  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    In V3.5.19.0 it seems that hide namespaces is forced, so our old 3.5.16.40 projects that show the namespace, are now loaded without namespace in 3.5.19.0. This sucks pretty hard, as it has to be turned off in EACH INDIVIDUAL program/method/act etc. Turning on namespaces in options does not help, it actually just makes it worse by some weird display error that shows some namespaces and some not. Another thing that really bothers me, why are all standard logic blocks like AND, OR etc, shifted 1 place...

  • MadsKaizer MadsKaizer posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    All the log files there are only with data from after the latest reboot. There is a logrotate.status file that contains this: logrotate state -- version 2 "/var/log/sudo.log" 2021-12-21-14:0:0 "/var/log/runtime.log" 2021-12-21-14:0:0 "/home/log/wagolog.log" 2021-12-21-14:0:0 "/var/log/openvpn.log" 2021-12-21-14:0:0 "/var/log/syslog.log" 2022-1-2-18:1:0 "/var/log/lighttpd/error.log" 2021-12-21-14:0:0 "/var/log/kernel.log" 2021-12-21-14:19:0 "/var/log/lighttpd/access.log" 2021-12-21-14:0:0 "/var/log/earlymsg"...

  • MadsKaizer MadsKaizer posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    I have a Wago PFC200 SL Runtime, that freezes up on me every 2-3 weeks. All it needs is a reboot and it runs again. But after the reboot, the log is "empty", I can only see the boot messages, not any messages from what made it halt. Is there a way to get a post-mortem log on freezing PLC? It looses network connection, so there is no OPC-UA connection, no webinterface, no shell access and cant even ping it.

  • MadsKaizer MadsKaizer posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Thank you for sharing these improvement speeds, its always nice to see some real numbers behind a patch note "Improved code execution" :)

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    It is not possible to do through the IDE yet. Codesys support told me that it will be fixed in a later release. But for now you can not make a network without disabling ALL security first, connect and then afterwards set up security with user/password. Which makes it practically impossible to implement into a existing opcua network.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I have a 3.5.17 installation with all options/plugins/packages installed, nothing excluded from the installation guide. I had to uninstall and reinstall it due to unselecting a package I needed and found no way to fix it through repair. The screenshot is from a CFC project, but once the project is made I can add all the different kinds of programming methods I want.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I have been using the guide on how to set this up, from the help files: https://help.codesys.com/webapp/_cds_encrypt_communication_data_sources_opc_ua_client;product=codesys;version=3.5.17.0 In step 4, I can only choose server and not client as described in the guide. Okay, I can assume its maybe just a type error, so lets continue. I have 10 PLCs running a OPC-UA server, currently connected to my SCADA platform, so the encrypted OPC-UA servers can talk to a client. I tried to add one of them, but...

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    In the new version of IDE (3.5.17), the CFC editor changed the way it shows a variable, its shorted down to last right part of the struct and has a leading =-like character. I can not find any options to disable this view. It bugs me quite a lot as it has resulted in my blocks jumping around :(

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The hint lies in "(Largest contiguous memory gap 488). Editing persistant variable lists may produce fragmented memory." You have changed too many blocks, data structures or something else that fragmented the PVL. Go to "Build" menu and run a "Clean" to de-fragment your project, this will however require a new download in PLC.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Error message fra Prosys POC UA browser on anonymous and username

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Error messages from UaExpert on connection with anonymous or a chosen username with access rights to OPCUAserver

  • MadsKaizer MadsKaizer modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    There can be found a wide topics covering how to ENABLE forced certificates on OPC-UA, but there is nowhere to be found on how to disable it again. Once it has been enabled, I can not go back to plain text communication or just authentication with username and password. I know the following setting for the cfg file: [CmpOPCUAServer] SECURITY.CommunicationMode=SIGNED_AND_ENCRYPTED from some V3.5.16.10 documentation found online, I know there is the following setttings in the OPCUA server, but what...

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    There can be found a wide topics covering how to ENABLE forced certificates on OPC-UA, but there is nowhere to be found on how to disable it again. Once it has been enabled, I can not go back to plain text communication or just authentication with username and password. I know the following setting for the cfg file: [CmpOPCUAServer] SECURITY.CommunicationMode=SIGNED_AND_ENCRYPTED from some V3.5.16.10 documentation found online, I know there is the following setttings in the OPCUA server, but what...

