  • Posted a comment on discussion Engineering 🇬🇧 on CODESYS Forge

    Hello Vincent, I don't have 75 channels but it works for me as described above without any problems. There is also a parameter MAX_MODBUS_CHANNELS in the library parameters for the IoDrvModbusTCP module. The default value there is 100. Perhaps you are reaching the limit there? The value can be adjusted accordingly. I assume that this value is not accepted in the input dialogue and therefore the 'fixed' limit value 10 is used.

  • Posted a comment on discussion Engineering 🇬🇧 on CODESYS Forge

    Hi, i found a solution for me. I had installed a 'old' version of CoDeSys (3.5.18 P5). I tried to add channels there, which works fine. I created a new project, added an Ethernet-Port, added a Modbus-Master and then I copied the ModBus-Slave from my working project to the new project. Now I could add more channels. I add the channels 10 and 11. Then I deleted (please make a backup before :-) the original ModBus-Slave in my working project and copied the extended Slave back to my working project....