Post by nizrahel on OpC UA server on Raspberry Pi 64 SL runtime
CODESYS Forge
talk
(Post)
Hi all! I'm working on an home project using a Raspberry Pi 3 device with Codesys for Raspberry Pi 64 SL runtime. I would like to create the HMI interface with Siemens WinCC Unified (or Advanced) configuring the Raspberry as OPC UA server. I tryed everything, but I didn't find the way to let the OPC UA connection works using UaExpert. I tryed to use anonymous connection, authenticated connection and the ip address instead of the server name in the path connection. There is no way to connect to the OPC UA server and I was asking myself if this feature is really supported for the runtime version used. Another strange thing I noted, is that is not possible to quickly create an OPC UA certificate in the Security Screen, as show in any tutorials. I have correctly created the Symbol Configuration enabling the OPC UA feature. I attach to this topic some printscreen of the actual configuration (sorry for the italian language interface, but I didn't find the way to switch to english). Thank you very much in advance for your support and advices!
Last updated: 2023-12-03
Post by kurtk on dynamic modbus devices
CODESYS Forge
talk
(Post)
I am CODESYS neophyte getting my wheels on. My goal is to re-platform an existing PLC application written in 61131 ST I've got the majority of the code/variables in a compilable form - excluding all the IO and comms nuances I am not sure whether this the right forum An important functionality which I implemented on the other platform was totally dynamic modbus devices... Most configurations I have come across impose static MB configs in which all configured devices MUST be present and functional... I have monkeyed around with MB enough to know that herding a half dozen MB cats into a working config can be tricky. I just do them one at a time and dynamically turn them on/off in whatever combination is convenient with ID, IP, baud, parity etc being runtime tweakable. I am totally curious whether this is possible with codesys, or whether its device configuration corrals one into a static cage which requires re-building the code to support flexible variations. Best regards
Last updated: 2025-08-19
Post by kurtk on runtime dynamic modbus devices
CODESYS Forge
talk
(Post)
I am CODESYS neophyte getting my wheels on. My goal is to re-platform an existing PLC application written in 61131 ST I've got the majority of the code/variables in a compilable form - excluding all the IO and comms nuances I am not sure whether this the right forum An important functionality which I implemented on the other platform was totally dynamic modbus devices... Most configurations I have come across impose static MB configs in which all configured devices MUST be present and functional... I have monkeyed around with MB enough to know that herding a half dozen MB cats into a working config can be tricky. I just do them one at a time and dynamically turn them on/off in whatever combination is convenient with ID, IP, baud, parity etc being runtime tweakable. I am totally curious whether this is possible with codesys, or whether its device configuration corrals one into a static cage which requires re-building the code to support flexible variations. Best regards
Last updated: 2025-08-19
Post by beavel on Feature Request: Text List Formatting
CODESYS Forge
talk
(Post)
Hi everyone, I'm working on a multilingual help system within a CODESYS visualization project and have run into a limitation with the current text list (.tlx) functionality. Right now, text list entries only support plain text, which makes it very difficult to format longer help texts in a readable way. For example, I’d like to: Use bold headers and larger font sizes for section titles Display variable names or keywords in italics Avoid having to split content into dozens of separate entries just to apply different styles This becomes especially unmanageable when supporting multiple languages — duplicating layout logic across languages is not scalable. Would it be possible to implement a Markdown text functionality for text list entries ? For example: #Header ##Sub-header 1.ordered 2.list 3.fun 4.times Alternatively, is there any existing workaround or planned feature that allows for styled text blocks without fragmenting the content? Thank you in advance and have a nice day :)
Last updated: 2025-09-23
Post by mrkm-dic on CODESYS: Combining Master Redundancy with EtherCAT Ring Topology – Is it Supported?
