Hi kporter, a more direct way would be to use SMC_FollowPosition to write the set positions directly to the servo drive. This FB has reacts on changes of the fSetPosition on each call, without a need for a rising edge on Execute. See https://content.helpme-codesys.com/en/libs/SM3_Basic/Current/SM3_Basic/POUs/Movement/Direct/SMC_FollowPosition.html. Best regards, Georg
Last updated: 2025-09-08

Post by snhatton on How to write a for loop in ladder? CODESYS Forge talk (Post)
Hi there, little late to the party, but you could also use the ST block for in-line ST code and implement a for loop as you normally would. ST Block is super handy if you just need a small amount of in-line structured text code without creating a new POU. Hope this helps!
Last updated: 2025-10-06

Post by arjunk on How to correctly create a device descriptor (.devdesc.xml) for a custom Linux ARM64 PLC in CODESYS 3.5.21.20? CODESYS Forge talk (Post)
Hi, I’m evaluating CODESYS for our devices. If I buy a standard runtime and the Toolkit, can I create a custom device descriptor so users can select my device (instead of just β€œCODESYS Control for Linux ARM64 SL”) when starting a new project? Has anyone done this or know if it’s possible? Thanks!
Last updated: 2025-10-07

Post by preimesbergert on Codesys Control for Raspberry Pi 4.10.0.0 - Raspberry Pi OS > 2023-12-05 CODESYS Forge talk (Post)
Same issue here: Raspberry Pi 4 Model B HW 1.5 Regardless of the image (tried 32bit / 64bit version from Raspberry Pi Imager- all the "standard version") and with all tested Codesys Control versions (4.2.0, 4.8.0, 4.10.0) and regardless if single core / multicore / 64 bit variant.
Last updated: 2023-12-21

Post by martinlithlith on Raspberry Pi: List of available drivers / libraries CODESYS Forge talk (Post)
Hi! I'm still on the hunt for drivers for example TCA9548 and a list or somewhere where all devices for raspberry is gathered. as this post is quite old I'm hoping/gussing that there is somewhere where work after 2021 is gathered? Or has the raspberry part if the community slowed down on creating device drivers?
Last updated: 2023-12-31

Post by peter-skokanek on Rpi install runtime licence on SP13 CODESYS Forge talk (Post)
Hi, I have an older project which has been running for years. Unfortunately I have to replace current Raspberry. I repplaced it by new rpi 3 with newest 32 bit Raspberry OS. I oredered a new runtime licence. When I try to activate it, the connection to target is interrupted immediatelly after press next button in the last step of instalation.
Last updated: 2024-01-08

Post by spiessli on Softmotion axis to CANopen Maxon IDX drive CODESYS Forge talk (Post)
Just verified the behaviour. Still is the same. It should be attached here. But I also tried the DCF-file with the axis in the lab with the real drive: The MC_Power block never goes out of busy. Had not time to investigate further, though.
Last updated: 2024-01-08

Post by anderson on function block output CODESYS Forge talk (Post)
so it is not possible for me to use the function blocks and through them I can select the digital outputs of the PLC so that pulses and direction are output, or some function block that does this reading and in it I can program the pulse and direction outputs for the drive?
Last updated: 2024-01-09

Post by timvh on Sysfile inuts CODESYS Forge talk (Post)
To prevent ambiguous use of this enumeration value. Let's say another ENUM is available in your project or in another library which has an enumeration value AM_WRITE, then it is not clear which AM_WRITE you want to assign. By this qualified access to the SysFile.AM_WRITE, it is completely clear for the compiler.
Last updated: 2024-01-14

Post by scarter on Import/Export PLCOpen xml Task Configuration CODESYS Forge talk (Post)
I'm Having the same issue. If I highlight PLC Logic and import it erases everything else and replaces the Task config. If I highlight the Application I get the same result. Simple manual fix is click and drag the task config onto the origional Application, and delete the second one. Easy fix but not the expected result of importing task config.
Last updated: 2024-01-17

