Post by ara32 on CODESYS 4 Linux:
CODESYS Forge
talk
(Post)
Hello! I managed to correctly launch CODESYS Developer Studio 3.5.17, almost all functionality works. The only issue remaining is that when connecting to a device and obtaining its public key, the NCryptEncrypt function is called, which is not fully implemented in the DLL source code, resulting in the connection not being established. Currently, the code of this function in the Wine repository looks like this: SECURITY_STATUS WINAPI NCryptEncrypt(NCRYPT_KEY_HANDLE key, BYTE *input, DWORD insize, void *padding, BYTE *output, DWORD outsize, DWORD *result, DWORD flags) { struct object *key_object = (struct object *)key; TRACE("(%#Ix, %p, %lu, %p, %p, %lu, %p, %#lx)\n", key, input, insize, padding, output, outsize, result, flags); if (flags & ~(NCRYPT_NO_PADDING_FLAG | NCRYPT_PAD_OAEP_FLAG | NCRYPT_PAD_PKCS1_FLAG | NCRYPT_SILENT_FLAG)) { FIXME("Flags %lx not supported\n", flags); return NTE_BAD_FLAGS; } if (flags & NCRYPT_NO_PADDING_FLAG || flags & NCRYPT_PAD_OAEP_FLAG) { FIXME("No padding and oaep padding not supported\n"); return NTE_NOT_SUPPORTED; } if (key_object->type != KEY) return NTE_INVALID_HANDLE; return map_ntstatus(BCryptEncrypt(key_object->key.bcrypt_key, input, insize, padding, NULL, 0, output, outsize, result, flags)); } The program crashes due to the NCRYPT_PAD_OAEP_FLAG flag. I'm not proficient in C++, but I attempted to add handling myself, and here's the result: SECURITY_STATUS WINAPI NCryptEncrypt(NCRYPT_KEY_HANDLE key, BYTE *input, DWORD insize, void *padding, BYTE *output, DWORD outsize, DWORD *result, DWORD flags) { struct object *key_object = (struct object *)key; TRACE("(%#Ix, %p, %lu, %p, %p, %lu, %p, %#lx)\n", key, input, insize, padding, output, outsize, result, flags); if (flags & ~(NCRYPT_NO_PADDING_FLAG | NCRYPT_PAD_OAEP_FLAG | NCRYPT_PAD_PKCS1_FLAG | NCRYPT_SILENT_FLAG)) { FIXME("Flags %lx not supported\n", flags); return NTE_BAD_FLAGS; } if (flags & NCRYPT_NO_PADDING_FLAG) { FIXME("No padding not supported\n"); return NTE_NOT_SUPPORTED; } BCRYPT_OAEP_PADDING_INFO oaepInfo = { 0 }; oaepInfo.pszAlgId = BCRYPT_SHA1_ALGORITHM; NTSTATUS status = BCryptEncrypt(key_object->key.bcrypt_key, input, insize, &oaepInfo, NULL, 0, output, outsize, result, flags); if (key_object->type != KEY) return NTE_INVALID_HANDLE; return map_ntstatus(BCryptEncrypt(key_object->key.bcrypt_key, input, insize, padding, NULL, 0, output, outsize, result, flags)); } Now, when calling the connection, it crashes with the error "bcrypt:BCryptEncrypt flags 0x4 not implemented." Can anyone help with enhancing this functionality or at least point me in the right direction?
Last updated: 2024-03-22
Post by mimodia1 on I do not have any reedings in RUN MODE from MPU6050........
CODESYS Forge
talk
(Post)
Good morning, mecke96. Exactly the same thing happens to me, although I have not done the part of executing a .py file. It only reads the temperature and the counter, but the other values are zero as in your image "no readings". I have tested the MPU6050 device on an Arduino and it works. Could you tell me if you solved it?
