Post by salvadegianluca on List files in a directory with SysDiropen And SysDirRead
CODESYS Forge
talk
(Post)
Good morning; I'm facing an issue that seems being caused by the library itself. I'm trying to create the list of all the files that are stored inside a psecific directory. Unluckily the first file is allways hidden. VAR CONSTANT arysEmptyArray:ARRAY[iArrayMinDimension..iArrayMAXDimension] OF STRING := [(iArrayMAXDimension - iArrayMinDimension)('')]; iArrayMinDimension:INT := 1; iArrayMAXDimension:INT := 99; END_VAR VAR_INPUT sDirectoryToInspect:STRING; sSearchFilter:STRING; END_VAR VAR_IN_OUT xCheckFileInsideDirectory:BOOL; END_VAR VAR arysListOfFoundFiles:ARRAY[iArrayMinDimension..iArrayMAXDimension] OF STRING; sNullString:STRING; iNullIndex:INT := 0; libInfoAboutThePath:DirInfo; libResultOfThePathMonitoring:CmpErrors.RTS_IEC_RESULT; libInstanceToMonitorThePath:CmpErrors.RTS_IEC_HANDLE; sEntityToSearch:STRING; dMaxEntityDimension:DINT := SIZEOF(sEntityToSearch); libFileInfo:DirInfo; sFilteredFileName:STRING; iIndexToScrollArrays:INT; END_VAR IF xCheckFileInsideDirectory THEN arysListOfFoundFiles:=arysEmptyArray; iIndexToScrollArrays:=iArrayMinDimension; libInstanceToMonitorThePath:= SysDirOpen(szDir:= sDirectoryToInspect,szDirEntry:=sNullString,diMaxDirEntry:= iNullIndex,pDirInfo:= ADR(libInfoAboutThePath),pResult:= ADR(libResultOfThePathMonitoring)); WHILE libResultOfThePathMonitoring = Errors.ERR_OK AND iIndexToScrollArrays <= iArrayMAXDimension DO sEntityToSearch:= ''; libResultOfThePathMonitoring:=SysDirRead(hDir:=libInstanceToMonitorThePath,szDirEntry:=sEntityToSearch,diMaxDirEntry:=dMaxEntityDimension,pDirInfo:=ADR(libFileInfo)); sFilteredFileName:= FUN_06_00_FindItemInString_0(sFilter:=sSearchFilter,sSource:=sEntityToSearch); IF sFilteredFileName <> '' THEN arysListOfFoundFiles[iIndexToScrollArrays]:=sFilteredFileName; iIndexToScrollArrays:=iIndexToScrollArrays + 1; END_IF IF libResultOfThePathMonitoring <> Errors.ERR_OK THEN libResultOfThePathMonitoring:= Errors.ERR_OK; END_IF END_WHILE libResultOfThePathMonitoring:=SysDirClose(hDir:= libInstanceToMonitorThePath); xCheckFileInsideDirectory:=FALSE; END_IF How is possible to solve this issue? Any known work around?
