Post by pietrobalint on Retain / Persistent Variables in Codesys for Raspberry Pi CODESYS Forge talk (Post)
If I select "Update boot aplication" while I download the code the persistent variables got a constant startup value. But during the running I am still not able make the persistent variables to hold they actual value.
Last updated: 2024-09-01

Post by ph0010421 on How to manage variable types larger than 64 bits - Ethernet/IP CODESYS Forge talk (Post)
My guess is that's a STRING, not an INT type. And it's 128 bytes, not bits
Last updated: 2024-09-23

Post by opineiro on How to manage variable types larger than 64 bits - Ethernet/IP CODESYS Forge talk (Post)
Thanks, I'm going to try it!
Last updated: 2024-09-23

Post by scarter on Bit / Bool data types in function parameters CODESYS Forge talk (Post)
Any reason BIT and BOOL data types are not interchangeable? Trying to make a function which takes a BOOL IN/OUT parameter (Not allowed to use BIT) In the main logic if I make a DINT variable, and want to use each bit on different functions CODESYS will not allow it.
Last updated: 2024-01-17

Post by askjong on Update variables when OPC UA Client updates. Error ID: 268468277 BadAttributeIdInvalid CODESYS Forge talk (Post)
Hi, I'm connecting to a OPC UA Server using the Data Soruce Manager OPC UA Client. This works well until the OPC UA Server updates and the OPC UA list doesn't match up when i did last clicked the "Update variables" to add variables. All the variables are still the exists and none are removed from the server, but more are added during the engineering process. The error message i get in CODESYS is "Error in OPC UA call BadAttributeIdInvalid, Error ID: 268468277". The issues is fixed when i press the "Update variables" button and just press ok without adding or removing any variables in the list. Is there a way to either automatically update the browsepath if it fails or on startup, or to trigger it by code?
Last updated: 2024-01-08

Post by lucaver89 on Raspberry pi 3 and runtime 4.9.0.0 CODESYS Forge talk (Post)
Good morning, I'm using a raspberry pi3 as plc with the runtime 4.9.0.0. My program has many of retrain variables but when an update is performed the retrain variables comes back to default values. Is the a way to backups the retrain variables n a csv file? Is still the way to restore them from the csv? Thank you for helping Luca
Last updated: 2023-09-23

Post by gatto on variables between two applications CODESYS Forge talk (Post)
Hello, I'm experimenting with two applications. I was able to start stop applications with the CmpApp library. Currently in my test the variables declared in the first application are not visible and writable in the second. I ask if there is the possibility of having variables that are visible both in the first application and in the second.
Last updated: 2024-06-22

Post by talhaali on Persistent variables not working for Control Win CODESYS Forge talk (Post)
Hi everyone, I am facing issues with persistent retain variables. It was working fine. I added a few new Persistent variables and it stopped working. If I do cold reset it holds persistent variable values. But when I close control win gracefully, and opens it again then it does not. Even, it is not saving ret file in application.
Last updated: 2024-09-10

Post by pietrobalint on Persistent variables are not read after initialization CODESYS Forge talk (Post)
Hi, I realized that if I replug the power supply the persistent variables lost their value with the new software too. Cold reset do not affect the variables value but hardware reboot still reset the values. Application Composer can't be activated. What is the solution?
Last updated: 2024-10-11

Post by danieldiaz on Problem with FB execution CODESYS Forge talk (Post)
Problem Solved, I was overwriting the variables somewhere else
Last updated: 2024-04-05

Post by eschwellinger on Persistent variables are not read after initialization CODESYS Forge talk (Post)
which version of the runtime do you use?
Last updated: 2024-09-02

Post by hambergg on Retain Variables on fRAM CODESYS Forge talk (Post)
Hi regarding NVRAM with SPI or I2C I expected reference too!
Last updated: 2024-09-03

Post by nathant on Saving variable values on power cycle (RevPi Connect) CODESYS Forge talk (Post)
Hello, this seems to be a known issue, but persistent/retain variables don't seem to work properly on RevPi devices. Is there a workaround to this? All I need is for a few configuration variables to be remembered through power cycle.
Last updated: 2023-12-03