Last updated: 2024-03-29
Post by amy123 on Alarm Manager Project Doesn't Open Successfully
CODESYS Forge
talk
(Post)
Hello, when I download AlarmManager.project from https://forge.codesys.com/prj/codesys-example/alarm-manager/home/Home/, it gives an error when I open it. If I ignore the warning and continue to open, the alarms are missing. ** Exception Text ** System.ArgumentNullException: Value cannot be null. Parameter name: first at _3S.CoDeSys.ControlsContrib.Utilities.WeakMulticastDelegate.Invoke(Object[] args) at _3S.CoDeSys.ControlsContrib.Controls.WizardControl.OnFinishClick(EventArgs e) at System.Windows.Forms.Control.OnClick(EventArgs e) at System.Windows.Forms.Button.OnMouseUp(MouseEventArgs mevent) at System.Windows.Forms.Control.WmMouseUp(Message& m, MouseButtons button, Int32 clicks) at System.Windows.Forms.Control.WndProc(Message& m) at System.Windows.Forms.ButtonBase.WndProc(Message& m) at System.Windows.Forms.Button.WndProc(Message& m) at System.Windows.Forms.NativeWindow.Callback(IntPtr hWnd, Int32 msg, IntPtr wparam, IntPtr lparam)
Last updated: 2024-04-04
Post by sachem on SysFileGetTime problem
CODESYS Forge
talk
(Post)
Good morning. I'm working with a Weidmuller controller using Codesys. My project use OPC-UA to communicate an application in my pc with the controller. Yesterday, I installed the license of the controller and test it, and the communication works perfect. I use the communication with anonymous login, and works fine. But, hours later, the anonymous login don't work, and the controller only allows connection via OPC with username and password. Someone know why this happend? Thanks
Last updated: 2024-04-09
Post by food on Beaglebone Black OPC-UA Server
CODESYS Forge
talk
(Post)
Man, this was a long time ago. I think the problem probably stemmed from not loading the certificates from the client and the server on the server and client respectively in the correct manner. I believe I ended up getting around it just by removing all security on the server. In the end we did not move forward with that architecture so I never had to actually fix it.
Last updated: 2024-04-10
Post by tib0r on c2iec - translating C to ST
CODESYS Forge
talk
(Post)
I was looking for a transpiler from some more widely used general programming language into ST. It was not easy but I found this :) https://forge.codesys.com/tol/c2iec/home/Home/ Does anybody use it for a programm/library of a couple of hundred lines or more? How does one go about using the output? Is there a “converter” into the Codesys IDE? PLCOpenXML? Would there be interest in this? tib0r
Last updated: 2024-04-20
Post by valenting on Problem with Licenced Software Metrics
CODESYS Forge
talk
(Post)
Hi, When I try to install my codesys program with the new application-based licensing, I have an error "it exceeds the scope of the license agreement. See Device > Licensed Software Metrics" In the Licensed Software Metrics section, I see a code size < 3MB and less than 2700 variables in visualiaztions. I'm using a license "Control Basic L" with "Codesys Visualization L" option, so it should be enough with these metrics. What can I do ?
Last updated: 2024-04-22
Post by hoatran on Use third party actuator with IO-Link Master (IFM)
CODESYS Forge
talk
(Post)
The generic sensor FB is for controlling the sensor via its cyclic input (PDI) and output (PDO). In this case, ifm raw cyclic input and output data are WORDs (16 bits total) The PDO data from the Buerkert unit are SINT (8 bits) In this case, I would use the unpackword fb from the CAA memory library to unpack the valve feed back value into the appropriate location.
Last updated: 2024-04-23
Post by valenting on Problem with Licenced Software Metrics
CODESYS Forge
talk
(Post)
Hi, I tried with another project, using codesys SP20 with the latest visualization installed, I can install the application on my device but it doesn't work I get an exception "invalid license metrics" and the app won't run See attached the metrics in project and allowed by license, and the logs What am I supposed to do ? Everything is in the newest version and the values are lower than allowed and nothing works...
Last updated: 2024-04-26
Post by timvh on Codesys SVN
CODESYS Forge
talk
(Post)
If you use 3.5 SP10, then Git is not supported. SVN will work fine, but with this version you do need a USB key, because software licenses are not supported with this version. Off course you can work without SVN (or Git), but especially if you work with multiple developers on one project, it will save you a lot of time and you can keep track of all changes and improvements much easier. So how much is this worth to you?