Last updated: 2024-09-17
Post by salvadegianluca on List files in a directory with SysDiropen And SysDirRead
CODESYS Forge
talk
(Post)
Good morning; I'm facing an issue that seems being caused by the library itself. I'm trying to create the list of all the files that are stored inside a psecific directory. Unluckily the first file is allways hidden. VAR CONSTANT arysEmptyArray:ARRAY[iArrayMinDimension..iArrayMAXDimension] OF STRING := [(iArrayMAXDimension - iArrayMinDimension)('')]; iArrayMinDimension:INT := 1; iArrayMAXDimension:INT := 99; END_VAR VAR_INPUT sDirectoryToInspect:STRING; sSearchFilter:STRING; END_VAR VAR_IN_OUT xCheckFileInsideDirectory:BOOL; END_VAR VAR arysListOfFoundFiles:ARRAY[iArrayMinDimension..iArrayMAXDimension] OF STRING; sNullString:STRING; iNullIndex:INT := 0; libInfoAboutThePath:DirInfo; libResultOfThePathMonitoring:CmpErrors.RTS_IEC_RESULT; libInstanceToMonitorThePath:CmpErrors.RTS_IEC_HANDLE; sEntityToSearch:STRING; dMaxEntityDimension:DINT := SIZEOF(sEntityToSearch); libFileInfo:DirInfo; sFilteredFileName:STRING; iIndexToScrollArrays:INT; END_VAR IF xCheckFileInsideDirectory THEN arysListOfFoundFiles:=arysEmptyArray; iIndexToScrollArrays:=iArrayMinDimension; libInstanceToMonitorThePath:= SysDirOpen(szDir:= sDirectoryToInspect,szDirEntry:=sNullString,diMaxDirEntry:= iNullIndex,pDirInfo:= ADR(libInfoAboutThePath),pResult:= ADR(libResultOfThePathMonitoring)); WHILE libResultOfThePathMonitoring = Errors.ERR_OK AND iIndexToScrollArrays <= iArrayMAXDimension DO sEntityToSearch:= ''; libResultOfThePathMonitoring:=SysDirRead(hDir:=libInstanceToMonitorThePath,szDirEntry:=sEntityToSearch,diMaxDirEntry:=dMaxEntityDimension,pDirInfo:=ADR(libFileInfo)); sFilteredFileName:= FUN_06_00_FindItemInString_0(sFilter:=sSearchFilter,sSource:=sEntityToSearch); IF sFilteredFileName <> '' THEN arysListOfFoundFiles[iIndexToScrollArrays]:=sFilteredFileName; iIndexToScrollArrays:=iIndexToScrollArrays + 1; END_IF IF libResultOfThePathMonitoring <> Errors.ERR_OK THEN libResultOfThePathMonitoring:= Errors.ERR_OK; END_IF END_WHILE libResultOfThePathMonitoring:=SysDirClose(hDir:= libInstanceToMonitorThePath); xCheckFileInsideDirectory:=FALSE; END_IF How is possible to solve this issue? Any known work around?
Last updated: 2024-09-17
Post by rossanoparis on Clarifications regarding the appropriate runtime system to use
CODESYS Forge
talk
(Post)
Hallo all I would appreciate some clarifications regarding the appropriate runtime system to use. I've been using 'KUNBUS CPUs' and 'CODESYS Control for Raspberry Pi MC SL' for the last 4 years. Recently, there have been some changes in the CODESYS licensing policy. [ https://store.codesys.com/en/howto_applicationbasedlicenses ] My questions are mainly two: 1) If I need to start a new project using 'KUNBUS CPUs', which is the correct runtime system to use. 2) Old projects built using 'CODESYS Control for Raspberry Pi MC SL' should be updated to another RT system? Current RT systems ... a)CODESYS Control for Raspberry Pi MC SL b)CODESYS Control for Linux ARM SL c)CODESYS Virtual Control SL May I count on receiving an explanation to understand the differences among the runtime systems listed above? A detailed and well-organized answer would be greatly appreciated. Kind regards Rossano
Last updated: 2024-09-23
Post by lbartik on J1939 TX/RX PDU1
CODESYS Forge
talk
(Post)