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I got a Codesys 3.5.16.20 runtime on a PLC communicating with a SCADA platform. We keep loosing connection to the PLC and the PLC log inside Codesys IDE has a lot of the following lines warning: CmpOPCUAStack, 05-02-2021 10:01:58 - OpcUa_TcpListener_ReadEventHandler: Process Request returned an error (0x800B0000)! error: CmpOPCUAStack, 05-02-2021 10:01:58 - OpcUa_SecureListener_ProcessRequest: Closing channel due error 0x800B0000! error: CmpOPCUAStack, 05-02-2021 10:01:58 - OpcUa_Endpoint_BeginProcessRequest:...

  • MadsKaizer MadsKaizer modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    Scroll down to programming: https://disorder.dk/wonderware/2020/10/07/modbus-tcp-between-codesys-controllers/ You could use a struct "Union", in this example I always read out the real value in the code where I use the value, but I can switch around on the word0 and word1 when writing into the union from the MODBUS register.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Scroll down to programming: https://disorder.dk/wonderware/2020/10/07/modbus-tcp-between-codesys-controllers/ You could use a struct "Union", in this example I always read out the real value, but I can switch around on the word0 and word1 when reading from the MODBUS register.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I still need an answer on to what needs to be changed to remove certificate requirements on OPC-UA communication, as per above reply from myself, I have also tried with the other possible OPC-UA settings as "ONLY_PLAINTEXT" or "ALL" with same result. It seems to me there there is some settings, somewhere, besides CODESYSControl_User.cfg that is affected by forcing on certificates that is NOT SET BACK, if that setting is set to something else. Especially "15:03:45.482 | General | | Error: UaSessionPrivate::activateSession...

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi All I have had my controllers running with certificate and encryption, worked fine. Now I wanted to remove it again, as certificate renewel will be a huge work load with the number of PLC's we are looking into. We are looking into finding a setup with automatic certificate renewal from a security server before working with that again. I have removed the following again: **CODESYSControl_User.cfg [CmpOPCUAServer] SECURITY.CommunicationMode=SIGNED_AND_ENCRYPTED** I have removed the certificates...

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Thank you, that works now and is forced to only use Basic256Sha256. Additional help to others: I had some troubles with a change of hostname that does not kick all the way through to /etc/hosts and thus when pulling a new certificate, it would get the old hostname. I commented out the old hostnames with # and rebooted the controller. OPCUAServer would then not start up as plain text is not allowed and it was shutdown according to the codesys IDE log, so it required to generate new certificates and...

  • MadsKaizer MadsKaizer posted a comment on discussion Deutsch πŸ‡©πŸ‡ͺ

    You need to use a place holder for Standard/Util or just "SysLog" to 3.5.14.00, Wago library is only compiled on 3.5.14.00 version of runtime.

  • MadsKaizer MadsKaizer posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Perhaps execute access rights to the file system? Located under controllers "user and groups" and "access rights"

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See pictures, the connecte UaBrowser client is under quarantined certificates, but could still login and change values with just username/password.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi I followed guide: https://help.codesys.com/api-content/2/codesys/3.5.14.0/en/_cds_runtime_opc_ua_server/ I set up a user called "opcua", gave it access rights to modify/write on the opcuaserver object under access rights. Created certificate. Now I can try to connect from f.ex. UaExpert with sign&encrypt, get the error, move quarentined certificate to trusted and all is fine, I can log in and change data. But I can also choose to login without any security options and only use username/password,...

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I will have to check later, I got a PFC200 with a modbus-rtu card, but I am not at the office right now.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Usually Wago identifies these speciel modules as each their own. So if you have 2 MODBUS-RTU cards and 2 DALI cards. These would just identify as port 1 and 2 on RTU function blocks and also port 1 and 2 on DALI cards, its limited to the specific type of card and first card is always 1.

  • MadsKaizer MadsKaizer posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Could you show your "Symbol configuration" in Codesys? Did you enable the OPC-UA features and also selected the variables with correct permissions?

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You could use the WORD_TO_BIT, BIT_TO_WORD or just call the BITs directly on the word variable as wVariable1.0 where ".0" is the first BIT of the WORD I wrote an example of doing MODBUS-TCP communication in Codesys: http://disorder.dk/wonderware/2020/10/07/modbus-tcp-between-codesys-controllers/

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I wrote a extensive guide on how to set up MODBUS TCP communication between codesys controllers: http://disorder.dk/wonderware/2020/10/07/modbus-tcp-between-codesys-controllers/

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering

    Did anyone yet try to set up a codesys opc ua client? I have trouble locating any examples, just the information on this page: https://www.codesys.com/products/codesys-runtime/opc-ua.html and from the help https://help.codesys.com/webapp/idx-CmpOPCUAClient%20Implementation-lib;product=CmpOPCUAClient%20Implementation;version=3.5.16.0 So far it seems to only be released as functions and not a feature/function blocks.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering

    Hi All What is the best way to upgrade a project from one runtime version to another? I have a project for a Wago PFC200 PLC made in 3.5.14.30 and I have tried to simply add a new controller with 3.5.16.10 runtime to the project, add all the busses and such first and then drag'n'drop the programs, lists and structs to the new one. Delete the old PLC and rename the new. Upon building the program, 0 errors/warnings. It seems to work, but is it also the "official" way of upgrading?