Last updated: 2024-04-30
Post by fless on FB having single input but initialized with Array
CODESYS Forge
talk
(Post)
Why will it retain the sum value from the last call? This is how PLC work. Usually variables only get initialized after a download or a reset (i.e. power loss). RETAIN variables are saved in a special kind of RAM and keep their value after a power loss. To initialize variables on every call of your FB use the VAR TEMP block. VAR_TEMP sum : INT; END_VAR
Last updated: 2024-05-07
Post by totorovic on Softmotion not working with simulation mode
CODESYS Forge
talk
(Post)
Good morning, I think that the mode Simulation does not support the Softmotion functionnality because it runs the CODESYS process with normal priority wich is not a good thing for real-time behavior. If you want to test your PLC project, please use a Codesys Control Softmotion (and your computer must have the Ethercat driver installed) or much easier, download your code into the C6 Smart. BR
Last updated: 2024-05-13
Post by tomas111 on OPC UA Client API
CODESYS Forge
talk
(Post)
I ran into a problem. Uploaded an example (https://content.helpme-codesys.com/en/CODESYS%20Examples/_ex_uacapi_example.html) After launch. on the emulator. I see that I am having problems: - UaExpert does not connect. There are many servers but no connection. - I can’t transfer the certificate from quarantine to trusted ones. There is some problem with creating the certificate. CS 19.2. If anyone has had similar problems, please give me advice. Thank you.
Last updated: 2024-05-20
Post by yofi on Raspberry Pi 4 POU not running
CODESYS Forge
talk
(Post)
I have this error where the pou doesn't run even for simple programs like contact and a coil if i remove the pou from the task and put another one it works for one run then it stops working again in the photo we can see a contact is on but the coil connected to it is still not on and the device is in run mode I had this issue again and again any help
Last updated: 2024-06-02
Post by yofi on Raspberry Pi 4 POU not running
CODESYS Forge
talk
(Post)
I have this error where the pou doesn't run even for simple programs like contact and a coil if i remove the pou from the task and put another one it works for one run then it stops working again in the photo we can see a contact is on but the coil connected to it is still not on and the device is in run mode I had this issue again and again any help
Last updated: 2024-06-02
Post by arcadium on TargetVisu element stacking on top of each other
CODESYS Forge
talk
(Post)
Hello, I'm new here so if I do something wrong please bare with me. I am using raspberry pi touchscreen made by comfile (CPi-C070WR4C). I also have a window 11 pc where I would like to have a second visualisation, but when I run a TargetVisu with it, all elements of the visualisation end up in the top left corner stacked on top of each other. I have same results running targetVisu on my laptop. Maybe someone had same issues and know the solution? Simas
Last updated: 2024-06-17
Post by s1mon on Two OneWireMaster on one Raspberry PI 5
CODESYS Forge
talk
(Post)
All Sensors from the OneWire Master are assigned already to a seperate task with low prio (26) that runs with 1s cycle time. My EtherCat Task is running with Prio 1. It all works fine, until I adjust the CODESYScontrol.cfg or the CODESYScontrol_Usr.cfg files so that it supports a 2nd OneWire Master in the Codeys Runtime. If I change something in this config file and reboot my EtherCat Master stops working.
Last updated: 2025-10-19
Post by mizi on SM_Drive_Virtual
CODESYS Forge
talk
(Post)
Hi I recently started learning Codesys SoftMotion. At first, I mainly used YouTube videos. I stopped at two videos where the same problem keeps recurring. fbReadPos( Axis := X_Axis, Enable := TRUE, Position => gAxes.lrActualPos); <- axis cannot move I checked the entire code line by line. Zero errors. GPT spits out nonsense, throwing up increasingly worse errors. And when I copy its code, it says the code is wrong and gets stuck in a loop of its own stupidity. Can anyone explain why it doesn't work? Link to the video below: https://www.youtube.com/watch?v=CYa2HvYZgbM&list=PLsEhEcYjG7na0OveU7cqFXBx7ATyGGn0A&index=3