Is it possible to transmit a PDU1 PGN using the J1939 manager and local device? What if I need to transmit a PGN RQST via 0xEA00 (PGN 59904)? How would I do this P2P (Destination < 0xFF) or broadcast (Destination 0xFF)? I don't think this is possible for any destination type. I don't think it's possible to receive broadcast PDU1 messages either. For example, an address claim PGN 60928 (0x18EEFF80) is addressed to all nodes (0xFF) and not any specific local device so it will be filtered out. These are major oversights in the IoDrvJ1939 library to not support every PDU1 RX/TX scenario. IoDrvJ1939 supported scenario: 1. Receive (RX) PDU1 (P2P) destination-specific (PDU-specific < 255) to local device with matching address IoDrvJ1939 unsupported scenarios: 1. Receive (RX) PDU1 (P2P) global (PDU-specific = 255) 2. Transmit (TX) PDU1 (P2P) global (PDU-specific = 255) 3. Transmit (TX) PDU1 (P2P) destination-specific (PDU-specific < 255)
Last updated: 2024-09-23
Post by egau on Hard shutdown: no code on device after power on
CODESYS Forge
talk
(Post)
Hi, We have a machine running Codesys on a Windows IPC (CODESYS Control Win v3 - x64). When we hard shutdown the machine, the code on the PLC sometimes becomes "corrupted" after a power on (When trying to login to the PLC, we get the message "The application 'Application' does not exist on device."). I've noticed these errors in the logs, but I'm not sure what to make of them. We are not using any RETAIN variables in our code, although I'm not sure about referenced librairies. (we are using the persistence manager). I'm pretty sure that not doing a graceful shutdown is the root cause of this. This being said, what is the proper way of doing a graceful shutdown? Is putting the Codesys application in "stop" sufficient? I know how to implement this, so if it works then it would be a quick fix. However, I think we need to add a UPS, which would detect power loss and inform the PLC that it needs to initiate its shutdown, and then the PLC would shutdown gracefully. Any help with this will be greatly appreciated :)
Last updated: 2024-10-03
Post by egau on Hard shutdown: no code on device after power on
CODESYS Forge
talk
(Post)
This explanation aligns with the issues we’re experiencing with our machines. The scenario I described is happening with one of them (let’s call it Machine A). This machine is identical to another one (Machine B), except for some custom code that facilitates communication with an external Beckhoff PLC for MES integration in the production line. Machine B has been powered on and off daily for at least three months and has never had this problem. Given that, I highly doubt the MES custom code is the cause of the code corruption. This being said, your explanation does seem plausible. However, if faulty EtherCAT cables were the issue, why wouldn't the error occur during normal operation? Why would bad cables only cause problems during a hard shutdown? One last question: When you encountered this behavior, did you see a similar error in your logs? i.e, an "AccessViolation" exception in the EtherCAT Task?
Last updated: 2024-10-03
Post by lsislsis on SIGABRT Error
CODESYS Forge
talk
(Post)
Please help us. Why we take this errors. We try different versions like 4.12.0 and 4.13.0 with same results. ;*********;<loggername>codesyscontrol.log</loggername>;<logoptions>; <enable>1</enable>; <type>normal</type>; <timestamp>rtc high resolution</timestamp>; <deactivatable>0</deactivatable>; <dump>always</dump>; <filter>0x0000000f<filter>; <maxentries>100000</maxentries>; <maxfiles>1</maxfiles>; <maxfilesize>1000000</maxfilesize>;</filter></filter></logoptions>;<entries>;Timestamp, CmpId, ClassId, ErrorId, InfoId, InfoText;ClassId: LOG_INFO =1;ClassId: LOG_WARNING =2;ClassId: LOG_ERROR =4;ClassId: LOG_EXCEPTION =8;ClassId: LOG_DEBUG =16;ClassId: LOG_PRINTF =32;ClassId: LOG_COM =64;</entries>;*********2024-11-05T08:23:59.728Z, 0x0000100c, 1, 0, 0, VisuFctCheckForUnusedClients: Removing Client with IEC-ID: 1 Time delta: T#33s1ms Locks: Paintbuffer: TRUE 2024-11-05T08:23:59.728Z, 0x0000100c, 1, 