Search talk: if statement

 
<< < 1 .. 4 5 6 7 8 .. 36 > >> (Page 6 of 36)

Post by robpqs on Program from one PLC to other WAGO 750-8204 CODESYS Forge talk (Post)
Hello, You use the WAGOUpload tool. You can download it on the download center of WAGO. Make a backup and restore it on the new device. (if can check the remanent data to copy the persistent variables if necessary) You can also use a SD card, go to the WBM copy it the image to the SD card and restart the other controller on the SD card. In the WBM, copy it back to the internal flash. If you contact your local Wago office, they will more than probably help you. There is also a WAGO forum. RP,
Last updated: 2024-05-27

Post by orbis-tertius on 3.5 P20 hangs - no response CODESYS Forge talk (Post)
Is there anybody can help me with the same problem? I have to migrate created project in ver.3.5.17.0 32BIT with runtime 4.7.0 to ver.3.5.20.0 64BIT with runtime 4.7.11.0 due to the new license. All the libraries and dependencies are updaded and there are no any errors. The first compilation and loading to the controller is being compleated well. After this being done and if I am forced to change any values or change any code in the current project, another compilation will be freezed. This problem can be solved if pressed Build/cleen or cleen all. There is another method to solve this; if project is loaded with excluded object (Alarm Configuration), repeated compilations will be done well.
Last updated: 2024-06-27

Post by andre-luis on Check if Codesys runtime is on 'Running' or 'Stopped' state? CODESYS Forge talk (Post)
Hi there, I'm running the Codesys runtime on Windows 64 and I need to know if it is on "Running" or "Stopped" state just after a system crash. The following commands works perfectly well to (re)start it... net stop “CODESYS Control Win V3 - x64" net start “CODESYS Control Win V3 - x64" ...however I'm unable to determine when it is required to be call; I mean, by checking the System Tray icon, it is possible to know if it is on "Stopped" state, but I wanted to run a .BAT command to retrieve it. How can we do that?
Last updated: 2024-07-02

Post by naks on Change IP address from IEC code CODESYS Forge talk (Post)
Hi, I'm working with wago 750-8212 controller. I want to change the IP address of the Ethernet adapter from webvisu. I have read some other threads in this forum and I have tried the following: Added the following text to the config file CODESYSControl.cfg: [SysSocket] Adapter.0.Name="br1" Adapter.0.EnableSetIpAndMask=1 Used the below code : IF xUpdateEthernet THEN Ethernet.Enable := FALSE; Reconfig ( xExecute := TRUE, itfNode := Ethernet, eError => ErrorReconfig, xBusy => xBusy, xDone => xDone, xError => xErrorReconfigure); IF Reconfig.xDone THEN ErrorCode := Ethernet.UpdateConfiguredIPSettings(IpAddress := NewIp, gateway := newGateway, subnetmask := newSubnetmask); END_IF IF Reconfig.xDone OR Reconfig.xError THEN reconfig(xExecute := FALSE); END_IF Ethernet.Enable := TRUE; Reconfig(xExecute := TRUE, itfNode := Ethernet ); END_IF I could change the IP address but when i restart my Controller then the IP address resets to the original, Is there anything I have missed, what else can i try ? Thank you in advance.
Last updated: 2024-07-08

Post by alez on CANopen safety , SRDO error behavior CODESYS Forge talk (Post)
I have a project in which there is a Safety device in CANopen, and the PLC interfaces with it as Master. I would like to understand if it is possible to set the behavior in case one of the SRDOs that I receive from the slave is no longer received. From what I have seen, if the SRDOs are not received, the CANopen safety status becomes "Not in progress" and the mapped variables freeze at the last value detected. I want to understand if it was possible to set the variables connected to the SRDOs to take a default value (e.g. zero) in the event of a CANOpen error during reception.
Last updated: 2024-07-15

Post by mondinmr on Jitter problems on imx8 CODESYS Forge talk (Post)
SOLVED!!! In this imx8 max_cstate=1 in kernel boot parameters is not working! We found a workaround: #include <stdio.h> #include <fcntl.h> #include <unistd.h> #include <stdint.h> int main(void) { int fd; uint32_t value = 0; fd = open("/dev/cpu_dma_latency", O_WRONLY); if (fd < 0) { perror("Error opening /dev/cpu_dma_latency"); return 1; } if (write(fd, &value, sizeof(value)) != sizeof(value)) { perror("Error writing to /dev/cpu_dma_latency"); close(fd); return 1; } while (1) { pause(); } } This simple code launched before CODESYS do the same work! Now jitter is identical as measured by cyclictest!
Last updated: 2023-10-19