CODESYS Forge
talk
(Post)
Hello, I would like to ask whether it is technically supported (and practically achievable) to combine CODESYS Master Redundancy with EtherCAT ring (loop) redundancy in the same system. System setup CODESYS version: CODESYS 3.5.21.40 CODESYS Control SL for Weidmuller u-OS-4.12.2.0 Controllers (Masters): Weidmuller UC20-M4000 ×2, configured as Active / Standby using CODESYS redundancy EtherCAT Slaves: Weidmuller UR20-FBC-EC ×3, supporting EtherCAT ring / line break detection Topology: EtherCAT ring (loop) Main question Is it officially supported to use: ・CODESYS PLC/Master redundancy (Active/Standby) and ・EtherCAT ring topology (for cable redundancy) at the same time? Expected behavior Our expectation is: ・When the Active PLC fails, the Standby PLC becomes Active ・The Standby PLC then takes over the role of EtherCAT Master ・EtherCAT communication is re-established ・I/O control continues after reinitialization (a short interruption is acceptable; no strict bumpless requirement) We do not expect completely seamless / zero-cycle switchover, but we want to understand: ・Whether this combination is supported by design ・Or whether there are known limitations or restrictions when EtherCAT ring mode is used together with Master redundancy Clarification At this stage, the question is mainly about feasibility and support, not about a specific error message yet. Any official guidance, limitations, or real-world experience would be greatly appreciated. Thank you in advance.
Last updated: 2026-02-05
Post by scoob on ModbusFB - Slow Response Time
CODESYS Forge
talk
(Post)
Hello, I have been trying to use the ModbusFB functions so I can put some code into libraries, but it seems to be very slow for me. I have a Modbus device with 100ms registers. I previously setup 10 channels in the 'traditional' Modbus Slave with channels and mappings - and set a cyclic trigger at 100ms - this worked fine. I then tried the ModbusFB example, and setup reading the same 10 blocks of modbus addresses, copying the example and putting all of the requests into an array and triggering the requests sequentially. I timed how long the requests are taking to get round to each one, and it is around 1s 450ms. How do I speed this up to match the cyclic time? IF NOT(init) THEN init := TRUE; // Set the required IP address: ipAddress[0] := 192; ipAddress[1] := 168; ipAddress[2] := 1; ipAddress[3] := 10; // Pass the required IP address to the clinet FB: client_NetworkSwitch.aIPaddr := ipAddress; client_NetworkSwitch.udiLogOptions := (ModbusFB.LoggingOptions.ClientConnectDisconnect OR ModbusFB.LoggingOptions.ClientReceivedValidReplies); // Try to connect the client client_NetworkSwitch(xConnect:=TRUE); // Configure all the channels to read connecting them to the client: portStatus_Request(rClient := client_NetworkSwitch, uiStartItem := 4096, uiQuantity := 32, pData := ADR(portStatus), udiReplyTimeout := udiReplyTimeout); portSpeed_Request(rClient := client_NetworkSwitch, uiStartItem := 4352, uiQuantity := 32, pData := ADR(portSpeed)); flowControl_Request(rClient := client_NetworkSwitch, uiStartItem := 4608, uiQuantity := 32, pData := ADR(flowControl)); linkUpCounter_Request(rClient := client_NetworkSwitch, uiStartItem := 5888, uiQuantity := 32, pData := ADR(linkUpCounter)); txPacketCounter1_Request(rClient := client_NetworkSwitch, uiStartItem := 8192, uiQuantity := 100, pData := ADR(txPacketCounter1)); txPacketCounter2_Request(rClient := client_NetworkSwitch, uiStartItem := 8292, uiQuantity := 28, pData := ADR(txPacketCounter2)); rxPacketCounter1_Request(rClient := client_NetworkSwitch, uiStartItem := 8448, uiQuantity := 100, pData := ADR(rxPacketCounter1)); rxPacketCounter2_Request(rClient := client_NetworkSwitch, uiStartItem := 8548, uiQuantity := 28, pData := ADR(rxPacketCounter2)); txErrors_Request(rClient := client_NetworkSwitch, uiStartItem := 8704, uiQuantity := 64, pData := ADR(txErrors)); rxErrors_Request(rClient := client_NetworkSwitch, uiStartItem := 8960, uiQuantity := 64, pData := ADR(rxErrors)); // Trigger all client requests initially FOR clientRequestsCnt := 0 TO (SIZEOF(clientRequests)/SIZEOF(clientRequests[0]))-1 DO pClientRequest := clientRequests[clientRequestsCnt]; pClientRequest^.xExecute := TRUE; END_FOR // Prepare sequential trigger / control of client requests. clientRequestsCnt := 0; pClientRequest := clientRequests[clientRequestsCnt]; END_IF // Call the client to do request processing: client_NetworkSwitch(); // Now we trigger client request sequentially ... IF NOT pClientRequest^.xExecute AND NOT pClientRequest^.xDone AND run AND client_NetworkSwitch.xConnected THEN pClientRequest^.xExecute := TRUE; END_IF // .. and check result/error IF pClientRequest^.xExecute AND run AND client_NetworkSwitch.xConnected THEN IF pClientRequest^.xDone THEN // Prepare next trigger of client request (a rising edge of xExecute) pClientRequest^.xExecute := FALSE; IF clientRequestsCnt < SIZEOF(clientRequests)/SIZEOF(clientRequests[0])-1 THEN // next client request clientRequestsCnt := clientRequestsCnt + 1; ELSE clientRequestsIterationCounter := clientRequestsIterationCounter + 1; clientRequestsCnt := 0; END_IF pClientRequest := clientRequests[clientRequestsCnt]; END_IF END_IF I did try a semi-coded way using the IoDrvModbusTCP library, and setting the slave com settings, then 10 commands and 10 requests, then using a TP on xDone as a pause, before triggering another request - this is time the delay is around 120ms - so the device is fine with the speed, just something I am doing wrong in the ModbusFB method I am sure.