0, 0, VisuFctCheckForUnusedClients: Successfully Removed Client at Address: 547195449944, IEC-ID was: 1, EXT-ID: 431000373 2024-11-05T08:28:57.913Z, 0x0000100c, 1, 0, 0, Visu_PRG: Creating Client for Extern-ID: 347055752 2024-11-05T08:28:57.926Z, 0x0000100c, 1, 0, 0, Visu_PRG: Creating Client successful for Extern-ID: 347055752 Returned IEC-ID: 1 2024-11-05T08:30:51.103Z, 0x0000100c, 1, 0, 0, Visu_PRG: Successfully Removed Client with IEC-ID: 1, Extern-ID: 347055752 2024-11-05T08:37:36.517Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state* We recommend a reboot of the controller now! 2024-11-05T08:37:36.517Z, 0x00000111, 8, 260, 3, #### Exception: HANDLED EXCPT <excpt>NonContinuable</excpt> in CH_COMM_CYCLE 2024-11-05T08:47:42.117Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T08:47:42.117Z, 0x00000111, 8, 260, 3, #### Exception: HANDLED EXCPT <excpt>NonContinuable</excpt> in CH_COMM_CYCLE 2024-11-05T09:14:41.316Z, 0x00000071, 1, 0, 13, Webserver stopped 2024-11-05T09:14:44.485Z, 0x0000013d, 1, 0, 4, Number of licensed cores for IEC-tasks: 1 from 4 2024-11-05T09:14:44.487Z, 0x0000013d, 1, 0, 4, Number of licensed cores for IEC-tasks: 4 from 4 2024-11-05T09:14:44.540Z, 0x00000002, 1, 0, 2, Application [<app>Application</app>] loaded via [Download] 2024-11-05T09:14:55.894Z, 0x00001012, 1, 0, 0, Opened alarm storage file, version: 6 2024-11-05T09:14:55.951Z, 0x0000100c, 1, 0, 0, Visuinitialization starting. 2024-11-05T09:14:55.983Z, 0x0000100c, 1, 0, 0, Visuinitialization done. 2024-11-05T09:14:55.995Z, 0x00000071, 1, 0, 12, Webserver started 2024-11-05T09:15:01.753Z, 0x0000100c, 1, 0, 0, Visu_PRG: Creating Client for Extern-ID: 2279884529 2024-11-05T09:15:01.753Z, 0x0000100c, 1, 0, 0, Visu_PRG: Creating Client successful for Extern-ID: 2279884529 Returned IEC-ID: 0 2024-11-05T09:34:44.667Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T09:34:44.667Z, 0x00000111, 8, 260, 3, #### Exception: More than 2 exceptions in CH_COMM_CYCLE: Stop logging 2024-11-05T10:13:26.867Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T10:15:21.966Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T10:19:12.167Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T10:26:02.566Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T10:31:42.866Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T11:01:54.468Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T11:09:29.868Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! 2024-11-05T11:14:44.540Z, 0x0000100d, 1, 0, 0, Demo mode expired. 2024-11-05T11:27:20.868Z, 0x00000103, 65544, 1, 0, runtime received SIGABRT - system may be in an inconsistent state We recommend a reboot of the controller now! * Regards
Last updated: 2024-11-05
Post by spiessli on Raspberry Pi 4 with Legacy Drivers and Codesys 3.5.19 Patch 4
CODESYS Forge
talk
(Post)
Hi, I wanted to use the Adafruit Hat for the Raspberry and get acquainted with Softmotion using servos for RC models. This did work great with Codesys 3.5.19 Patch 1, but with Patch 4 and 5 i get errors. I suspect changes in the SoftMotion library have broken dependencies in the legacy drivers, might that be true? Thanks for any hint, spiessli Here the error log: ------ Übersetzungslauf gestartet: Applikation: Device.Application ------- Code typisieren... Code erzeugen... [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.6.0.0 (3s - smart software solutions gmbh): GetStandardConfigParams AXIS_REF_SERVO: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet Übersetzung abgeschlossen -- 15 Fehler, 0 Warnungen : Kein Download möglich
Last updated: 2023-12-19
Post by spiessli on Raspberry Pi 4 with Legacy Drivers and Codesys 3.5.19 Patch 4
CODESYS Forge
talk
(Post)
