Post by talhaali on Alarm status in logic CODESYS Forge talk (Post)
Hi, I am trying to access active alarms in code(As alarm count variable updates only when we go to to alarm table frame in visualization). I wrote following code but it is not working: VAR iCountActiveAlarms : INT; parritfActiveAlarms : POINTER TO ARRAY[0..0] OF IAlarm; itfAlarmManagerClientAll : IAlarmManagerClient; END_VAR AlarmManager.g_AlarmHandler.GetActiveAlarms( itfAlarmManagerClient :=itfAlarmManagerClientAll, iCountActiveAlarms => iCountActiveAlarms, parritfActiveAlarms => parritfActiveAlarms); The Value is always 0. Please help.
Last updated: 2024-06-06

Post by garmusd on Raspberry Pi 5 GPIO not working. CODESYS Forge talk (Post)
Hi, Codesyscontrol 4.13.0.0 Raspberry Pi5 64bit with latest updates. Cant get working GPIO - no output and no input. SPI/I2C not tested. GPIOs B+/Pi2, Input/Output is set in the parameters, assigned variables int the Mapping. Absolutely no reaction. Do I need to configure anything else to make it work? Thanks!
Last updated: 2024-09-26

Post by timvh on Converting each character to a string into ASCII CODESYS Forge talk (Post)
Nice puzzle for a Saturday afternoon :-). Here my suggestion: VAR sInput : STRING := 'R123'; byChar : BYTE; sOutput : STRING; i: INT; END_VAR sOutput := ''; IF LEN(sInput) = 0 THEN RETURN; END_IF FOR i := 0 TO LEN(sInput) - 1 DO byChar := sInput[i]; sOutput := Concat(sOutput, TO_STRING(byChar)); END_FOR
Last updated: 2024-11-09

Post by davidmic on Struct Literal CODESYS Forge talk (Post)
Hi all I want to pass a struct into a function without declaring the struct in a VAR/END_VAR. Is this possible? I think this would be called a struct literal It would look something like this someFB.write(structArgument := MyStruct#(a := 1, b := 1.2), otherArgument := TRUE); With this struct declaration TYPE MyStruct : STRUCT a : INT; b : REAL; END_STRUCT END_TYPE
Last updated: 2025-03-28

Post by benemenn on Type mappings in Datasource CODESYS Forge talk (Post)
Hi! I am trying to achieve the same issue. Has there been a solution? I can create the mapping, and map the local variable, but somehow the object does not update. Furthermore, i have an issue where codesys doesn't let me set ReadWrite accesses to the variables in the "Type Mapping" place. The access will simply not be set. Has anyone ran int that issue?
Last updated: 2025-04-02

Post by timvh on Management of a PLC network from a remote station CODESYS Forge talk (Post)
Maybe the CODESYS HMI is a good solution. https://store.codesys.com/en/codesys-hmi-sl-bundle.html Run this on the remote main control station. In the HMI application you can add the data source manager and to this manager you can add Data sources. A data source has a reference to the PLC you want to connect to and can get access to the variables of the PLC application. You can then use these variables in the visualization of the HMI application.
Last updated: 2023-12-04

Post by lsislsis on Alarms Placeholder CODESYS Forge talk (Post)
Hello. When i put placeholders at "/etc/codesyscontrol/CODESYSControl.cfg" : [SysFile] FilePath.1=/etc/codesyscontrol/, 3S.dat IecFilePath.1=/proc/, cpuinfo IecFilePath.2=/proc/, iomem PlaceholderFilePath.1=/sys/devices/w1_bus_master1, $OneWire$ PlcLogicPrefix=1 PlaceholderFilePath.2=/data/persistence, $ac_persistence$ PlaceholderFilePath.2.Volatile=1 PlaceholderFilePath.2.View=1 PlaceholderFilePath.3=/data/alarms, $alarms$ PlaceholderFilePath.3.Volatile=1 PlaceholderFilePath.3.View=1 Where "Data" are my USB Flash. I take these attachment errors at run time. What i am doing wrong.
Last updated: 2024-10-15

Post by respl on IFM EXOR Network variable Error CODESYS Forge talk (Post)
We are connected IFM CR711S to Exor EX710. We are exchanging data using network variables. Both devices are configured on same project so no need to use file source. When tested application it works fine. But after 3 months same application not working. We are able to send data from CR711 to EX710 but data from Ex710 to CR711s works only for one scan when we cold reset CR 711S. Can somebody help to find out error.
Last updated: 2025-03-17