Last updated: 2024-04-26
Post by lukebouchard on NVL generating ADwin packets instead of UDP?
CODESYS Forge
talk
(Post)
Using Codesys 3.5 SP11 32bit to program a pair of IFM CR711S controllers. They each have an NVL sender and are set up to receive each others messages. One is transmitting properly but not receiving, the other is receiving the first's messages just fine. When I look at the traffic in wireshark, I can see the one transmitting properly as UDP packets on the subnet and port I had specified. The Second is transmitting on the right subnet and port, but is sending 'ADwin Config' packets. Has anyone run into anything simmilar? From some reading on ADwin from google, nothing is enlightening. Both are set up in the same way, have their own ports and List Identifiers. I have deleted the NVL files and regenerated them, cycled power, and even deleted and remade the NVL's so many times.
Last updated: 2024-08-24
Post by phoward131 on Alarm Table Filtering
CODESYS Forge
talk
(Post)
I am having trouble getting the alarm table filtering to work. I downloaded the alarm filter latch example project and ran it on the local Codesys Control Win and the filters worked fine. I am trying to replicate it in my project and everything seems to be set up the exact same way and every time I turn on the filter, it shows no alarms. I even started a blank project and just copied in elements from the example project so that it is exactly the same and when I attempt to filter, it again shows no alarms. Could there be some project settings I need to adjust to make this work? I have attached my project with elements copied from the example project and filtering is not working.
Last updated: 2024-10-28
Post by dasch on eCockpit - unable to start simulation
CODESYS Forge
talk
(Post)
This is a known bug in e!Cockpit. See Release notes of V 1.11: 1 e!Cockpit Release Version 1.11 (2022-07) ATTENTION: If a library that uses asynchronous tasks (e.g. WagoAppConfigTool, WagoAppCloud or function modules such as Dali-Master) is dragged into the project, the simulation cannot be started. It is already sufficient to add the library to the project (an FB does not even have to be instantiated). I guess you are using one of these libraries/modules in your project. We e.G. often use PWM modules, these are also affected.
Last updated: 2023-09-05
Post by john-martin on Send file from codesys to...... ftp, cloud, etc
CODESYS Forge
talk
(Post)
Hi everybody, I am looking for a solution to send files, for example, to an ftp or a cloud. I can't use oscat library because 64 bit controller are not supported. Therefore, I see that the IIoT library has some functions that might help me to implement this sending process in codesys. Does anyone have any examples of how to do this? I have spent some days with this issue without success. Best regards.