Thanks for the suggestion, I have tried it eagerly: I have updated all packages to latest version with Codesys Installer and installed newest runtime and gateway on Raspberry Pi. Unfortunately, the error is still there. As soon as I add the SM_Drive_Servo to the device tree, I get the error below when generating the code. Reverting SM3_Basic to version 4.14 makes the error disappear. ------ Übersetzungslauf gestartet: Applikation: Device.Application ------- Code typisieren... Code erzeugen... [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0032: Typ 'Unbekannter Typ: 'ConfigGetParameterValueLREAL(pParam, 0)'' kann nicht in Typ 'LREAL' konvertiert werden [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0046: Bezeichner 'ConfigGetParameterValueLREAL' nicht definiert [FEHLER] sm3_drive_servo, 4.10.0.0 (codesys): GetStandardConfigParams [AXIS_REF_SERVO]: C0035: Programmname, Funktion oder Funktionsbausteinstanz an Stelle von 'ConfigGetParameterValueLREAL' erwartet Übersetzung abgeschlossen -- 15 Fehler, 0 Warnungen : Kein Download möglich
Last updated: 2023-12-20
Post by ara32 on CODESYS 4 Linux:
CODESYS Forge
talk
(Post)
Hello! I managed to correctly launch CODESYS Developer Studio 3.5.17, almost all functionality works. The only issue remaining is that when connecting to a device and obtaining its public key, the NCryptEncrypt function is called, which is not fully implemented in the DLL source code, resulting in the connection not being established. Currently, the code of this function in the Wine repository looks like this: SECURITY_STATUS WINAPI NCryptEncrypt(NCRYPT_KEY_HANDLE key, BYTE *input, DWORD insize, void *padding, BYTE *output, DWORD outsize, DWORD *result, DWORD flags) { struct object *key_object = (struct object *)key; TRACE("(%#Ix, %p, %lu, %p, %p, %lu, %p, %#lx)\n", key, input, insize, padding, output, outsize, result, flags); if (flags & ~(NCRYPT_NO_PADDING_FLAG | NCRYPT_PAD_OAEP_FLAG | NCRYPT_PAD_PKCS1_FLAG | NCRYPT_SILENT_FLAG)) { FIXME("Flags %lx not supported\n", flags); return NTE_BAD_FLAGS; } if (flags & NCRYPT_NO_PADDING_FLAG || flags & NCRYPT_PAD_OAEP_FLAG) { FIXME("No padding and oaep padding not supported\n"); return NTE_NOT_SUPPORTED; } if (key_object->type != KEY) return NTE_INVALID_HANDLE; return map_ntstatus(BCryptEncrypt(key_object->key.bcrypt_key, input, insize, padding, NULL, 0, output, outsize, result, flags)); } The program crashes due to the NCRYPT_PAD_OAEP_FLAG flag. I'm not proficient in C++, but I attempted to add handling myself, and here's the result: SECURITY_STATUS WINAPI NCryptEncrypt(NCRYPT_KEY_HANDLE key, BYTE *input, DWORD insize, void *padding, BYTE *output, DWORD outsize, DWORD *result, DWORD flags) { struct object *key_object = (struct object *)key; TRACE("(%#Ix, %p, %lu, %p, %p, %lu, %p, %#lx)\n", key, input, insize, padding, output, outsize, result, flags); if (flags & ~(NCRYPT_NO_PADDING_FLAG | NCRYPT_PAD_OAEP_FLAG | NCRYPT_PAD_PKCS1_FLAG | NCRYPT_SILENT_FLAG)) { FIXME("Flags %lx not supported\n", flags); return NTE_BAD_FLAGS; } if (flags & NCRYPT_NO_PADDING_FLAG) { FIXME("No padding not supported\n"); return NTE_NOT_SUPPORTED; } BCRYPT_OAEP_PADDING_INFO oaepInfo = { 0 }; oaepInfo.pszAlgId = BCRYPT_SHA1_ALGORITHM; NTSTATUS status = BCryptEncrypt(key_object->key.bcrypt_key, input, insize, &oaepInfo, NULL, 0, output, outsize, result, flags); if (key_object->type != KEY) return NTE_INVALID_HANDLE; return map_ntstatus(BCryptEncrypt(key_object->key.bcrypt_key, input, insize, padding, NULL, 0, output, outsize, result, flags)); } Now, when calling the connection, it crashes with the error "bcrypt:BCryptEncrypt flags 0x4 not implemented." Can anyone help with enhancing this functionality or at least point me in the right direction?
