Post by jst69 on Python script: Launch Codesys, Execute Script, Exit Codesys
CODESYS Forge
talk
(Post)
Dear all: Question about scripting: I am creating a .NET program that is supposed to Open codesys, open template project, export a bunch of pou, then exit codesys. Launch works, Open project works, Export works, But how do i tell codesys to close itself? I can tell windows to terminate codesys, but i would prefer to do it properly. from __future__ import print_function import sys import System proj = projects.primary # We're interested in POU nodes: POUGuid = Guid("6f9dac99-8de1-4efc-8465-68ac443b7d08") # We collect all POU nodes in that list. pous = [] # From the parent node on, we recursively add POU nodes: def CollectPous(node): if node.type == POUGuid: pous.append(node) else: for child in node.get_children(): CollectPous(child) # Now we collect all the leaf nodes. for node in proj.get_children(): CollectPous(node) # We print everything just to know what's going on. for i in pous: print("found: ", i.type, i.guid, i.get_name()) # And now we export the files. for candidate in pous: # We create a list of objects to export: # The object itsself objects = [candidate] # And sub-objects (POUs can have actions, properties, ...) objects.extend(candidate.get_children()) # And the parent folders. parent = candidate.parent while ((not parent.is_root) and parent.is_folder): objects.append(parent) parent = parent.parent # Create an unique file name: if len(sys.argv) == 1: filename = "parent\\%s.export" % (candidate.get_name()) else: filename = "%s\\%s.export" % (sys.argv[1],candidate.get_name()) # print some user information print("exporting ", len(objects), " objects to: ", filename) # and actually export the project. proj.export_xml(objects, filename) proj.close() print ("script finished.") System.exit(0) // Dont work .NET: public static void Export(string path,string proj) { if (checkSettings()) { var p = new System.Diagnostics.Process(); p.StartInfo.FileName = Properties.Settings.Default.CSVersion +"\\CODESYS\\Common\\CODESYS.exe"; p.StartInfo.Arguments = " --Profile=" + qoute(Properties.Settings.Default.CSProfile) + " --culture=en" + " --project=" + qoute(path + "\\" + proj) + " --runscript=" + Properties.Settings.Default.LastOpenProjectPath + "\\INPUT_DATA\\SCRIPT\\Export.py" + " --scriptargs:" + qoute(path) ; p.StartInfo.RedirectStandardOutput = true; p.StartInfo.UseShellExecute = false; p.StartInfo.CreateNoWindow = false; p.Start(); p.StandardOutput.ReadToEnd(); p.CloseMainWindow(); p.Close(); } }
Last updated: 2024-01-16
Post by r-niedermayer on C0564 Warning Message
CODESYS Forge
talk
(Post)
Please see or Online Help on how to initialize variable before using them: https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_pragma_attribute_global_init_slot.html Regarding the Attribute global_init_slot: You can use this pragma to influence the order in which signatures are processed during global initialization. It can only be applied to signatures. By default, the initialization sequence for variables from global variable lists is undefined! However, if, for example, variables from one list depend on variables from another list, it is necessary to initialize one before the other. (Aee OLH and Syntax) The placeholder <slot> must be replaced by an integer value that defines the position in the initialization sequence.</slot> The default value is 50000. A lower value causes an earlier initialization! If several signatures have the same value for the 'global_init_slot' attribute, the order of their initialization remains undefined! Cautious application should therefore be considered! Example: The project contains f.e. two global variable lists GVL_1 and GVL_2. The global variable "A" is part of the global variable list GVL_1: {attribute 'global_init_slot' := '300'} VAR_GLOBAL A : INT:=1000; END_VAR The initialization values of the variables "B" and "C" of GVL_2 are dependent on the variable "A". {attribute 'global_init_slot' := '350'} VAR_GLOBAL B : INT:=A+1; C : INT:=A-1; END_VAR So if you set the 'global_init_slot' attribute of the global variable list GVL_1 to 300, i.e. to the lowest initialization value in the example, then it is ensured that the expression "A+1" is well-defined at the time of initialization of "B".
