Post by eaglealex on Length of string and Array of bytes
CODESYS Forge
talk
(Post)
Thank you for your answer! I know that 0 will be the end of the string. I checked it. There is no 0 in array of bytes. I made screenshots. There is array of bytes, aborted string and the result of my test via online converter.
Last updated: 2025-04-02
Post by gseidel on Dynamic limits invaild
CODESYS Forge
talk
(Post)
Hi jbu0105, which error doe you get, exactly? Is it error 11008, SMC_MOVE_INVALID_DYNAMICS? (It might help if you check the "Log" tab in the PLC device and copy the exact error.) Please double-check whether the inputs Velocity, Acceleration, Deceleration, and Jerk of MC_MoveCircularAbsolute have correct (positive) values. Best regards, Georg
Last updated: 2025-04-07
Post by fionexyan on Codesys Installation Always Freeze when the installing is almost done
CODESYS Forge
talk
(Post)
Hello Everyone , I have try in repeatedly with uninstall and reinstall the Codesys software and even turn-off the antivirus application before implement to reinstall the codesys ,but at the consequence the problem still same although go with such method, therefore is there any solution for this issue . Thank You .
Last updated: 2025-05-16
Post by damian177 on Serialports in EdgeBox-RPI-200
CODESYS Forge
talk
(Post)
Hi, Two years ago i used EdgeBox-RPI-200 with Codesys and serial ports works fine. Now I try run the same application but only new runtime but serial ports doesnt works: I have two serial: /dev/ttyACM0 - RS485 /dev/ttyACM1 - RS232 and below configuration in my sudo nano /etc/CODESYSControl_User.cfg: [SysCom] Linux.Devicefile=/dev/ttyACM But it doesnt work. what can i do ?
Last updated: 2025-05-17
Post by bjohnson on CODESYS and Win10 - "the version profile is not valid" error
CODESYS Forge
talk
(Post)
We just had this problem today when our IT updated a group policy. You need to go to Local Group Policy Editor > Local Computer Policy > Computer Configuration > Windows Settings> Security Settings > Local Policies > Security Options. Set "System Cryptography: Use FIPS compliant algorithms for encryption, hashing, and signing" to DISABLED
Last updated: 2025-05-23
Post by bjohnson on CODESYS and Win10 - "the version profile is not valid" error
CODESYS Forge
talk
(Post)
We just had this problem today when our IT updated a group policy. You need to to got Local Group Policy Editor > Local Computer Policy > Computer Configuration > Windows Settings> Security Settings > Local Policies > Security Options. Set "System Cryptography: Use FIPS compliant algorithms for encryption, hashing, and signing" to DISABLED
Last updated: 2025-05-23
Post by zoppp on Visu Frame-configuration___text will not work
CODESYS Forge
talk
(Post)
Yup, I've been having the exact same issue. A workaround that was working until Visu 4.8.0.0 was using TextList as the type in the frame configuration and then wrapping the text in quotes when configuring it. Im not sure if it will work with variables and I know it does not work if the type is text.
Last updated: 2025-06-17
Post by dnordenberg on BOOL variable in OPC UA and modbus simultaneously
CODESYS Forge
talk
(Post)
How can I have an BOOL variable that is read/write in both modbus TCP server and from OPC UA at the same time? Variables with %MX.n %QX.n addressing which is used for BOOL/coils in modbus server is not allowed in OPC UA symbol list on Schneider M251 controllers. I have already asked on Schneiders forum but there are not a lot of codesys experts over there :( So OPC symbols can't have a address and the modbus TCP server needs a address. So how should I do it then? It seems like an impossible combination. Since I want read/write access from both ways I can't just simply make a second variable and assign it the value of another since it would be a one way assignment. I also tried using VAR_CONFIG which then makes the address syntax %Q or %M in my main variable list and that fools OPC UA Symbol Configuration to allow it and then I add the complete %MX.n address of it in the VAR_CONFIG list. This semi works, I can toggle the BOOL from modbus but the OPC UA symbol seems to be read only. It displays symbol status but nothing happens when I toogle it. I think I need another way to have the variables and symbols pointing to the same bits in memory... My plan B is to write a BOOL array compare FB that saves a history bit from previous cycle and if that does not match current status at next cycle for either the OPC symbol or the modbus variable then it copies the new status over to the other. Maybe ugly but it's like my last alternative. Kind regards David
Last updated: 2025-07-14
Post by llewv123 on Codesys Control for RPi and Waveshare AD/DA hat
CODESYS Forge
talk
(Post)
Good day, I am attempting to use a Waveshare AD/DA precision HAT with RPi 4B+, using Codesys Control for Rpi. The waveshare hat uses SPI. I am successfully using the RPi GPIO (inputs and outputs) but do not know how to access the AD/DA channels. Any help would be appreciated.