Last updated: 2024-03-22
Post by jickisticki on Witch library?
CODESYS Forge
talk
(Post)
Crafting my Fellowship Personal Statement was like weaving the threads of my aspirations into a tapestry of words. Each sentence became a brushstroke, painting a vivid portrait of my journey and ambitions. Beyond being just a document, it became a mirror reflecting the depth of my experiences. Like a conductor guiding an orchestra, my personal statement was composed to resonate with my unique voice. In the realm of specialized opportunities, this statement serves as a compass, guiding me toward the next chapter of my professional growth. With each word, I felt the guidance of mentors shaping my story into an eloquent narrative.
Last updated: 2023-08-17
Post by ellcap on Did a library update and now can't open project
CODESYS Forge
talk
(Post)
EDIT: Title was a mistake. Should say now I can't compile / download project. Codesys V3.5SP19 Patch 2. Updated the libraries/packages using the Codesys Installer. I'm hit with this error ------ Build started: Application: ------- Typify code... [ERROR] iecvaraccess, 4.4.0.0 (system): IecVarAccess: C0086: No definition found for interface 'IIecVarAccess17' [ERROR] iecvaraccess, 4.4.0.0 (system): IecVarAccess: C0077: Unknown type: 'IIecVarAccess17' [ERROR] iecvaraccess, 4.4.0.0 (system): Initialize [IecVarAccess]: C0032: Cannot convert type 'IECVARACCESS(iecvaraccess, 4.4.0.0 (system))' to type 'IIecVarAccess17' [ERROR] iecvaraccess, 4.4.0.0 (system): QueryInterface [IecVarAccess]: C0231: Expression of type 'BOOL' expected in this place [ERROR] iecvaraccess, 4.4.0.0 (system): QueryInterface [IecVarAccess]: C0077: Unknown type: 'ITFID_IIecVarAccess17' [ERROR] iecvaraccess, 4.4.0.0 (system): QueryInterface [IecVarAccess]: C0046: Identifier 'ITFID_IIecVarAccess17' not defined Compile complete -- 6 errors, 101 warnings Build complete -- 6 errors, 101 warnings : No download possible
Last updated: 2023-09-25
Post by damian177 on Codesys V3.5 + Pixtend v1.3 + RaspberryPi
CODESYS Forge
talk
(Post)
Hi, I use Pixtend v1.3 with my RaspberryPi with Codesys V3.5 SP15 Patch1. Actually in my project I used two packages: - CODESYS Contro for Raspberry PI 3.5.15.10 - PiXtend for CODESYS 1.3.8.0 Now I would like to extend my project about the IIot Libraries SL package, I installed them. Next I added SMS_Service_SL 1.0.0.8 version library and I have problem with compile my project because I get error: [ERROR] PiXtend_DemoProject_q: Library Manager [Device: PLC Logic: Application]: Could not open library '#CAADTUtil'. (Reason: The placeholder library 'CAADTUtil' could not be resolved.) Any have idea what can I do to properly add SMS library to my project?