Can a table be used as an input to date and time variables on a function block diagram? CODESYS Forge talk (Thread)
Can a table be used as an input to date and time variables on a function block diagram?
Last updated: 2022-09-15

Can a table be used as an input to date and time variables on a function block diagram? CODESYS Forge talk (Thread)
Can a table be used as an input to date and time variables on a function block diagram?
Last updated: 2022-09-15

Post by damian177 on Persistence variables PFC200 CODESYS Forge talk (Post)
Hi, I using persistence variables like below: VAR_GLOBAL PERSISTENT RETAIN id_worker1: ARRAY [0..3] OF INT := [231,234,176,222]; id_worker2: ARRAY [0..3] OF INT := [211,129,125,221]; Initial values can cause some problems?
Last updated: 2023-12-08

Post by alex-wall on Network Variables not updating CODESYS Forge talk (Post)
This worked for me. I had four identical PLC's. Three of them worked just fine with 255.255.255.255 as the broadcasting address but the 4th would not update the variables. Changed it to 192.168.x.255 and everything worked.
Last updated: 2024-05-07

Post by k4zz on Continuous Build Server CODESYS Forge talk (Post)
Hallo Martin, Thank you so much for the Code example. It works really fine for .porject Types. However, I encountered a challenge when attempting to apply it to .library Types. I also tried the option to "Perform static analysis automatically after compilation" # get Project values myProject = projects.primary # Creates an active application app = myProject.active_application # build Application and run static code analysis app.generate_code() Could you please offer any insights into why this might be occurring?
Last updated: 2024-03-15

Post by k4zz on Scripting static code analysis CODESYS Forge talk (Post)
Currently, I am working on integrating static code analysis into our CI/CD pipeline. Specifically, I have successfully performed static code analysis for .project types, and it works flawlessly. However, I have encountered difficulties in executing the same for .library types. In this regard, I have tried two methods: system.commands["staticanalysis", "run"].execute() # get Project values myProject = projects.primary # Creates an active application app = myProject.active_application # build Application and run static code analysis app.generate_code() your help is greatly appreciated.
Last updated: 2024-03-18

Post by simotion on Axis variable indicating modulo of finite setting CODESYS Forge talk (Post)
What variable of the axis indicates it is a modulo of finite axis? I want to check that in the code, to adopt my motion code between the two types.
Last updated: 2023-11-24

Post by tvm on multiply gives negatives CODESYS Forge talk (Post)
you might have some slight inaccuracies with using a REAL. See here for an explanation: https://knowledge.ni.com/KnowledgeArticleDetails?id=kA00Z0000019ZSMSA2&l=en-US It might not matter, depends on how accurate you need it. I usually stick with integer types for something like this
Last updated: 2024-01-04

Post by smartcoco on Bit / Bool data types in function parameters CODESYS Forge talk (Post)
Memory addressing is measured in bytes, with BOOL occupying one byte. BIT is quite unique as it occupies one bit. So, try not to use BIT in the program. You can use the Unpack function to solve your problem.
Last updated: 2024-01-18

Post by fraccaroli on New Codesys Library Dependencies CODESYS Forge talk (Post)
Hello, you probably fixed in this meanwile, but I think your problem comes from dependencies of other libraries. I see in the Project column of errors the "caa types extern" and "caa fb factory", that both have dependencies. Try to check there. Regards, Francesco
Last updated: 2024-03-21

Post by dekelec on Codesys 2.3 & Peak PCAN CODESYS Forge talk (Post)
IF you have an USB interface type in "Peak_USB" for CAN card driver (Name of CAN card driver). No need to add libraries for communication via CoDeSys Gateway. For other card types contact PEAK support and they will help you. Regards,
Last updated: 2024-07-08

Post by ph0010421 on How to manage variable types larger than 64 bits - Ethernet/IP CODESYS Forge talk (Post)
So it's currently mapped to an array of BYTES? Can you create a UNION? TYPE sBytesString : UNION AsBytes: ARRAY[0..127] OF BYTE; AsString: STRING(128); END_UNION END_TYPE Map it to the bytes, read it in the STRING!