Last updated: 2023-11-02
Post by patliby on Cannot Find "Automatically Generate POUs" Option
CODESYS Forge
talk
(Post)
I would like to enable the feature to automatically generate POUs for Project/Library properties in some of my library/project files. The Codesys help pages indicate it should be on the bottom of the Project Information Summary tab, but mine has no such options (see screenshot). Is there somewhere I have to enable this overall feature or any other prerequisite I am missing? I am using Codesys 3.5.19.20 Reference https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_obj_project_information.html#UUID-9ddc3572-a024-5a49-c0c1-31677991a419_id_c95bfe46c6c18a67c0a8640e01715107_id_0a188ec6fa561b9fc0a8640e0019d8bf
Last updated: 2025-05-08
Post by nz-dave on Custom library, ethernet/ip adaptor
CODESYS Forge
talk
(Post)
Im Putting alot of my custom functions blocks into a library I have a EthernetIP VSD FB that i would like to get Status from the adaptor. EthernetIP_remote_adaptor.estate is one what i want to get. so anyone know how to point that to my function block? when i use the block i just want to have an input "Drive" that would point to the adaptor. like in softmotion when you just put the axis name in the FB to point the FB to a certain axis. Hope that makes sense, cheers
Last updated: 2025-05-21
Post by ph0010421 on General question about library versions
CODESYS Forge
talk
(Post)
Hello I can't find anything to read on the subject so I'll ask here. Up to now, when adding a (for example) Modbus Master, I've selected the version <= the RT version, so if I'm using SP13 Patch 3, I can use a library that doesn't exceed this. I've no idea if this is correct, but it's always worked. Can someone explain the 4.x.x.x libraries that have appeared; are they tied to a RT version? The controller I use is now at SP18Patch60, so should I continue to use 3.5.xxx or change? thanks
Last updated: 2024-05-29
Post by ph0010421 on ModbusTCP_FunctionCode06
CODESYS Forge
talk
(Post)
Hi You can add a channel to the standard Modbus TCP library with FC06. From the device tree, add Ethernet device, ModbusTCP master then finally a ModbusTCP slave (your power meter). You can add read/write channels (for any FC) in here. As you add these devices, the necessary libraries will be inserted for you. Alternatively, I have a ModbusTCP client/server library if your RT doesn't have Modbus (I think they all do these days?)
Last updated: 2026-05-18
Post by julianramirez on ModbusFB write update
CODESYS Forge
talk
(Post)
Hello everyone, I am testing the ModbusFB library tcp server and so far I am able to create holding registers successfully, however, I am trying to identify after each write which registers got updated (i.e. function code, write value). I can even see the var udiNumWriteRequests, which increases with every write. I noticed that there is logging with the LogStatusInfo method. After I call it I am able to read in the console stuff that I want. Nevertheless, this is only available at the logs and is not easy to decode because it consists on several messages, I would like to know if there is a way for me to retrieve this information from the function itself with pointers or if there is any way to copy the logs messages (assuming that I can filter them with the LoggingOptions to only show what I need) inside the runtime code and not in the console. Thanks for your help :)
Last updated: 2024-09-16
Post by mubeta on Strange problem with the ‘MC_SetPosition’ function
CODESYS Forge
talk
(Post)
Hi gseidel, before moving to HW implementation, I had created the same program in simulation mode with virtual drives and, as far as I remember, everything worked fine simulating process and the few useful inputs. So it does not seem to be a SoftMotion library problem, but rather a problem with dynamics or physical axis adjustments. What escapes me, however, is the fact that this function is supposed to perform a position shift virtually, in fact without interfering with the axis itself, thus independent of its adjustments. MC_SetPosition() is not a homing function, in fact it is clearly intended to be executed on the fly with the axis moving. Now I'll see if I can reduce the program, although I don't like it very much. In my life I have learned that problem searches should be done on the part, and not in a more or less similar way.
Last updated: 2025-01-10
Post by levih on DocScripting
CODESYS Forge
talk
(Post)
Hello I'm trying to use the DocScripting collection in Codesys. I've made it work on one PC(1) for the 3.5.16.4 version of the script collection. But when I try the same setup on another PC(2), I get an error message: Error loading Python DLL: D:\SCRIPTING\3.5.16.40\python27.dll (error code 14001) My setup on both PC's is thus: 1. Downloaded and installed Python 2. Copied the folder with the scripting collection to C: (because of admin rights) 3. Placed my .library file in the same folder as the scripting collection Only difference is that Python is v3.12.0 on PC1 and v3.12.1 on PC2. I thought maybe it was something with Python, but then I have tried using the scripting collection from 3.5.16.1, and that seems to work. Just not for scripting collection 3.5.16.4. I also can't seem to find any scripting collections on newer versions of Codesys? (e.g. 3.5.19.10) Thanks in advance!