Post by tehthoams on Find Function: Object reference not set to an instance of an object. CODESYS Forge talk (Post)
Hey, Sorry this isn't super helpful, but i had this problem once and was able to resolve it. I can't recall how I solved it and whether it was a problem with my codesys installation or the project itself. If it is the codesys installation, make sure all your required libraries and plugins are installed and available. compare with a colleagues installation if possible. I vaguely recall saving a copy of my project and deleting things one by one until the error went away...
Last updated: 2023-10-30

Post by tehthoams on Find Function: Object reference not set to an instance of an object. CODESYS Forge talk (Post)
Hey, Sorry this isn't super helpful, but i had this problem once and was able to resolve it. I can't recall how I solved it and whether it was a problem with my codesys installation or the project itself. If it is the codesys installation, make sure all your required libraries and plugins are installed and available. compare with a colleagues installation if possible. I vaguely recall saving a copy of my project and deleting things one by one until the error went away...
Last updated: 2023-10-30

Post by joanm on Tab control element, hide/show tabs programatically? CODESYS Forge talk (Post)
Hi all, Is it possible to hide or show tabs from the PLC code? I have created a few tabs in my visualizations to configure the program behavior, I'd like to be able to hide some of them if the related option in the main tab has been disabled. Is that possible? if so, how should I do it? Thank you all in advance.
Last updated: 2023-11-25

Post by suthesan on Error when I go online on Simulation or PLC CODESYS Forge talk (Post)
Hello I not sure if I made this topic under the right category. But I have a error, when I try to run a simple code on simulation or PLC. I have also tried to make a fresh project. I am testing the PLC and want to see if there is some way I can make an actuator run. Please help by looking at the picture, Iam stuckd and I don't know how to fix it.
Last updated: 2024-02-07

Post by marcolim on RPC failed 0x16c9a085 CODESYS Forge talk (Post)
Hello Matteo, I think the problem is about configuration of firewall (windows firewall usually). You can disable temporary the firewall to check if the communication works. Eventually you can: Go to the control panel -> Windows Defender Firewall -> Allow an app or feature Enable the options to change the settings. Scroll down in the application list to CODESYS and CODESYS ControlService. If you don’t see this application add it to the list. Make sure that all the checkboxes are checked (Domain, Private and public).
Last updated: 2024-04-01

Post by pjoret on IFM CR711S Can Low Level Library Use CODESYS Forge talk (Post)
Hello, I'm using CR711S from IFM and I would like to use the CAA Can Low Level in de Safety part. I already use it on the Standard part and it works properly. I would like to know if there is some restriction on using it on the safepart of the PLC (I tried but my PCL put himself in Stop...) ? And if you have some example or even a forum with some types on IFM and CoDeSys, I would Take It. Have a nice Day.
Last updated: 2024-04-03

Post by eschwellinger on License problem gateway CODESYS Forge talk (Post)
I just try to help. Anyway it is a big difference if a Store SL runtime or an oem plc and licence is used. These licenses need to be activated on plc side - so you have dependencies to the version (CODESYS and Runtime Version) Did you ever ask Epis out for this situation? They should know which license fit to their device. Even they should know if the device is capable for Softmotion and see the requiremnts in the CODESYS store: Runtime 4.9.0.0 - how should this work with Epis 3.5.16.x? Anyway refund is not a problem.
Last updated: 2024-04-26

Post by timvh on Codesys SVN CODESYS Forge talk (Post)
If you use 3.5 SP10, then Git is not supported. SVN will work fine, but with this version you do need a USB key, because software licenses are not supported with this version. Off course you can work without SVN (or Git), but especially if you work with multiple developers on one project, it will save you a lot of time and you can keep track of all changes and improvements much easier. So how much is this worth to you?
Last updated: 2024-04-30

Post by hjohnson123 on Automatically selecting a visualization element CODESYS Forge talk (Post)
I'm looking to automatically select a text field element in my visualization. I'm not sure if this is possible, as I don't know how to get the data on specific elements. I am wanting automatic selection of the text field, as I am using a keyboard-input barcode scanner, which should always input the barcode into the text field whenever a barcode is scanned. Does anyone know if this can be done?
Last updated: 2024-05-21

Post by ph0010421 on General question about library versions CODESYS Forge talk (Post)
Hello I can't find anything to read on the subject so I'll ask here. Up to now, when adding a (for example) Modbus Master, I've selected the version <= the RT version, so if I'm using SP13 Patch 3, I can use a library that doesn't exceed this. I've no idea if this is correct, but it's always worked. Can someone explain the 4.x.x.x libraries that have appeared; are they tied to a RT version? The controller I use is now at SP18Patch60, so should I continue to use 3.5.xxx or change? thanks
Last updated: 2024-05-29