Last updated: 2025-08-04
Post by r0udy on Adress problem
CODESYS Forge
talk
(Post)
Hi, I 've just started a new project. Translating SoMachine (SCHNEIDER) to CODESYS 3.5.18//DEMO (EATON XC303) I succeed (I think so) to copy FB, STRUCT,... and I also integrated old library. When I build F11, I have a first problem : - Adress out of rang - Overlay It's strange, usually %ML100 > %MB800 Here ONLINE: %ML100 > %MB100 !! I don't understand why ? And idea ? Thanks
Last updated: 2025-08-06
Post by wagokurt on TargetVisu option missing in IDE
CODESYS Forge
talk
(Post)
I have installed both the Codesys Control for Linux SL 4.16.0.0 and Target Visu for Linux 4.16.0.0 packages in Codesys 3.5 SP21 Patch2. When I try to add a target visu, it is missing. I have spent hours on this and tried different machines, all behave the same way. Is this a bug?
Last updated: 2025-08-21
Post by timvh on update data/tim
CODESYS Forge
talk
(Post)
Change the actual time of your PLC. How to do this sometimes depends on the PLC you use. Please contact the vendor of the PLC to get this information. Or see the following example for using CODESYS date and time functions: https://forge.codesys.com/prj/codesys-example/date-and-time/home/Home/
Last updated: 2025-08-26
Post by eksheep on Unit Tests and C007: Unknown Type
CODESYS Forge
talk
(Post)
Hello, I am attempting to implement unit tests for my POUs. When building and running the unit tests I receive error C007: Unknown Type for all types defined in the library, Standard, 3.5.18.0. Which is included in the POU Library Manager. Any input would be appreciated. TIA.
Last updated: 2025-08-27
Post by leandroct on Creating Boot Application not working
CODESYS Forge
talk
(Post)
I did these steps and it worked: - Copied Application.app and Application.crc to the Folder C:\ProgramData\CODESYS\CODESYSControlWinV3x64\ID_of_CPU\PlcLogic\Application\ copied the visu folder content to the folder C:\ProgramData\CODESYS\CODESYSControlWinV3x64\ID_of_CPU\PlcLogic\Application\visu\ Changed by Notepad the CODESYSControl.cfg at the folder C:\ProgramData\CODESYS\CODESYSControlWinV3x64\ID_ of_CPU\ Where is [CmpApp], adding a line with: Application.1=Application
Last updated: 2025-09-04
Post by kio123 on SysFileOpen not working
CODESYS Forge
talk
(Post)
I have exactly the same problem and tried entering “ForceIecFilePath=0” in the file “CODESYSControl.cfg” ([SysFile]). Unfortunately, this was unsuccessful. Can anyone help in the meantime, e.g., with some sample code or with the FAQ that TimvH refers to above (link no longer works)? Many thanks and best regards
Last updated: 2025-09-15
How to select the real I/O module terminals/channels in CODESYS V3.5 ? Or better to say, How to specify the real physical terminals of analog and digital I/O modules in the CODESYS programm ?
CODESYS Forge
talk
(Thread)
How to select the real I/O module terminals/channels in CODESYS V3.5 ? Or better to say, How to specify the real physical terminals of analog and digital I/O modules in the CODESYS programm ?
Last updated: 2022-08-13
How to select the real I/O module terminals/channels in CODESYS V3.5 ? Or better to say, How to specify the real physical terminals of analog and digital I/O modules in the CODESYS programm ?
CODESYS Forge
talk
(Thread)
How to select the real I/O module terminals/channels in CODESYS V3.5 ? Or better to say, How to specify the real physical terminals of analog and digital I/O modules in the CODESYS programm ?