Last updated: 2024-01-22
Post by manuknecht on XY Chart causes extremely long cycle in Visu Task
CODESYS Forge
talk
(Post)
I am using the visualization element "Cartesian XY Chart" in a visualization template within a library to display recorded position values. I managed to configure the chart as desired and it displays the values like it should. A problem occurs when clicking on the chart to move the cursor, zoom or pan. Upon clicking the visualization element for the first time, the task in which the visualization is run spikes to a cycle time of around 5'000 to 15'000 ms (the configured cycle time is 100 ms). Sometimes this even completely crashes the web-visualization. After this very long cycle, the visu task normalizes again and the chart can be interacted with as usual. Another spike in cycle time occurs once the visualization is switched to a frame that does not contain the chart. I did reduce the data array to only a few values and tried changing the update behaviour of the chart, but it did not change the problems I am facing. Did anyone experience a similar issue or even has a solution for this?
Last updated: 2026-06-16
Post by bbm1995 on Camera RTSP Feed
CODESYS Forge
talk
(Post)
Hi dgrard, I had the same issue for a long time, but on a WAGO webvisu. Now I'm glad that I can share my solution. I don't know if you are trying to use the webvisu or the target visu, but this works on webvisu: Get "go2rtc" and set it up according to the documentation. I'm running the Windows binary. Here's my example of the go2rtc.yaml config file (contains working example streams): api: listen: ":1984" # default ":1984", HTTP API port ("" - disabled) origin: "*" # default "", allow CORS requests (only * supported) static_dir: "www" # default "", folder for static files (custom web interface) tls_listen: ":443" # default "", enable HTTPS server tls_cert: "./SSL/fullchain.pem" tls_key: "./SSL/privatekey.pem" streams: # Streams with multiple links will fall back on the next link. ABUS TVIP48511: - rtsp://<username>:<password>@<hostname>:<port>/ch1/main - rtsp://<username>:<password>@<hostname>:<port>/ch1/sub # Diagnostic connections Kirchhoff Institute for Physics - Germany: http://pendelcam.kip.uni-heidelberg.de/mjpg/video.mjpg Blanton Bottling, Kentucky - USA: http://camera.buffalotrace.com/mjpg/video.mjpg Tokyo - Japan: http://61.211.241.239/nphMotionJpeg?Resolution=320x240&Quality=Standard Tampere Hacklab - Finland: http://tamperehacklab.tunk.org:38001/nphMotionJpeg?Resolution=640x480&Quality=Clarity Soltorget Pajala - Sweden: http://195.196.36.242/mjpg/video.mjpg Kaiskuru Skistadion - Norway: http://77.222.181.11:8080/mjpg/video.mjpg webrtc: listen: ":8555" #ice_servers: # - urls: [ "stun:localhost:3478" ] # username: "" # credential: "" Access the webinterface of go2rtc and get the link of your stream. Use the link as for your browser frame in the visualization. Depending on your device, you need to be able to access the file /etc/lighttpd/lighttpd.conf or /etc/lighttpd/webvisu.conf and change the contents similar to this one, otherwise you'll get CORS and CSP errors in the browser and you won't be able to view the stream on the webvisu: # Webvisu specific settings $SERVER["socket"] =~ port_webvisu_used_any { url.redirect += ( "^/webvisu/?$" => "/webvisu/webvisu.htm" ) $HTTP["url"] =~ "^/webvisu/?" { var.response_header_policy_webvisu = ( # CSP for WebVisu, allowing inline sources. "Content-Security-Policy" => "default-src 'self' 'unsafe-inline'; media-src *; frame-src *", # CORS for WebVisu, allowing any origin to access. "Access-Control-Allow-Origin" => "*", # Tell older browsers that this page can only be displayed if all ancestor # frames are same origin to the page itself. "X-Frame-Options" => "SAMEORIGIN" ) # Response header policy for WebVisu setenv.set-response-header = var.response_header_policy_webvisu setenv.set-response-header += var.response_header_policy_common }
Last updated: 2023-11-14
Post by madskaizer on Task Priority Documentation?