Last updated: 2024-01-30
Post by westcountryewe on ac_persistence not working when creating a Boot Application but works with a Direct Download to the PLC
CODESYS Forge
talk
(Post)
I am using V3.5 SP18 Patch 5. I have noticed that when I Create a Boot Application from CODESYS, and upload this to my PLC via a USB stick the AC_Persistence does not work and none of my values that are in my PersistenceChannel are retained. However, if I connect direct to my PLC and I perform a direct download of my CODESYS program, my values that are in my PersistenceChannel are retained and work as they should. This makes me wonder if there are files that are missing when a Boot Application is created. I have tried taking a backup of my configuration files after performing a direct download, which gives me the plclog.zip folder, and appears to have the ac_persistence folder present within the file structure, however when I replace the plclogic.zip with the same folder that was created when I created a Boot Application, it still does not work but I wonder whether this is because the ac_persistence folder isn't stored in the correct location for reading. The .app and .crc files are embedded within the plclogic.zip folder, which obviously when uploading need to be standalone files in the root directory of the USB, so the intention there is clearly to extract the .app and .crc files and put them into the correct location within the USB. I wonder if it could be the same for the ac_persistence folder? I have tried moving it to different locations but none have worked. Has anybody else discovered a fix for this? I know the short-term solution is to do a direct download to the PLC but there are some logistical reasons why this isn't neccesarily the best solution for us.
Last updated: 2024-02-27
Post by ellcap on Symbol Configuration, I'm doing it wrong
CODESYS Forge
talk
(Post)
if you're here because you are making the same mistake as me, I just resolved it. I mistakenly thought I didn't need to write the word attribute in the column labeled attribute. changed this 'symbol' := 'read' to this attribute 'symbol' := 'read' The last two in this clip are still wrong: I recongize this is probably a big "duh". That's ok. I like to fail out loud in hopes it helps someone else from looking silly.
Last updated: 2023-08-31
Post by martinlithlith on Relay board / relays for raspberry pi 3 b+
CODESYS Forge
talk
(Post)
hi! im planning a project on a raspberry with Codesys. For this I'll need a number of relays to control heating and fans, all a max of 24v and about 2a. How would i know if the board / relays i buy will be working with Codesys? Does every hat work or does it need a library/driver? is there a list of drivers/libraries created? as this is a hobby project all tips on a relay board or single boards that works with codesys and not to expensive are very welcome.
Last updated: 2023-09-03
Post by dasch on eCockpit - unable to start simulation
CODESYS Forge
talk
(Post)
This is a known bug in e!Cockpit. See Release notes of V 1.11: 1 e!Cockpit Release Version 1.11 (2022-07) ATTENTION: If a library that uses asynchronous tasks (e.g. WagoAppConfigTool, WagoAppCloud or function modules such as Dali-Master) is dragged into the project, the simulation cannot be started. It is already sufficient to add the library to the project (an FB does not even have to be instantiated). I guess you are using one of these libraries/modules in your project. We e.G. often use PWM modules, these are also affected.
Last updated: 2023-09-05
Post by john-ronald on Communication error (#0), logout performed,please check if plc is connected
CODESYS Forge
talk
(Post)
Hi, I have the same problem. However I am using ethernet connection not USB. I can ping the PLC and also connect to it via Wago ethernet settings, but I cannot upload using the Codesys 2.3. My PLC is Wago 750-862. The detailed error is - " connect: Connection refused Write attempt from invalid socket. " Any help would be appreciated.
Last updated: 2023-09-11
Post by ernesto881124 on ernesto881124
CODESYS Forge
talk
(Post)
Hello good morning everyone I would like to ask a question, is it possible to directly connect a device that only contains modbus RTU communication through an R-45 connector, directly to the PC? Or would you need an intermediate device to achieve communication? It would be of great help to me because I cannot achieve communication between the Codesys simulator plc and a Fuji Frenic mini VFD, please help me if anyone has had the same experience. Thank you so much
Last updated: 2023-09-13
Post by manuknecht on Detect "Cancel" Press in FileOpenSave Dialog
CODESYS Forge
talk
(Post)
When using the FileOpenSave dialog and using the Visu_FbFileListProvider FB as an In/Output I could not manage to detect the difference of pressing the "Load" button on the dialog vs. pressing the "Cancel" button. In both cases, the selected file is updated if the dialog is closed when checking using the Visu_FbFileListProvider.GetSelectedFileName() command. How can I prevent reading or writing of a file when the "Cancel" button was pressed?