Post by aniket-b on How to protect library project? CODESYS Forge talk (Post)
I have library projects which has few function blocks. I have assigned security to each FB. I want to protect them and user can only be able to use it without viewing the code inside. What kind of file I should send to user? Is it compiled library file?
Last updated: 2024-01-22

Post by kees-b on PLCnext Phoenix Contact CODESYS Forge talk (Post)
Hello We started with the new design of Codesys, through a "CODESYS Control Standard S" license. However, after installing the license, connecting, etc. (without any problems), we cannot get the program into the PLC with entries that we have not seen before. Is there anyone who has also experienced this? Better yet, does anyone have the solution?
Last updated: 2024-01-24

Post by kevin123 on MessageKey for missing library dialog CODESYS Forge talk (Post)
Hi Martin, I got the messagekey of the "upgrade format warning dialog" with key:"<< No Key>>". (please refer to the attachment) Is that means i can't use system.prompt_answers["<<No Key>>"] = PromptResult.OK; to auto-answer 'OK' in this dialog? Is there any other way to auto-answer this dialog? Thanks!
Last updated: 2024-01-26

Post by wiresplus on Connect to remote PLC via local pc and teamviewer CODESYS Forge talk (Post)
Hello, Depends on the architecture of your PLC. If the PLC is a PC-based item with a normal desktop environment, then you probably can. I find it simpler to install an IIoT Router in the panel, and use an encripted VPN to link to my office PC / Laptop on demand.
Last updated: 2024-01-26

Post by rkohser on Python Script for Finding "Last saved with" Value CODESYS Forge talk (Post)
Hi jkilburn, I have the exact same issue and thought I would search a solution on this forum. I see you did not get any answer, did you find a solution on how to extract the last saved version of codesys from the project file ? Roland
Last updated: 2024-01-29

Post by hagroth on v3.5 SP19 - Modbus TCP Devices - Channel Limit? CODESYS Forge talk (Post)
Today I was struggling with the same problem. in search for a solution i found this thread. Then i tried some things. It doesn't seem to be just a libraries' fault. In addition to 3.5.19, we also have a 3.5.18 version installed, the library versions of Modbus_TCP_Master and Modbus_TCP_Slave are the same, but more than 10 slave channels can be added in 3.5.18
Last updated: 2024-02-02

Post by mondinmr on Why SysPipeWindows is not implemented in RTE? CODESYS Forge talk (Post)
This library would be very useful for IPC communications. Using a UDP socket on localhost is unpredictable, as with slightly loaded machines it does not even guarantee packet delivery locally. Using TCP creates a lot of overhead. Message named pipes would be an excellent solution for Windows RTE. On Linux, since the release of the extension package, there is no issue, as it is sufficient to develop a component. However, although now 90% of our clients understand that Linux runtimes are better in every way compared to Windows RTE, especially from the security aspect (Not in kernel space) and the issues with Windows updates, 10% stubbornly insist (sometimes for trivial commercial reasons) on using Windows. Managing IPC with circular buffers in shared memory is quite ugly, or rather really ugly and unaesthetic. In the manuals, I saw the SysPipeWindows libraries, so I decided to test them, but unfortunately, I noticed that they are not implemented for RTE devices. Technically, I could try to open them as regular files, but SysFileOpen returns 16#27 or 16#39 depending on how I set the name (direction of the slashes). Here is the code to create shared memory and named pipes. Shared memory work great, named pipes no! #ifdef Q_OS_WIN32 SECURITY_ATTRIBUTES sa; SECURITY_DESCRIPTOR sd; InitializeSecurityDescriptor(&sd, SECURITY_DESCRIPTOR_REVISION); SetSecurityDescriptorDacl(&sd, TRUE, NULL, FALSE); sa.nLength = sizeof(SECURITY_ATTRIBUTES); sa.lpSecurityDescriptor = &sd; sa.bInheritHandle = FALSE; const wchar_t* name = L"Global\\ShmTest"; HANDLE hMapFile = CreateFileMapping( INVALID_HANDLE_VALUE, NULL, PAGE_READWRITE, 0, sizeof(SharedData), name); if (hMapFile == NULL) { qCritical("Error creating shared memory"); return 1; } data = static_cast<SharedData*>(MapViewOfFile(hMapFile, FILE_MAP_ALL_ACCESS, 0, 0, sizeof(SharedData))); if (data == NULL) { qCritical("Error mapping shared memory"); return 1; } HANDLE hPipe = CreateNamedPipe( TEXT("\\\\.\\pipe\\MyPipe"), PIPE_ACCESS_DUPLEX, PIPE_TYPE_MESSAGE | PIPE_READMODE_MESSAGE | PIPE_WAIT, PIPE_UNLIMITED_INSTANCES, 1024 * 1024, 1024 * 1024, NMPWAIT_USE_DEFAULT_WAIT, &sa); if (hPipe == INVALID_HANDLE_VALUE) { qCritical("Error creating named pipe"); return -1; } if (!ConnectNamedPipe(hPipe, NULL)) { qCritical("Error connecting to named pipe"); return -1; } checkPipe(hPipe); #endif
Last updated: 2024-02-02