CODESYS Forge
talk
(Post)
Hi All I was watching the Wago PFC300 webinar ( https://www.wago.com/global/lp-thank-you-onlineseminar-pfc-300 ), and the presenters comment about priority 1 being way above the Ethernet task priority, so that a priority 1 PLC program can actually loose SCADA connection, made me try to round up some hard evidence on Codesys Priorities. I find there is very little information on "correct" task priority configuration. There is a lot of different hardware manufacturers, using Codesys Runtime, that has different descriptions in their manuals on how to set up priority. https://doku.amk-motion.com/en/Subsystems/PDK_202975_A-Serie_en/Content/Projekt/AMKAMAC/PDK_202975_A4-A5_Produktbeschreibung/Funktionalitaet/PLC-Programming/PLC%20Tasks.htm?TocPath=PLC-Programming%7C_____7 https://product-help.schneider-electric.com/Machine%20Expert/V1.1/en/SoMProg/index.htm?#t=SoMProg%2FTask_Editor%2FTask_Editor-7.htm&rhsearch=priority&rhhlterm=priority&rhsyns=%20&SUBSTRSRCH=1 https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_f_task_configuration.html So my questions :) 1) If there is only 1 PLC_PRG task, does priority matter? 2) What is the priority of Ethernet / communication, if nothing is entered? 3) What is the priority of Codesys OPC UA server? 4) Some users here on forge mentions that Wago PLC programs should run as priority 11, but where does this recommendation origin from? 5) What are you recommendations for a relatively slow process, like building automation? It uses OPC UA for communication to SCADA, maybe some MODBUS-RTU and MODBUS-TCP, usually around 100 I/O, been running with everything in a single task at priority 1, 50-100ms cycle time. Some controllers have separate MODBUS tasks, but doesn't seem like a big difference. How would you recommend splitting up communication, IO fieldbus and programs into differently prioritized tasks? I know its a complex matter and all about my application, but I really miss there was just some kind of guidance in the documentations and with all new standard Codesys programs having priority 1 as default, makes it seem less important, than it really is.
Last updated: 2025-08-11
Post by mondinmr on COL.IMap2 and HashTableFactory cause frequent Access Violation
CODESYS Forge
talk
(Post)
Good morning, I’ve been using the Collection library for a long time, mostly with Stack, LinkedList, and List. From your examples I was able to manage the different factories, even for custom elements. Now I need a hashtable, but with this object I’m running into a lot of random access violations. If I append something inside FB_Init after constructing the hashtable, it crashes, even though the list was already created. If I only create the hashtable in FB_Init and append afterwards, it usually works. I don’t understand the meaning of the dispose call in this code: pSlave := ADR(slave); uSlave := TO_ULINT(pSlave); iKey := fKey.Create(uSlave); IF hash.CountKeys() = 0 THEN Service.logger.appendLog('Filling hashtable', 'HashManager', AdvLogType.AdvDebugMsg); ok := FALSE; ELSE eError := hash.ContainsKey(iKey, xResult => ok); END_IF IF NOT ok THEN pI := __NEW(UINT); iVal := fKey.Create(TO_ULINT(pI)); Service.logger.appendLog(CONCAT('New slave', TO_STRING(uSlave)), 'HashManager', AdvLogType.AdvDebugMsg); hash.AddKeyValuePair(iKey, iVal); appendNewSlave := pI; ELSE eError := hash.GetElementByKey(iKey, itfValue => iElem); xResult := __QUERYINTERFACE(iKey, itfIInstance); IF xResult THEN itfIInstance.Dispose(); END_IF IF eError <> COL.COLLECTION_ERROR.NO_ERROR THEN Service.logger.appendLog(CONCAT('ERROR ', TO_STRING(eError)), 'HashManager', AdvLogType.AdvCriticalMsg); appendNewSlave := nullptr; RETURN; END_IF __QUERYINTERFACE(iElem, iVal); {warning disable C0033} pI := TO___UXINT(iVal.UlintValue); {warning restore C0033} appendNewSlave := pI; END_IF Without the dispose call, every second cold reset crashes immediately when I try to access iVal, even if eError doesn’t report any error. With the dispose call, the cold reset issue disappears, but I get other problems: a) If I start the runtime using systemctl start codesyscontrol, it crashes at IF hash.CountKeys() = 0 THEN b) If I delete the files in PlcLogic and download again, it works and survives multiple cold resets. But as soon as I run systemctl restart codesyscontrol, everything gets corrupted again and it starts