Last updated: 2023-09-26
Post by derpaul on PFC200 Update to 4.9.0.0 - No Connection
CODESYS Forge
talk
(Post)
Hallo Today I decided to perform an Update on my PFC200 but after the Update the Device was not reachable anymore. I tried reseting to factory reset. Software reset and so on, but nothing helps... In my Router I can see it, I cann SSH into the PFC200 but it is not reachable. Then I try to go back to 4.8.0.0 But now I get this error: [INFORMATION] Befehl SSH auf root@192.168.1.17 ausführen: Laufzeitsystem stoppen [FEHLER] Fehlerausgabe: /etc/init.d/codesyscontrol: line 34: /opt/codesys/scripts/init-functions: No such file or directory [INFORMATION] Standardausgabe: /etc/init.d/codesyscontrol: line 34: /opt/codesys/scripts/init-functions: No such file or directory Please help, I can't get this thing working... Regards
Last updated: 2023-09-27
Post by derpaul on PFC200 Update to 4.9.0.0 - No Connection
CODESYS Forge
talk
(Post)
Hallo Today I decided to perform an Update on my PFC200 but after the Update the Device was not reachable anymore. I tried reseting to factory reset. Software reset and so on, but nothing helps... In my Router I can see it, I cann SSH into the PFC200 but it is not reachable. Then I try to go back to 4.8.0.0 But now I get this error: [INFORMATION] Befehl SSH auf root@192.168.1.17 ausführen: Laufzeitsystem stoppen [FEHLER] Fehlerausgabe: /etc/init.d/codesyscontrol: line 34: /opt/codesys/scripts/init-functions: No such file or directory [INFORMATION] Standardausgabe: /etc/init.d/codesyscontrol: line 34: /opt/codesys/scripts/init-functions: No such file or directory Please help, I can't get this thing working... Regards
Last updated: 2023-09-27
Post by ofey on Modbus TCP communication
CODESYS Forge
talk
(Post)
Hi! I tried setting up the PLC I'm working with (Beijer GN-9373) to connect to a modbus master running on a laptop. I have an ethernet connection (via USB-C to ethernet) between the laptop and the controller. I have tried following tutorial on how to set this up. I have added an ethernet device with the IP-address of the PLC. Further I added a ModbusTCP_Slave_Device with default settings. I get the error "Failed to open TCP Port: 1" when I try to go online with the PLC. Earlier I tested the exact same set up with the soft PLC from codesys. I can then read/write values correctly with the Modbus master i have running on the laptop. Hope anybody can help me with this, thanks in advance!
Last updated: 2023-10-06
Post by matthew on New Ladder Editor Issues
CODESYS Forge
talk
(Post)
Hi There, When using the new ladder editor there is no option for function blocks to Remove uncalled FB call parameters. I also see no update function block. When you double click the function block it no longer opens the function block. I also now get warnings if I insert FB call without a contact in front. Warning is: (Impl)): C0373: Expression or part of it has no effect I take it the new editor must work differently? The only reason for using new ladder editor is the ST execute/block editing is far better, If you have alot of text in the old ST execute the editor window is very small and when online it's even worse. The new ST block seems a lot better Thanks!
Last updated: 2023-10-10
Post by simotion on Pointer to Softmotion axis
CODESYS Forge
talk
(Post)
In my projet I use Softmotion. There are several Softmotion axis (type SM_Drive_Virtual). In the Global Variable List I have an array of pointers to the adress of the Axis. Axis : ARRAY[1..iMaxCntAxes] OF POINTER TO AXIS_REF_SM3 := ADR(AX01_Axis), // [1 ADR(AX02_Axis), // [2] This works, but when compiling I get the message : . [WARNING] E3D: GVL Device: PLC Logic: Application: C0564: A reference to uninitialized variable AX01_Axis is used for initialization of Axis. Accessing the uninitialized variable may result in unexpected behavior. [WARNING] E3D: GVL Device: PLC Logic: Application: C0564: A reference to uninitialized variable AX02_Axis is used for initialization of Axis. Accessing the uninitialized variable may result in unexpected behavior. Is there a way when initializing to force the hardware (softmotion axis) to first initialize and then the Global Variable List?
Last updated: 2023-10-25
Post by ewi04 on Recipe Manager - RecipeManCommands, load & write wrong values, Bug?
CODESYS Forge
talk
(Post)
I'm getting closer to the error. The combination of STRUCT and ARRAY probably causes the strange behavior. As soon as the ARRAY is followed by a variable, the problem arises. Examples: X: ARRAY[1..2] OF INT; // okay Y: ARRAY[1..2] OF STRUCT; // problem Z: STRUCT; Z.ArrayOfInt[1]; // okay Z.ArrayOfStruct[1].Variable // problem // *update - array of array also causes the error A: ARRAY[1..2] OF ARRAY[1..4] OF BOOL; // problem I can't be the only one who has this problem. Or? Maybe there is a solution. Anyone? Or is it a bug after all?