Post by paro on send appliaction files to wago plc (codesys 3.5) via ssh CODESYS Forge talk (Post)
Hi, it is enough to copy the files to /home/codesys/PlcLogic/Application and adding the lines [CmpApp] Application.1=Application to the eRUNTIME.cfg, if your Application in your program is also called "Application". Reboot -> Bootapp should be loaded. If not please check the log /var/log/runtime.log There should be a line which explains why the bootproject is not loaded.
Last updated: 2024-05-29

Post by kris-samoy on Get Alarm status in Codesys CODESYS Forge talk (Post)
I am rather new to Codesys and I'm trying to figure out how to get the status of an alarm. This to interlock the start of a device until the alarm has been acknowledged... I am not sure if IAlarm.GetState (METH) can be used for this purpose. If yes then could someone please briefly explain how to use this? https://content.helpme-codesys.com/en/libs/AlarmManager/4.1.0.0/Interfaces/pou-IAlarm/GetState.html Thx & grtz, Kris
Last updated: 2024-06-03

Post by mandeepahujaifm on Ethernet/IP 4.6.0 causing exceptions? CODESYS Forge talk (Post)
I have experienced the same with one of our customers after updating EIP Scanner to 4.6.0.0 and really baffled by it. The core dump simply shows error with ENIPScanner I/O task and on analyzing it says no source code available for 4.6.0.0. Contemplating to go back to 4.5.1 but 4.6.0.0 has some really nice fixes. I guess it don't matter if it crashes anways. Please keep us posted if you find anything.
Last updated: 2024-07-11

Post by mubeta on Some 'pathetic' errors in SoftMotion program CODESYS Forge talk (Post)
Yes, this point is part of my misunderstanding. Why, after the execution ot the motion FBs is set to FALSE and exsecuted at lest one time, it must be continuosly called, even if the motion control it's take from another subsequent instruction. This is what I really don't undertand, but what in fact it's happening. For example, in case of stopping a MoveVelocity FB, then Halting the motion by the related FB, the axis at spot goes into error. If there was bad trigger management, the various instructions would NEVER work.
Last updated: 2024-07-18

Post by micik on ERR_OK not recognized CODESYS Forge talk (Post)
Hello, if I try to use ERR_Ok in my code to check whether the file is open correctly or not, I get an error "Identifier ERR_OK not recognized", I can use plain 0 (zero) instead. But in general, is this a proper way to check for success of file operation since the 4th parameter is a poinmter to RTS_IEC_RESULT, and normally I would expect this to be used somehow. _hFile := SysFileOpen(_sFileName, am:=SysFile.ACCESS_MODE.AM_WRITE, ADR(_result)); IF _result <> 0 THEN udDiag := 100; RETURN;
Last updated: 2024-08-17

Post by carohe on %t SystemTime in Variable CODESYS Forge talk (Post)
Hello, if you enter %t as a "Text" on a rectangle and do not link a variable in "Text variable", it automatically displays the system time. My question is, where do if find a variable, that contains exactly this time? I tried numerous variants using GetLocalDateTime or GetSysTime but I always have to manage timezones myself (which I do not want to do). I only want a variable with the date an time from my windows system, where the visualization is running. Where can I find this variable?
Last updated: 2024-08-20

Post by richiemuia on Static Analysis, Loading Files via script. CODESYS Forge talk (Post)
I've seen that you can use cmds like below to run SA from scripts. system.commands["staticanalysis", "run"].execute() But I would like to run different SA configuration files to create separate logs and cant find anywhere in the scripting engine if this is supported. This stems from if I turn on everything, SA stops reporting issues in the message log when the list gets over 600ish issues. Once we have done an initial clean up of code this wont be an issue, but I'm trying to get a baseline to track improvement.
Last updated: 2024-08-21

Post by richiemuia on Static Analysis, Loading Files via script. CODESYS Forge talk (Post)
I've seen that you can use cmds like below to run SA from scripts. system.commands["staticanalysis", "run"].execute() But I would like to run different SA configuration files to create separate logs and cant find anywhere in the scripting engine if this is supported. This stems from if I turn on everything, SA stops reporting issues in the message log when the list gets over 600ish issues. Once we have done an initial clean up of code this wont be an issue, but I'm trying to get a baseline to track improvement.
Last updated: 2024-08-21

Post by timvh on Communication between applications on same device/controller/runtime (Win RTE 3.5.20.20) CODESYS Forge talk (Post)
The RTE will take the RTE license. The HMI will take the HMI license. For the Application Based Licenses, the Runtime will take the smallest which is required. So if you have an application running EtherCAT and no visualization, only the Control with support for EtherCAT is used. If you have another runtime which requires the visualization, it will take the smallest Control license which is required and available + the smallest visualization license which is required.
Last updated: 2024-10-01

<< < 1 .. 4 5 6 7 8 .. 36 > >> (Page 6 of 36)

Showing results of 877

Sort by relevance or date