Last updated: 2023-09-19
Post by timvh on When Keyboard Key is in Hold, then Webvisu is extreme slow and latent
CODESYS Forge
talk
(Post)
I'm not really sure what you are trying to do, but maybe you are referring to using the CmpCharDevice library? When you "open" the connection to a device, you can pass flags. What helped me is to set the non-blocking flag. I'm not sure if this is what you are referring to, but maybe it helps: dFlags: DINT := CmpCharDevice.ACCESS_MODE.O_RDONLY + DINT#4000; // see details for flags: http://linux.die.net/man/2/open, + DINT#4000 is for non-blocking hDevice := CmpCharDevice.CDOpen(szFilename, dFlags, Result);
Last updated: 2023-09-20
Post by tehthoams on Library Search not working
CODESYS Forge
talk
(Post)
Hello All! Having a strange issue. When adding a library, I'm unable to search. Each time a window pops up 'creating the search index' and then has 0 results. I have the same behavior when using the library repository and pressing the 'Find' button. I wonder if there is a way to reset or fix this issue? It is making it very difficult to search and find proper libraries to add to my project. Much appreciated.
Last updated: 2023-10-17
Post by eschwellinger on Persistence Manager Backup
CODESYS Forge
talk
(Post)
you need at them moment a download once (for the configuration files generated including addresses) then stop the plc - exchange the persistence file ( without the config file) This will be improved to 3.5.18.6 and 3.5.20.0. (possible then to generate offline bootproject including full persistenmanager files) - this is if you have not 100% the same bootapplication on the devices. In case you copy the whole Application (PLCLogic) directory it should work out of the box - but only with 100% same bootprojects as mentioned above. By the CODESYS Automation Server would help solve this too.
Last updated: 2023-10-19
Post by ekristoffe on Beispieldateien finden / Inhalt der Packages
CODESYS Forge
talk
(Post)
Hello @eschwellinger, Why not using one of those 2 folders: C:\ProgramData\CODESYS C:\Users\Public\Documents\CODESYS The main reason is depending on the company and the user right, the end user may not have the access to use those folders. Also having a non version dependent folder may help if the end user uninstall a previous version and forgot all its sample project where in this previous version installation. Thanks.
Last updated: 2023-11-24
Post by macros8 on Translation - How to get text as reference in Frames translated?
CODESYS Forge
talk
(Post)
Hi all, I need a help. I want to create Frame where some parameters are done via reference input to this frame. What I have realized that if I use for Label/Caption etc. string variable (%s) it is not included in translation list. This is a quite a big deal and I did not find way how to add text to the list manually. Would you give me a hint how to proceed? I hope there is a way (workaround) how to do it. Thanks a lot. M.
Last updated: 2023-12-01
Post by snhatton on Running webvisu with Codesys Control Win V3 in Simulation Mode
CODESYS Forge
talk
(Post)
Yes, you can use the CODESYS ControlWin V3 Soft PLC. However, if simulation is enabled on the device this will disable all communication, so you need to turn off simulation to view the visualization in a web browser. In simulation mode, all IO and communication is disabled for standalone testing. In addition, make sure to set the start visualization in the WebVisu object in the application tree. I hope this helps!
Last updated: 2023-12-04
Post by mmoncada on Dinamically loading recipes
CODESYS Forge
talk
(Post)
I'm having trouble with the initial loading of recipes. I can create them and load one or the other, but when the program restarts the recipes are not listed. I'm calling: RecipeManCommands.ReloadRecipes and then RecipeManCommands.GetRecipeCount which returns 0 recipes. None of the methods returns error and if i call them again after RecipeManCommands.CreateRecipe RecipeManCommands.ReadAndSaveRecipe getRecipeCount returns the number of recipes created. When i restart the system, once again they are not listed even though the recipe files are there. Any ideas? Martin Btw, Codesys 3.5 SP 16 Path 9
Last updated: 2023-12-06
Post by voffi on Converting UINT into bytes and converting 2Bytes into UINT
CODESYS Forge
talk
(Post)
There are some ways. One is to use SHR and SHL and it depends on your byte order in the data array. For Motorola byte order: PROGRAM PLC_PRG VAR u : UINT; byte_array_in : ARRAY [1..8] OF BYTE := [16#11, 16#12, 16#13, 16#14, 16#15, 16#16, 16#17]; byte_array_out : ARRAY [1..8] OF BYTE; END_VAR u := SHL(TO_UINT(byte_array_in[2]), 8) + TO_UINT(byte_array_in[1]); byte_array_out[1] := TO_BYTE(u); byte_array_out[2] := TO_BYTE(SHR(u, 8)); If it's Intel byte order just change 1 and 2 in the array indexes.