Last updated: 2025-10-21
Post by shaunvdm on OSCAT Scale_r function not working in LD 4.60 works in LAD2 on 3.5.21sp3
CODESYS Forge
talk
(Post)
Hi We have picked up an issue OSCAT_BASIC.Scale_r function call not working in the old lad and FBD version 4.60. Gives no output on the function call. When we convert this to LAD2 it works. As can be see by the two screenshot in normal LD not working in LAD2 it works. Please confirm if this is an issue with Oscat or with LAD in 3.5.21sp3, is there an workaround. Regards Shaun
Last updated: 2025-10-23
Post by shaunvdm on OSCAT Scale_r function not working in LD 4.60 works in LAD2 on 3.5.21sp3
CODESYS Forge
talk
(Post)
Hi We have picked up an issue OSCAT_BASIC.Scale_r function call not working in the old lad and FBD version 4.60. Gives no output on the function call. When we convert this to LAD2 it works. As can be see by the two screenshot in normal LD not working in LAD2 it works. Please confirm if this is an issue with Oscat or with LAD in 3.5.21sp3, is there an workaround. Regards Shaun
Last updated: 2025-10-23
Post by gatewail0 on Digital Clock
CODESYS Forge
talk
(Post)
You can definitely pull the actual system time into CODESYS without too much trouble. Take a look at the SysTimeRtc or SysTime library—both let you read the current date and time from the Raspberry Pi. You can call SysTimeRtcGet() or SysTimeGetTime() in your PLC code and then format the hours, minutes, and seconds into variables that feed your 7-segment visualization. Once you’ve mapped those values, your Visu display will update automatically each cycle. It’s a pretty common approach for clocks in CODESYS, so you should be able to get it working quickly. golf hit
Last updated: 2025-12-04
Post by nxbp on About Compatibility
CODESYS Forge
talk
(Post)
Let's say I have a CODESYS controller (PLC) with a runtime version around 3.5.19. If I use development software version 3.5.21.40 or a later version that will be released in the future for programming, could there be any problems or malfunctions in the controller's program execution or in the execution of the new, updated function blocks from the newer software? I mostly work with servo-based motion applications, so please keep that in mind when answering, and provide a detailed answer so I don't have to email you again about this topic.
Last updated: 2025-12-11
Post by bertus on Can't get SMC_SmoothPath to work
CODESYS Forge
talk
(Post)
Hello all, I am trying to run a XY trajectory from a static G-Code file. Everything works except the smoothing/blending of the corners. My setup: Codesys v3.5sp18 Raspberry Pi 4 CODESYS Control for Raspberry Pi SL, using demo license. Zero axes (only using the interpolator). The order of processing for my decoding is: SMC_NCDecoder (ok) SMC_SmoothMerge (ok) SMC_SmoothPath (not ok) SMC_LimitDynamics SMC_CheckVelocities I created following instances and buffers: fbNCDecoder: SMC_NCDecoder; fbSmoothMerge: SMC_SmoothMerge; fbSmoothPath: SMC_SmoothPath; fbLimitDynamics: SMC_LimitDynamics; fbCheckVelocities: SMC_CheckVelocities; aNCDecoderBuffer: ARRAY[0..49] OF SMC_GeoInfo; // buffer stage 1 (fbNCDecoder) aSmoothMergeBuffer: ARRAY[0..19] OF SMC_GeoInfo; // buffer stage 2 (fbSmoothMerge) aSmoothPathBuffer: ARRAY[0..99] OF SMC_GeoInfo; // buffer stage 3 (fbSmoothPath) aLimitDynamicsBuffer: ARRAY[0..39] OF SMC_GeoInfo; // buffer stage 4 (fbLimitDynamics) My original G-Code file has a lot of short G1 elements but this example, I reduced it to a simple square: N000 G51 D10 N010 G38 O1 N020 G00 X0 Y0 F50 E1000 E-1000 N030 G01 X0 Y-37.5 N040 G01 X-75 Y-37.5 N050 G01 X-75 Y37.5 N060 G01 X0 Y37.5 N070 G01 X0 Y0 N080 G50 N090 G39 O1 In the Codesys CNC settings, I have these instances activated: SMC_SmoothMerge SMC_SmoothPath SMC_LimitDynamics SMC_CheckVelocities And with those settings (and the path-preprocessing button actived), the G-Code viewer shows the square with nicely blended corners (see attached picture). However, when running it on the PLC, it doesn't blend the corners at all. Below the relevant part of my code. The process