  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Maybe this helps: https://forge.codesys.com/forge/talk/Runtime/thread/fa012acc3e/#9506

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Which PLC do you use? If it is a standard CODESYS Runtime (from the store), then maybe update the device in your project to the latest version. If it is not a standard CODESYS Runtime, then maybe contact the supplier.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    1) In the library manager of your project select "Download missing libraries". 2) In the library manager open the "Placeholders" dialog. In here find the Placeholder which is not referenced to a specific library yet. Click in this line on the Library column and select the latest version of this library.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Maybe it is better to use the functionality of the Extension Package: https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_extension.html https://content.helpme-codesys.com/en/CODESYS%20Examples/_ex_extension_package.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    According to the documentation: https://wiki.teltonika-networks.com/view/RUT956_Modbus You need to create a Channel to read 2 registers from address 143 to get the lattitude. It doesn't specify if you need to read it as a Holding Register or as an Input Register. You could try both. So in the Teltonika router, you need to enable it as being a Modbus Server. Then in CODESYS add an Ethernet Adapter, then a Modbus Client (Master) and to the Client (Master) add the Modbus Server (Slave). Set the IP address...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You can consider using OR_ELSE: Coils[0] := Coils[0] OR_ELSE (Buttons[0] AND Sensors[0] > 6); https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_operator_or_else.html IF Coils[0] is TRUE, then the rest is not relevant anymore and doesn't have to be evaluated anymore. PS, there is also an AND_THEN https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_operator_and_then.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    https://store.codesys.com/en/codesys.html#versions

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Maybe the ANY type can help? https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_datatype_any.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Go to the menu Tools - CODESYS Installer. Here you can manage your add-on packages. Go to Browse, find CODESYS Communication and install this add-on.

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Take a look at the following for the possible location: https://forge.codesys.com/forge/talk/Runtime/thread/7959e0c66c/#618c

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    In your soft plc folder, there is a file called targetvisuextern.cfg. Open this with a text editor to change the settings. Remove the semi-colons in front of the lines to enable your custom window settings. WindowType=0 means you will get a moveable window. Save the file and restart the soft PLC to enable these settings.

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    Double click on the device (communication settings). At the top of this Window, go to Device -Options. Disable the option "Confirmed online mode".

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    Double click on the device (communication settings). At the top of this Window, go to Device -Options. Disable the option "Confirmed online mode".

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Double click on the device (communication settings). At the top of this Window, go to Device -Options. Disable the option "Confirmed online mode".

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    This has been moved because of security reasons. But it depends on how you start CODESYS where the project files are located (at least for Control Win from SP20). 1) If you start it through the sys tray icon, you start it as a service and the files will be located in: C:\Windows*System32\config\systemprofile\AppData\Roaming\CODESYS... (or C:\Windows*SysWOW64**\config...) 2) If you start it as a user, e.g. with a shortcut to the runtime, you can find it in: C:\Users\<your user="" name="">\AppData...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Try this: VAR sTextList : STRING; END_VAR sTextList := 'NameOfTheTextList'; // call to the function with the address of the string variable which contains the name of the textlist : ... ADR(sTextList), ....

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You can get the state by just using the name of your node (same name as in device tree): VAR etcState: IoDrvEthercatDriverLib.ETC_SLAVE_STATE; END_VAR etcState := EJ1100.wState; Alternatively, you can iterate through the device tree to get the status of all (Ethercat) nodes. See here an example (no guarantee it works, just give as suggestion): PROGRAM P_IO_State VAR CONSTANT uiMAX_NR_OF_TERMINALS : UINT := 100; END_VAR VAR // general device diagnosis // can only be used when the Device - PLC Settings...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I guess that the printer expects to receive an array of byte values. So where it is described that it expects to receive: Hercules String : 1B4F513030311B7532626C61636B04 it actually expects to receive an array of bytes with the values 1B,4F,51,30,30, etc. So what you can do is create an array of bytes and assign the byte value to each item in the array: VAR abyToSend : ARRAY[0..99] OF BYTE; END_VAR abyToSend[0] := 16#1B; // ASCII Escape character, hexadecimal representation uses 16# as prefix abyToSend[1]...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I also couldn't find it at first, but please check this: C:\Program Files\CODESYS ..your version..\CODESYS\CODESYS Virtual Safe Control SL\Delivery\Manuals\

