0.0-0.9999... and since you are using word and integer only 50 would work since there is no representation for mantissa in integer values. Declare a temporary real variable and do the calculation and then do a REAL_TO_WORD in the DRV2Speed assignment.
Last updated: 2024-01-26

Post by melle17 on Steuerung einer Geschirrspülmaschine CODESYS Forge talk (Post)
Hallo, ich muss im Rahmen einer Hausarbeit die Steuerung einer Geschirrspülmaschine erarbeiten. Leider bin ich mit dem Programm noch nicht so vertraut und habe Probleme bei meinem Zeitschalter und finde leider selber das Problem nicht. Deswegen zu meiner Frage ob mir jemand helfen könnte. Und zwar kommt das meine Variablen nicht deklariert sind und ich finde aber nicht wieso. Die zwei Screenshots zeigen nochmal den Zeitschalter und das Programm wo der Zeitschalter eingesetzt wird. Vielen Dank im Voraus.
Last updated: 2024-01-30

Post by matt-s on HMI Pushbutton/Move Instruction CODESYS Forge talk (Post)
I have not gotten to the bottom of this yet no. I have double check that the variables are correct linked. When online with the program I can see the button and rung going true for the move instruction, yet it does not change. Forcing the bit in the program does change the value in Groov View. I am kind of at a loss here, especially since the other POU(For the pumps) does the same thing fine.
Last updated: 2024-02-02

Post by jshirazi on Restore license on Raspberry Pi CODESYS Forge talk (Post)
Hi, I recently got a license for Raspberry Pi, after license activation I made a backup copy of "CMLicenseNew.WibuCmRaU" file to a safe place. Things got complicated and I tried to downgrade OS for some reason after that I tried several times/ways to restore my license with no luck. the specifications are as follows: Raspberry Pi 4 Model B Rev 1.1 codesyscontrol 4.10.0.0 SDK 3.5.19.30 Logs: **** ERROR: CodeMWriteLicenseFile: 'CMLicenseNew.WibuCmRaU' failed: Container not found or Server dose not support .... So if someone know a solution for this please kindly help me. Regards
Last updated: 2024-02-03

Post by josephbourgeois on Tracking out product CODESYS Forge talk (Post)
Hi everyone! I synchronize the operation of the tripod and the conveyor. I have a problem with the product tracking algorithm on the conveyor (PCS_1). Sometimes I need to stop tracking a product on command without completing the operation. I do this using MC_GroupStop. But when I need to start moving in WCS again (using fb movelinearabsolute), I get a tripod kinematics error - SMC_CP_INVALID_ORIENTATION (Invalid orientation (non-orthonormal matrix or non-unit quaternion, internal error)). MC_ResetGroup does not help. What could be the problem? Has anyone encountered this?
Last updated: 2024-02-05

Post by josephbourgeois on tracking out product CODESYS Forge talk (Post)
Hi everyone! I synchronize the operation of the tripod and the conveyor. I have a problem with the product tracking algorithm on the conveyor (PCS_1). Sometimes I need to stop tracking a product on command without completing the operation. I do this using MC_GroupStop. But when I need to start moving in WCS again (using fb movelinearabsolute), I get a tripod kinematics error - SMC_CP_INVALID_ORIENTATION (Invalid orientation (non-orthonormal matrix or non-unit quaternion, internal error)). MC_ResetGroup does not help. What could be the problem? Has anyone encountered this?
Last updated: 2024-02-05

Post by jinlee on Multiple WebVisu CODESYS Forge talk (Post)
Hi, thank you for replying. Basically, I have a main visu with frame selection. So, under some condition the frame will switch to a specific frame. It used to be controlled by variable using "Switch frame variable". However, I realise it will change all the HMI screen at one time. So I removed the variable, and still looking for a solution to do that. Do you have any idea?
Last updated: 2024-02-06

Post by jinlee on How do you get the CURRENT ClientData? CODESYS Forge talk (Post)
Hi there, I wonder how to use this CURRENTCLIENTID. However, what I am trying to do is to use PLC_PRG.aIndexVisu[CURRENTCLIENTID]. to switch the frame within the mainpage without affecting the other screen same as the first question of this post. However, I failed to do it. Can you tell me how to do it ? Or can you advise me on this issue
Last updated: 2024-02-07