is started with bDecode. // stage 1: decoding G-code fbNCDecoder( ncprog := square, bExecute:= bDecode, bAbort:= NOT bDecode, nSizeOutQueue := SIZEOF(aNCDecoderBuffer), pbyBufferOutQueue := ADR(aNCDecoderBuffer) ); // stage 2: merge short linear segments fbSmoothMerge( bExecute := bDecode, poqDataIn := fbNCDecoder.poqDataOut, nSizeOutQueue := SIZEOF(aSmoothMergeBuffer), pbyBufferOutQueue := ADR(aSmoothMergeBuffer), piMaxDifference := PI_MAX_DIFFERENCE, usiMaxDegree := 5, wFeatureFlag := 1, wAdditionalParamNumber := 0, dMinimumCurvatureRadius := D_MIN_CURVATURE_RADIUS ); // stage 3: smooth corners fbSmoothPath( bExecute := bDecode, bAbort := NOT bDecode, poqDataIn := fbSmoothMerge.poqDataOut, eMode := SMC_SMOOTHPATHMODE.SP_SPLINE5_MIN_CURVATURE, eAddAxMode := SMC_SMOOTHPATHADDAXMODE.SPAA_NONE, nSizeOutQueue := SIZEOF(aSmoothPathBuffer), pbyBufferOutQueue := ADR(aSmoothPathBuffer), dAngleTol := D_ANGLE_TOL, bSymmetricalDistances := TRUE, bImprovedSymmetricCuts := TRUE ); // stage 4: keep acc/dec and velocity within limits fbLimitDynamics( bExecute := bDecode, bAbort := NOT bDecode, poqDataIn := fbSmoothPath.poqDataOut, wAxis := 16#07, nSizeOutQueue := SIZEOF(aLimitDynamicsBuffer), pbyBufferOutQueue := ADR(aLimitDynamicsBuffer), bIncludePathSettings := TRUE, dMaxVel := 2500, dMaxAccDec := 10000 ); // stage 5: check the path speed fbCheckVelocities( bExecute := bDecode, bAbort := NOT bDecode, poqDataIn := fbLimitDynamics.poqDataOut, dAngleTol := D_ANGLE_TOL); pathQueue := fbCheckVelocities.poqDataOut; // repeat until MaxDuration ... Any idea what I'm doing wrong? Is smooth path supposed to work at all when using a demo license? Thanks.
Last updated: 2 days ago
Post by adamrobotic on llcallback() iec exception caught cmpid=0x00000002, eventid=0x00010008
CODESYS Forge
talk
(Post)
Hi All, Recently I have been experiencing a issue in CodeSys SP16 Patch 3, with a exception which comes up after I have made several online changes. callcallback() iec exception caught cmpid=0x00000002, eventid=0x00010008, after I experience this fault then I receive a error message for any subsequent online change "online change failed, no task gap within 10000ms". To recover either the controller needs a orgin reset, which will allow online edits thereafter until falling back into the loop. I am using a TURCK TX707 product which is controlling robot trajectory, We have hard coded the coordinate data rather than using persistence variables so hence the need to do online changes consistently. I have read on the forum other people have experienced similar issue with the online task gap, but I have no task which have same priority and also monitored the CPU usage and have not seen it go above 13%. Anyones help would be much appreciated, thankyou.
Last updated: 2023-08-18
Post by ewi04 on Git with visu
CODESYS Forge
talk
(Post)
Hi, I have several problems with the git extension. Situation: I am working with Codesys v3.5 SP19 Patch 1 and Git V1.2.1.0. The remote repository is GitLab Community Edition v16.1.2. I am working on a project with one other person. Problems: 1: After each start of Codesys all of the visu pages are marked as modified. So we have to discard all changes first. Otherwise the history is not clean and the merge request becomes more complex. I tested it with a new project and only local. I made the observation, that a page is not marked as modified when it is committed a second time (after a restart of codesys). But this is necessary after every change of a page. However, since we are working in a team, it seems we are playing ping-pong and so all pages are marked as modified on each startup. 2: Each image pool causes a parent child conflict. Also in my local project. The only solution that I have found, is to ignore the issue. Does anyone have the same problems? I think it looks more like bugs. Thanks ewi04
Last updated: 2023-11-22
To search for an exact phrase, put it in quotes. Example: "getting started docs"
To exclude a word or phrase, put a dash in front of it. Example: docs -help
To search on specific fields, use these field names instead of a general text search. You can group with AND or OR.