  • eschwellinger eschwellinger posted a comment on discussion Deutsch

    Hi, mach bitte mal CANOPEN_DEBUG als compiler define und dann bitte in den SPS logger schauen.. Grüße Edwin

  • eschwellinger eschwellinger posted a comment on discussion Engineering

    it seems that you are on a 64bit plc - so the steps are: (if this error is caused by a lib you need to change the library) in order for it to run at 64 bits, you have to: - set everything to at least 3.5.5.0 - Interface lib use CmpError2, SysTypes2 and Systypes2 interfaces instead of CmpError and SysTypes, namespaces are the same but: RTS_INVALID_HANDLE is now in SysTypes and no longer in CmpErrors! There may be other interface libs that need to be raised. Replace 32 bit pointer variables with 64...

  • eschwellinger eschwellinger posted a comment on discussion Visualization

    Hi, for me it sounds like your plc needs better realtime capabilites ;-) ? Then these kind of problems should not occure. Which plc is it? If it is Control Win ( think you have mentioned this in an older post, not sure) an option would be to switch to Control RTE? BR Edwin

  • eschwellinger eschwellinger posted a comment on discussion Engineering

    Hi, i think this is the only application struct ( for multible application) which makes really sense. https://store.codesys.com/multiple-applications.html?store=en&from_store=default#Product%20Description BR Edwin

  • eschwellinger eschwellinger posted a comment on discussion Runtime

    Hallo, rotes Kreuz bedeutet tatsächlich du musst eben SMC_Homing verwenden und den /RefEndschalter z.B am Master also z.B an eine EL Klemme auflegen. Grüße Edwin

  • eschwellinger eschwellinger posted a comment on discussion Engineering

    Hi, not really sure but guess this is already solved in the 3.5SP15... current version. Possible to update to that version? BR Edwin .

  • eschwellinger eschwellinger posted a comment on discussion Visualization

    yes, i agree this need to be fixed... we will. BR Edwin

  • eschwellinger eschwellinger modified a comment on discussion Motion

    Hi, did you start with this example here? "c:\Program Files\CODESYS 3.5.15.30\CODESYS\Projects\SoftMotion\4.6.0.0\Examples\Tutorial\Robotics_PickAndPlace_without_Depictor.project"

  • eschwellinger eschwellinger posted a comment on discussion Motion

    Hi, did you start with this example here? "c:\Program Files\CODESYS 3.5.15.30\CODESYS\Projects\SoftMotion\4.6.0.0\Examples\Tutorial\Robotics_PickAndPlace_without_Depictor.project"

  • eschwellinger eschwellinger posted a comment on discussion Motion

    Hi, usually if this happens, the parameters for the length etc are not correct. https://help.codesys.com/webapp/_sm_trafo_pou_parallel_kinematics;product=codesys_softmotion;version=4.6.0.0#tripod-with-rotary-axes BR Edwin

  • eschwellinger eschwellinger posted a comment on discussion Deutsch

    Hallo Patrick, ich würde mal hier anfangen: https://www.wago.com/de/d/16186 Ich meine auch auf Youtube ein clip gesehen zu haben: nach PFC200 und VPN suchen: https://www.youtube.com/watch?v=BHng26nh4Yo Grüße Edwin

  • eschwellinger eschwellinger posted a comment on discussion Engineering

    Hi, check the following: Is WinPcap installed? turn off the firewall check the plclogger of control win an finally - which version exactly are you using? BR Edwin

  • eschwellinger eschwellinger modified a comment on discussion Visualization

    Hi, no this is not needed. Just set up the Automation Server according the fist steps: https://help.codesys.com/webapp/_cas_first_steps;product=codesys_automation_server;version=1.7.0.0 install the Edge Gateway ... upload the project to the Automation Server - deploy the application to the plc - open the Webvisu If you need some help on doing this please let me know. Regards Edwin

  • eschwellinger eschwellinger modified a comment on discussion Visualization

    Hi, no this is not needed. Just set up the Automation Server according the fist steps: https://help.codesys.com/webapp/_cas_first_steps;product=codesys_automation_server;version=1.7.0.0 install the Edge Gateway ... upload the project to the Automation Server - deploy the application to the plc - open the Webvisu Regards Edwin

  • eschwellinger eschwellinger posted a comment on discussion Visualization

    Hi, no this is not needed. Just set up the Automation Server according the fist steps: https://help.codesys.com/webapp/_cas_first_steps;product=codesys_automation_server;version=1.7.0.0 install the Edge Gateway ... upload the project to the Automation Server - deploy the application to the plc - open the Webvisu B Edwin