Post by tk096 on SMC_Interpolator + SMC_controAxislbyPos CODESYS Forge talk (Post)
Hi, you can define a start position for your GCode. How the start position can be defined depends on the CompileMode: For File and SMC_CNC_REF: Set the start position input of SMC_NCInterpreter (https://content.helpme-codesys.com/en/libs/SM3_CNC/Current/SM_CNC_POUs/NC2/Interpreter/SMC_NCInterpreter.html) For SMC_OutQueue: * Right-click on the CNC object in the project tree * Select Properties * Select the tab 'CNC' * Set the start position Concerning your second question: If the new set position cannot be reached with the given velocity limit (AXIS_REF_SM3.fSWMaxVelocity), SMC_controlAxisByPos will report bStopIpo and close the 'gap' with the given gap dynamics (SMC_controlAxisByPos.fGap*).
Last updated: 2024-02-07

Post by matthew on New Ladder Diagram conversion does not work due to missing features CODESYS Forge talk (Post)
Hi @eschwellinger, I have been trying out v1.0 of the new ladder and have a few questions. I have warnings Expression or part of it has no effect I can't get rid of them, what do they exactly mean? Using the ST_Block, is there a way when online to open the ST_Block and view the running code? Thanks!
Last updated: 2024-02-09

Post by andrax on Prüfen ob Datei existiert wenn nicht neu erstellen CODESYS Forge talk (Post)
Hi, ich ich möchte prüfen ob eine Datei existiert. Wenn diese nicht existiert, soll eine erstellt werden und dort hinein geschrieben werden. Die Datei wird im Programmlauf mehrfach geöffnet und Daten hinein geschrieben. Ich will hier die Funktion File.MODE.MAPPENDPLUS benutzen, das funktioniert aber nicht. fopen.xDone bleibt false. Hier der Code: fopen.sFileName:=sFileName; fopen.eFileMode:=File.MODE.MAPPENDPLUS; // Neu erstellen und anhängen fopen.xExclusive:=TRUE; fopen( xExecute:=TRUE); IF fopen.xDone THEN hFile:=fopen.hFile; sStringToWrite:=''; writeIndex:=0; SchrittDatenlog:=60; END_IF Wo liegt mein Fehler?
Last updated: 2024-02-11

Post by nmcc on Toggling Visualizations using HMI Physical Buttons CODESYS Forge talk (Post)
Hey thank you for the reply dkugler. I am sorry if this seems like a stupid question. I have the use current visuvariable checkbox enabled. I can see the string names of all my visualizations. I am trying to use ladder logic to be the anser to the button press using "VisuElems.CurrentVisu := 'MainScreen';. This returns an error. Any idea what I am doing wrong or could you point me in the right direction for fixing this. Thanks,
Last updated: 2024-02-13

Post by nmcc on Toggling Visualizations using HMI Physical Buttons CODESYS Forge talk (Post)
Hey thank you for the reply dkugler. I am sorry if this seems like a stupid question. I have the use current visuvariable checkbox enabled. I can see the string names of all my visualizations. I am trying to use ladder logic to be the anser to the button press using "VisuElems.CurrentVisu := 'MainScreen';. This returns an error. Any idea what I am doing wrong or could you point me in the right direction for fixing this. Thanks,
Last updated: 2024-02-13

Post by roccom1910 on variablen inhalt in datei schreiben bei system event CmpApp.EventIDs.EVT_PrepareStop CODESYS Forge talk (Post)
Hallo, ich möchte meine Variablen vor dem stoppen der CPU in eine Datei schreiben. Das schreiben der Datei dauert ca. 1 minute (sehr viele Daten). Ich habe versucht das mittels Szstemevent zu bewerkstelligen leider kreiert er nur die datei sofern nicht vorhanden. Ich vermute das die Zeit nicht ausreicht um die daten zu schreiben. Anbei mal der Entsprechende FB. Kann mir da eventuell jemand weiterhelfen?
Last updated: 2024-02-15

Post by marlutec on [ERROR] The PLCopenXML import is not possible because Device not found. Type: 89, Id: 0000 0005, Version: 3.5.10.0 CODESYS Forge talk (Post)
Hello every one. Now i'm instaling a Weintek cMT2108x2(v2) with IR-ETN40R. When I start to import the archive content the code of I/O remote IR-ETN40R, ocurred this error. [ERROR] The PLCopenXML import is not possible because Device not found. Type: 89, Id: 0000 0005, Version: 3.5.10.0 Can someone help me? Marcos Gentil, from Brazil.