Last updated: 2022-07-29
Post by open on How to create a stopwatch?
CODESYS Forge
talk
(Post)
Hi @ph0010421 and @Ton, Is it possible to program a stopwatch to measure a system running time when it is turn on, and pause when the system is turn off. I tried your examples when stopped, the elapsed time will then be calculated, but i need the time to be continuously counting. Warmest regards,
Last updated: 2023-12-11
Post by preimesbergert on Codesys Control for Raspberry Pi 4.10.0.0 - Raspberry Pi OS > 2023-12-05
CODESYS Forge
talk
(Post)
Same issue here: Raspberry Pi 4 Model B HW 1.5 Regardless of the image (tried 32bit / 64bit version from Raspberry Pi Imager- all the "standard version") and with all tested Codesys Control versions (4.2.0, 4.8.0, 4.10.0) and regardless if single core / multicore / 64 bit variant.
Last updated: 2023-12-21
Post by smartcoco on Add visual background FB blocks.
CODESYS Forge
talk
(Post)
Can you add a background FB block to the visualization page, and loop through this FB block when the page is in display mode. This FB block requires two more functions, one for executing when the page is displayed and the other for executing when the page is closed.
Last updated: 2024-01-16
Post by scarter on Bit / Bool data types in function parameters
CODESYS Forge
talk
(Post)
Any reason BIT and BOOL data types are not interchangeable? Trying to make a function which takes a BOOL IN/OUT parameter (Not allowed to use BIT) In the main logic if I make a DINT variable, and want to use each bit on different functions CODESYS will not allow it.
Last updated: 2024-01-17
Post by acc00 on Redundancy Codesys Runtime, Synchronization
CODESYS Forge
talk
(Post)
Hi, I’m currently testing the Codesys Redundancy application with 2 Raspberry Pi, with the idea is of using in my project 2 Wago PFC200 and 1 Ethercat Master with 2 Remote IO. After I configure the redundancy, and one Pi is Active and the other is Passive, if I disconnect the Ethernet cable of the Active, the Passive become Standalone, which is good, but the problem is the following: -When I recover the Ethernet connection, both stay Standalone. They will NOT Sync until I do it manually in the Codesys environment. How to make the synchronization automatically? -If both Pi/PLC stays Standalone, who is managing the IO? (Ethercat and Serial) I have done a test with an Modbus Slave, where I am sending a counter that increase every second. And I see that when both PLC are standalone, they both keep an active connection with the Slave, and both write values. This does not seem good, since according to this in my project both PLC would try to control the IO at the same time. Note: The Codesys have an option (greyed out, not possible to select) which says “Auto Sync”. What is the purpose, and why I’m not able to select it? I'm using Codesys Control for Rapsberry Pi 64SL Runtime in my test environment (2xRaspberry Pi 4), with the idea of using Codesys Control PFC 200 Runtime in my project (2xWago PFC200 and 1 Ethercat Master with 2x Wago 750-354 Ethercat Fieldbus Coupler). Using the last Codesys 3.5 version (SP19 PAtch 5). I'd appreciate a lot any help on this questions!
Last updated: 2024-01-22
Post by masmith1553 on SDO generation
CODESYS Forge
talk
(Post)
If you add any device to the CANOpen Manager it will send messages to verify the device is on the network. Do you have the Enable expert settings check box checked in the General tab? have you added any SDOs in the SDOs tab? I avoid using the CANOpen Manager and just use the CAN_Tx and CAN_Rx blocks from the library.
Last updated: 2024-01-25
Post by wiresplus on Connect to remote PLC via local pc and teamviewer
CODESYS Forge
talk
(Post)
Hello, Depends on the architecture of your PLC. If the PLC is a PC-based item with a normal desktop environment, then you probably can. I find it simpler to install an IIoT Router in the panel, and use an encripted VPN to link to my office PC / Laptop on demand.
Last updated: 2024-01-26
Post by eschwellinger on New Ladder Diagram conversion does not work due to missing features
CODESYS Forge
talk
(Post)
The "remove unused" parameters have been added to 1.0 version as well as the "manual" removal of pins... also allowed "empty" inputs for blocks is in and the compile error described there should no longer occurs. Drag drop of variables is not yet implemented and I don't think the double-click feature yet either.
Last updated: 2024-01-29