Post by timvh on Active alarm access in ST CODESYS Forge talk (Post)
See https://forge.codesys.com/forge/talk/Engineering/thread/280fdf4806/#9fe5 And https://forge.codesys.com/prj/codesys-example/alarm-manager/home/Home/ The application should contain: - an FB which implements AlarmManager.IAlarmFilterCriteria (see example - FB_AlarmFilterCriteria) - an FB which implements AlarmManager.IAlarmManagerClient (see example - FB_AlarmManagerClient) Then register the client and get the information through this client. VAR xInit : BOOL := TRUE; udiResult : UDINT; fbAlarmFilterCriteriaAll : FB_AlarmFilterCriteria; fbAlarmManagerClientAll : FB_AlarmManagerClient; itfAlarmManagerClientAll : IAlarmManagerClient := fbAlarmManagerClientAll; xAlarm1 : BOOL; xAlarm2 : BOOL; xWarning : BOOL; iNrOfAlarmsInAlarmList : INT; iNrOfActiveAlarmsInAlarmList : INT; paitfAlarm: POINTER TO ARRAY [0..0] OF AlarmManager.IAlarm; iAlarmIndex : INT; eAlarmState: AlarmManager.AlarmState; END_VAR IF xInit THEN xInit := FALSE; fbAlarmManagerClientAll.m_itfAlarmFilterCriteria := fbAlarmFilterCriteriaAll; // register alarm client to get updated about alarm status / changes udiResult := AlarmManager.g_AlarmHandler.RegisterClient(itfAlarmManagerClientAll, 0, 0); END_IF // Polling the number of alarms udiResult := AlarmManager.g_AlarmHandler.GetActiveAlarms(itfAlarmManagerClientAll, parritfActiveAlarms => paitfAlarm, iCountActiveAlarms => iNrOfAlarmsInAlarmList); iAlarmIndex := 0; iNrOfActiveAlarmsInAlarmList := 0; WHILE iAlarmIndex < iNrOfAlarmsInAlarmList DO eAlarmState := paitfAlarm^[iAlarmIndex].GetState(); IF eAlarmState = AlarmManager.AlarmState.Active OR eAlarmState = AlarmManager.AlarmState.ActiveAcknowledged THEN iNrOfActiveAlarmsInAlarmList := iNrOfActiveAlarmsInAlarmList + 1; END_IF iAlarmIndex := iAlarmIndex + 1; END_WHILE
Last updated: 2025-04-23

Post by pjoret on IFM CR711S Can Low Level Library Use CODESYS Forge talk (Post)
Hello, I'm using CR711S from IFM and I would like to use the CAA Can Low Level in de Safety part. I already use it on the Standard part and it works properly. I would like to know if there is some restriction on using it on the safepart of the PLC (I tried but my PCL put himself in Stop...) ? And if you have some example or even a forum with some types on IFM and CoDeSys, I would Take It. Have a nice Day.
Last updated: 2024-04-03

Post by engrahman on The current baud rate could not be determined in CR0020 IFM with maintenance tool CODESYS Forge talk (Post)
Hello everyone, im working with IFM CR0020 controller via RS232 protocol where im trying to connect it to my PC but, every time when im using the maintenance tool to identify the device i get the error "The baud rate could not be determined" i have tried to change the cable of RS232 with different types but the error presist, any idea how to fix it
Last updated: 2024-05-21

Post by mase on Python script: Launch Codesys, Execute Script, Exit Codesys CODESYS Forge talk (Post)
Hi, sorry I can´t help you with your issue, but I hope you can give me a hint on getting GUID for other objects than POUs. Your code states "Guid("6f9dac99-8de1-4efc-8465-68ac443b7d08")". We can I find the GUID / ObjectIds`? I wasn´t able to get details about the GUID of DataTypes (STRUCT/ENUM,..)m, Functions (FUN), GLOBALS and TYPES. I want to create markdown of all available project elements. Thanks for your help
Last updated: 2024-08-06

Post by lepewe4ka on Sysmac Studio to Codesys CODESYS Forge talk (Post)
Could you send me an example? I would like to generate a data structure using XML files.
Last updated: 2023-09-20

Post by lepewe4ka on Sysmac Studio to Codesys CODESYS Forge talk (Post)
Could you send me an example? I would like to generate a data structure using XML files.
Last updated: 2023-09-20

Post by trycyclepower on How to transfer data from DINT to Union(16 Bools) which I need to use in Few FBs CODESYS Forge talk (Post)
Thanks a lot, it worked.
Last updated: 2023-12-14

Post by ph0010421 on How to transfer data from DINT to Union(16 Bools) which I need to use in Few FBs CODESYS Forge talk (Post)
In the Struct, change the 'BOOL' to 'BIT'
Last updated: 2023-12-14

Post by eschwellinger on Data Transferring between 2 PLCs in a same PC CODESYS Forge talk (Post)
.. this will not work on the same pc
Last updated: 2024-02-06

Post by hasangenc on DI4 USB - Transfer Data CODESYS Forge talk (Post)
Hi! Did you find any solution to your problem. I'm having the same right now. Best Regards.
Last updated: 2024-02-19

Post by hasangenc on DI4 USB - Transfer Data CODESYS Forge talk (Post)
Well, Hi again. I solve the problem, if anyone having the same problem, I might help. You can reach me through this platform.
Last updated: 2024-02-22

Post by egau on Git - User identification data is lost when codesys is closed CODESYS Forge talk (Post)
It bothers me for sure.
Last updated: 2024-04-04

Post by nano on Persistent variable storage CODESYS Forge talk (Post)
use the persistence manager. with the persistence-manager, you're aböe to define how, when and where you store your data
Last updated: 2024-06-16

Post by mos89p on Data source and safety PLC CODESYS Forge talk (Post)
it works only for me when i specify an IP adress in communication tab
Last updated: 2024-06-17

Post by vladimirsmall on Send data to USB CODESYS Forge talk (Post)
Hello/ Need send some file ( for example Array of string) to USB. Which library need used for this. Thank you
Last updated: 2024-07-20

Post by damian177 on Problem with downloading OPC UA tags by Data Source Manager CODESYS Forge talk (Post)
After 3 hours is some progress - please find in attachment - progress1.jpg
Last updated: 2024-09-04

Post by lsislsis on RPI Serial port connects with no errors but not data being transmitted or received CODESYS Forge talk (Post)
Is there any solution because we have the same problem with other hardware?
Last updated: 2024-09-30