Last updated: 2023-12-07
Post by svn123 on Can V3.5.19 and V2.3.9 be installed on same Windows10 PC without affecting each other?
CODESYS Forge
talk
(Post)
Hi All, Seasons Greetings! I have Codesys V3.5.19 patch 5 installed on a Windows 10 PC. I have received a program which is for Codesys V2.3.9. First I tried to convert it but had many conversion errors. I am wondering if it is possible to install Codesys V2.3.9 on same PC without affecting the V2.5.19 installations. Is this possible? SVN123
Last updated: 2023-12-28
Post by tvm on multiply gives negatives
CODESYS Forge
talk
(Post)
It's probably because you have an INT in the input to the MUL function, which will then try to output an INT as well. INT variables can only handle values of -32768 to 32767. Your value of 523000 won't fit in an INT, so it turns into an invalid number. Use a DINT. This is usually better for working with time values anyway, because time values are all 32 bit. Or if you can't, use INT_TO_DINT(gvlp.detectie_nalooptijd_s) in the input to the MUL function.
Last updated: 2024-01-04
Post by toby on SM Drive license error
CODESYS Forge
talk
(Post)
Hi albert1999 and forest, I hope you are well. I too am wondering if you have found any solutions? Im working with a RPi and a Omron R88D-ETH servo amplifier. The SoftMotion is timing out after 30min without the license, but I cant figure out how to license it, and I seem to have some compatibility issues between my RPi license and any SoftMotion licenses. Did you guys have any luck? Thank you very much for any assistance offered. Toby
Last updated: 2024-01-10
Post by timvh on Minimum system requirements for codesys control standard S
CODESYS Forge
talk
(Post)
It depends on your application which CPU speed and RAM size you need. If you think the Control Standard S license is sufficient then my guess is that your selected PC has no problem running your application. There are no more "hardware" based single licenses available anymore, only application based licenses. So this "Raspberry Pi" restriction for home automation is not applicable anymore. For more information see: https://store.codesys.com/en/howto_applicationbasedlicenses
Last updated: 2024-01-14
Post by sturmghost on Find visualization elements that require a lot of computing time
CODESYS Forge
talk
(Post)
I found out that the Codesys simulation mode is not good to measure performance. As soon as I upload the code onto the hardware PLC I can see that my visu-task needs around 60 ms to complete. I'm wondering if there is a possibility to find out which visualization/visualization element takes a lot of computing time? Then I would look for ways to decrease the long computing time.
Last updated: 2024-01-22
Post by jinlee on Multiple WebVisu
CODESYS Forge
talk
(Post)
Hi guys, I am new to the Visualization. I am having a problem. I have multiple web-panel to use webvisu. I have my software dowwloaded into the one PFC200. There are 3 screens connected to it. I noticed that if I switch page/visualisation on one of the screens, the others will change as well. Three screens are with different URLs that I set in the software. Is there any method to make them independently ? Kind regards, Jin.
Last updated: 2024-01-25
Post by wiresplus on INT_TO_WORD function not working
CODESYS Forge
talk
(Post)
Hello, I need to take an INT input, and convert it to a WORD value. VAR DRV2Speed : WORD; //IO card takes a WORD where 16000 = full 10V output (equivalent to 50Hz) PumpFillSpeed : INT; //Users enter a value between 0 and 50 END_VAR IF <conditions> THEN DRV2Speed :=INT_TO_WORD((PumpFillSpeed/50)*16000); END_IF </conditions> According to me this should work - but it stays at 0, no matter what. What am I doing wrong?
Last updated: 2024-01-26
Post by ojz0r on INT_TO_WORD function not working
CODESYS Forge
talk
(Post)
That calculation will not work the way you expect it to. If PumpFillSpeed is limitied to 0-50 then the only whole number would be 50/50 = 1 everything else is 0.0-0.9999... and since you are using word and integer only 50 would work since there is no representation for mantissa in integer values. Declare a temporary real variable and do the calculation and then do a REAL_TO_WORD in the DRV2Speed assignment.
Last updated: 2024-01-26
To search for an exact phrase, put it in quotes. Example: "getting started docs"
To exclude a word or phrase, put a dash in front of it. Example: docs -help
To search on specific fields, use these field names instead of a general text search. You can group with AND
or OR
.