crashing at that point. FUNCTION_BLOCK SlaveMapCounter VAR hash : COL.IMap2; eError : COL.COLLECTION_ERROR; END_VAR In its FB_Init I create it: METHOD FB_Init: BOOL VAR_INPUT bInitRetains: BOOL; // TRUE: retain variables are initialized (reset warm / reset cold) bInCopyCode: BOOL; // TRUE: the instance will be copied to the copy code afterward (online change) END_VAR VAR hF : COL.HashTableFactory; END_VAR hash := hF.Create(256); In another FB I instantiate it statically: FUNCTION_BLOCK ABSTRACT AbstractServoEthercatController EXTENDS AbstractServoController VAR_STAT hashSlaves : SlaveMapCounter; END_VAR VAR field : REFERENCE TO ADVAbstractFieldUnitEthercatCia402; initCnt : REFERENCE TO UINT; END_VAR The append method is the one shown above, and I call it after the runtime has started. The accesses are performed by a single task, and in any case I’m working on an isolated single core. I’ve tried everything, moving the create, the instances, and all the rest several times, but nothing seems to work. I’d like to point out that these FBs are part of our own library, which is used in many applications.
Last updated: 2025-09-11
Post by shafiq-dsc on Beckhoff EK series cannot detect but BK1120 detect
CODESYS Forge
talk
(Post)
Dear Support, I have i950 wants to connect with Beckhoff EtherCAT coupler BK1120. There are 2 GSD files for BK1120. 1. BK1120 without MDP.(EtherCAT ESI Device Description (XML)) 2. BK1120 with MDP. (EtherCAT BKxxx (MDP) configuration files) When connecting the BK1120 with i950, scanned devices detects BK1120 without MDP from ESI No1 above. But the KL1408 & KL2408 not detect because they have ELxxxx IO type. When manually insert BK1120 with MDP, the KL1xx8 is able to add manually also but the error shows and Install Missing Descriptions appears. The questions; 1. Why the error occurs? 2. Can the i950 connect with KLxxxx IO type or not? Regards, Shafiq
Last updated: 2024-10-25
Post by ameba on PersistentVars and Webvisu Element
CODESYS Forge
talk
(Post)
hello everyone I would like to try to better understand how persistent variables work. I created some boolean variables in the PersistentVars section initialized to the value TRUE. I have tied these boolean variables to toggle switches placed inside the HMI interface pages. Once the PLC program is started, the lever selectors, if operated, change their state, at least at a graphical level, but the persistent variables do not undergo any variation. Initially the above variables were declared as simple global variables, in this case the operation with the levers was correct; I then tried to transform them into persistent ones with the aim of using them as "settings saver" Thank you for support Bye
Last updated: 2025-04-03
Post by davidbo on All the things needed for anonymous login to OPC UA
CODESYS Forge
talk
(Post)
I thought I knew what I am doing, but something is missing what? From Device-Communication Settings select from drop down menu "Device" Select entry "Change Runtime Security Policy" Check the "Allow anonymous login" Select "Symbol Configuration" in your application In settings check "Support for OPC UA features" Check some of the values you want in your set Press the build button in the "Symbol Configuration" Press the button "Configure Symbol Rights" Make sure that Anonymous_OPCUAServer has access right to your "default set" From Device-Communication Settings select "Access Rights" in RemoteConnections-OPCUAServer Anonymous_OPCUAServer should be given modify and view rights I suppose. I can connect with UaExpert but I cannot see my Application or browse my values. What is missing?
Last updated: 2025-09-10
Post by alexgooi on Licensing info not available.
CODESYS Forge
talk
(Post)
Thank you for your quick response, I have updated to the 4.17.0 (Virtual control and the license server). Now I am able to see the softcontainer from the Codesys IDE. But when I want to activate the license I get the following message: Licensing info not available. The device does not support this service (See picture). I then tried to active it via the WBM service like you suggested. But when I try this is get an error (see picture for error). I also tried to put RTS- in front of the serial number, but when I try this I get an error that the serial number is not correct. I think I'm getting closer, but I'm not there yet.
Last updated: 2025-10-01