Post by dhumphries on Using Codesys example problems CODESYS Forge talk (Post)
You have to install any libraries needed by the sample program. Click the button with ... next to one of the errors (see attached image,) then choose download missing libraries. Codesys should automatically locate and install the missing libraries, it's not flawless though, I've had some issues getting libraries to install. The best advice I can give if it doesn't work is re-install Codesys.
Last updated: 2024-02-03

Post by dhumphries on WAGO PLC 200 750-8216 Ethernet connection to Codesys 3.5 CODESYS Forge talk (Post)
make sure the PLC and the programming PC have IP addresses that are on the same subnet, you'll have to know the default address of the PLC or you may need to connect to it with a special cable and use a software tool to set the IP address.
Last updated: 2024-02-06

Post by davidbo on i2c How does CODESYS handle exception or error messages. CODESYS Forge talk (Post)
For Raspberry Pi I have made a python script which regularly read a bulk of data over the ic2 from a device. Sometimes I get an Exception an IOError. I assume similar things can happen in CODESYS. So how does CODESYS handle that? Can I get any info about such an event?
Last updated: 2024-02-07

Post by davidbo on Is it possible in the log to see previous shutdown CODESYS Forge talk (Post)
If my application does some kind of violation which makes it cast an exception it will trigger my real watchdog which results in a reboot. Unfortunately the log it seems only shows the boot sequence. Is it possible to see what happen before reboot?
Last updated: 2024-02-08

Post by nima-khajehali on Touch Issues in Tablet (HMI) CODESYS Forge talk (Post)
Hi Everybody, I download the Visualization on the Dell tablet as HMI. The button of HMI does not work with any touches. However, the buttons is working well with a plugged in mouse. Is there any configuration in Visu. manager or setting that I can modify? (Latitude 7230 Rugged Extreme Tablet) Please help me.
Last updated: 2024-02-08

Post by ferrim on IEC 61499 CODESYS Forge talk (Post)
Hello otdeveloper, I am very interested in this topic. I have been dedicated to IEC 61499 for some time and I would like to understand if the time has come to adopt it in the real world of automation or if it will continue to fill up research papers only.
Last updated: 2024-02-09

Post by dkugler on Color Change for Symbols not working CODESYS Forge talk (Post)
to modify and change the color of this icons from symbols lib I placed it in a visu. After download to the device, I uploaded the SVG files and saved it local. Now I was able to modify them with inkscape and import it to my own imagepool in the project :-)
Last updated: 2024-02-13

Post by rmaas on Direct Pointers in IOMapping for EtherCAT with IoDrvEthercatLib.ETCSlave_Dia CODESYS Forge talk (Post)
Hi, Im not sure if this is what you mean, but i do succesfully use the IoDrvEthercatLib.ETCSlave.InputData and IoDrvEthercatLib.ETCSlave.OutputData to read from and write to beckhoff DI and DO cards. Very convenient as you can make an FB with an VAR_IN_OUT of type IoDrvEthercatLib.ETCSlave and only have to pass the slave reference... So i am not using .ETCSlave_Diag but .ETCSlave...
Last updated: 2024-02-13