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering

    A little more explanation about the IEC standard here http://81346.com/english/about-81346/about-81346-2-2019-edition/

  • MadsKaizer MadsKaizer modified a comment on discussion Engineering

    There isn't really an idea in naming your variables to suit up with the OPC-UA driver, as it uses the runtime name as a large part of the total string. I replaced all of our tagname conventions with a single * to short it down, but we use CCS code for tagnames as its a much more wholesome naming strategy than just using TT, PT, etc. It is the IEC 81346-2:2019 standard and you can check out the latest CCS(2014) standard as its called CCI(2020) now here, its in Danish, but can give you an idea in the...

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering

    There isn't really an idea in naming your variables to suit up with the OPC-UA driver, as it uses the runtime name as a large part of the total string. I replaced all of our tagname conventions with a single * to short it down, but we use CCS code for tagnames as its a much more wholesome naming strategy than just using TT, PT, etc. It is the IEC 81346-2:2019 standard and you can check out the latest CCS(2014) standard as its called CCI(2020) now here, its in Danish, but can give you an idea in the...

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering

    I should have googled that before asking :) I was just thrown off by the possibility to add a Modbus RTU and not a TCP, but that is explained by the Ethernet interface host being a difference between them. Thank you.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering

    Is there anywhere to see a list of the latest versions? It is not listed in the full features description of 3.5.16.0: https://www.codesys.com/fileadmin/data/Images/Download/features-and-improvements-V35SP16-en.pdf

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering

    Hi I can not add a MODBUS TCP Master to my 3.5.16.10 project, browsing the device repository I can see the version of the driver is listed as 3.5.16.0, does this mean the MODBUS TCP Master device can only be added in a 3.5.16.0 project? From the codesys store description, the MODBUS TCP Master is listed in the features, but it does not seem present in a clean installation of the IDE.

  • MadsKaizer MadsKaizer posted a comment on discussion Engineering

    Hi all I have the following IDEs installed - 3.5.14.10 - 3.5.16.0 - 3.5.16.10 But the standard libraries under Application->Common->Standard is listed as 3.5.14.0 and 3.5.15.0, is this just because there is no new version of the standard libraries for 3.5.16.0/10? How do I check where the latest libraries are? From visiting this help page: https://faq.codesys.com/display/CDSFAQ/Downloading+missing+libraries and I do not have the "download missing libraries" in my IDE and the url given for the libraries...

  • MadsKaizer MadsKaizer posted a comment on discussion Runtime

    Thanks for the pointers on how to attack this the easiest way, I can confirm that it was indeed just to install the RTE from the package downloaded to the CX controller, cx5000 driver installed automatically and configuration was easy. I wrote a guide for myself to remember, but also for help to others on how the process is: http://disorder.dk/wonderware/2020/08/11/codesys-3-5-16-10-runtime-on-a-beckhoff-cx-5130/

  • MadsKaizer MadsKaizer modified a comment on discussion Runtime

    Hi All I have a Beckhoff CX5130 which I want to run Codesys 3.5 runtime on. I got a bunch of DI/DO/AI/AO modules as well. I know from WAGO PLC that I need to use the WAGO configuration tool on the I/O modules before loading the codesys runtime intot he WAGO PLC, but what is the sequence of work needed for a Beckhoff PLC? So do I need to configure my modules with something like TwinCat system manager? ( https://infosys.beckhoff.com/english.php?content=../content/1033/tc3_io_intro/1109041931.html&id=7330306022718482839...

  • MadsKaizer MadsKaizer posted a comment on discussion Runtime

    Hi All I have a Beckhoff CX5130 which I want to run Codesys 3.5 runtime on. I got a bunch of DI/DO/AI/AO modules as well. I know from WAGO PLC that I need to use the WAGO configuration tool on the I/O modules before loading the codesys runtime intot he WAGO PLC, but what is the sequence of work needed for a Beckhoff PLC? So do I need to configure my modules with something like TwinCat system manager? before loading a codesys runtime on it? Looking forward to hear peoples experience with hardware...