Last updated: 2023-11-17
Post by felipemsgarcia on Edge Gateway online, but PLC is not online
CODESYS Forge
talk
(Post)
Hello, Up until yesterday (2023/11/20) I was able to connect to the PLC remotely with no issues through Edge Gateway. However, today I can see the Edge Gateway online but I can find the PLC even if I do a network scan. Following the same path as janber0206 @ https://forge.codesys.com/forge/talk/automation_server/thread/e78b11d7e9/, I looked into certificates and found that one of the Trusted publisher certificates has expired earlier today (2023/11/21). Please see image. Questions are: Does it affect the connection to the PLC through Edge Gateway? How do I fix it? Thank you very much in advance!
Last updated: 2023-11-21
Post by appling on License status of Linux 64Bit runtime via CLI
CODESYS Forge
talk
(Post)
Hi, I have a Linux 64Bit system with a Codesys application running on it. It stops after 2hours and a few minutes, which makes me think something is wrong with the installed license. (in my last timing it stopped after 2h4min, on the codesys website it is stated that runtimes without a license stop after 2h) I installed the license via a USB license dongle that I activated on my workstation with the Codesys IDE a while ago. Now the system is shipped at not accessible physically, only remotely via SSH. So is there a way to check the status of the License of the Codesys runtime when it is running on the system? Running the codesyscontrol script with "status" just tells me that it is running, but does not provide any license information. Best regards
Last updated: 2023-12-04
Post by manuknecht on Using SMC_MOVTYP.INITPOS without specifying the start position
CODESYS Forge
talk
(Post)
I am using the object SMC_GEOINFO to generate a trajectory and move a system accordingly using the SMC_INTERPOLATOR function block similar to the sample project CNC10_DynamicPath.project. According to the documentation, the movement type INITPOS does not require a start position in the SMC_GEOINFO object, which is confirmed in the documentation of the SMC_GEOINFO object. When using the movement type INITPOS however, the motion will still start from the starting point defined in the SMC_GEOINFO object (0,0,0 if not specified otherwise). Does someone know how to resolve this or is there an example project that makes use of the INITPOS movement type without specifying the starting point? Thanks in advance!
Last updated: 2023-12-15
Post by sean-barton on Function block method default arguments
CODESYS Forge
talk
(Post)
I have default arguments specified for function block methods but when calling a method, an error is produced requiring me to supply all the arguments despite there being default values. According to the online documentation, under section "Calling a Method" and subsection "argument passing" of the following link: https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_obj_method.html "Passing an argument for an input ... can be omitted ... for which a default or initial value was specified in the declaration..." I have found this to be the case for all Codesys IDEs I've used, 3.5.11, 3.5.16, 3.5.17, 3.5.19. Am I missing something?
Last updated: 2023-12-21
Post by sawicpx on CANbus Remapping PDOs During Runtime
CODESYS Forge
talk
(Post)
Hello, I am working on an application where I need to remap PDOs to a different CANopen object during runtime depending on what value is at a specific register. I have gotten to the point where I put the device into Preoperational State using the CIA405.NMT function. I then reconfigure the PDO 180x and 1a0x obejcts usings SDOs to point to a new canopen object on the device however when I go to restart the Device from PREOP to OP using the CIA405.NMT function the device is reset back to the original configuration as per the initial setup. I am wondering is there any way to change the PDOs at runtime is there some more functionaility I can access to do this. Any direction is appreciated!
Last updated: 2023-12-22
Post by dhumphries on Codesys device configuration
CODESYS Forge
talk
(Post)
First make sure the programming laptop and HMI are both on the same subnet. For example if the IP address of the HMI is 192.168.1.125 with a subnet mask 255.255.255.0 set your laptop IP to 192.168.1.120 with a subnet mask of 255.255.255.0. Make sure the cables are fully connected (the ethernet port on my programming laptop will click once but the cable is not fully seated.) Make sure the HMI is powered on, try pinging the device from a command prompt, if you can't ping the HMI there is a network issue that has to be resolved first.