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Could you send a screenshot of the Ethernet "General" settings? In that screen you can also search for the Ethernet interface you would like to use for your communication. Did you do that? Did you change any settings manually in the CODESYSControl_user.cfg?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Is it really the same CODESYS version with the same add-ons? Maybe open the CODESYS installer on your home laptop, and export the configuration. On your work PC open the CODESYS installer and import the configuration.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    VAR RuntimeVersion: VERSION; END_VAR RuntimeVersion := __SYSTEM.Constants.RuntimeVersion; PS, when I call the SysTargetGetVersion on a Control Win, I get the value 50664488 = 16#03051428 equals version 3.5.20.40

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    What do you want to accomplish?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    What do you want to accomplish?

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    At the top of the Visualisation Properties View, you can enable the "Advanced" options. This will give you access to more properties than what you currently see. There might be a variable linked to the "advanced" colour property where the fill colour is determined by the value of this variable (dword).

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Probably the enum from the library doesn't have text support. In that case you need to add your own TextList to the application. In the rectangle you should use the property "dynamic text" to link this object to the textlist which you have created yourself and then link the text index to your enum variable.

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    A Task is a standard IEC 61131-3 object, so logically that you can export the VISU_TASK. A visualization is no standard IEC 61131-3 object, so not compatible with other IEC tools. Just use the standard export / import functionality. These files are not IEC compatible and can only be used in CODESYS. But these do support visu objects.

  • TimvH TimvH posted a comment on discussion Motion πŸ‡¬πŸ‡§

    See the attached picture.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Open the CODESYS installer (you can open this as stand-alone tool, or from CODESYS Tools menu). Then go to Browse, search for Git and select install.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If you are really happy with PLCnext engineer, then just use that. There is probably also something in CODESYS that cannot be done in PLCnext engineer. But if you are forced to make something like this in CODESYS, then maybe just use CFC instead of FBD.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    A standard string is actually a list of bytes that represent the ASCII code for each character. The following part of code will give you the ASCII code of one of the characters in the string: byChar := sInput[i];

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Go in Windows to this location. Right click on this file and go to properties. Is it in Read-only state? Then CODESYS cannot open in Write mode.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    A branch is a branch (doesn't grow back to the tree). But what you are trying to do is use several XORs. See attachement.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Nice puzzle for a Saturday afternoon :-). Here my suggestion: VAR sInput : STRING := 'R123'; byChar : BYTE; sOutput : STRING; i: INT; END_VAR sOutput := ''; IF LEN(sInput) = 0 THEN RETURN; END_IF FOR i := 0 TO LEN(sInput) - 1 DO byChar := sInput[i]; sOutput := Concat(sOutput, TO_STRING(byChar)); END_FOR

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The Modbus Master example must work. We have used this several times on multiple projects. See https://forge.codesys.com/prj/codesys-example/modbus/home/Home/

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You can enable "Sync Producing" in the configuration of the CANopen Manager. Then this manager will send a SYNC message every interval you set. Depending on your PDO configuration, the CAN nodes can send a PDO on every Sync (cyclic-synchronous). If this is not possible, then as alternative you can send a low level CAN message with COB-ID 16#80.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Do you mean VAR_TEMP? https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_vartypes_var_temp.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    This is not possible. Possible solution could be: CASE var1 OF 10: CASE var2 OF 10:; 20:; END_CASE 20: CASE var2 OF 10:; 20:; END_CASE ELSE ; END_CASE

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Most likely your IP address is set to 172.... because you use a VPN connection to your device. Probably best to use the other Ethernet interface for your modbus communication.

  • TimvH TimvH modified a comment on discussion Runtime πŸ‡¬πŸ‡§

    It seems you have 2 network interfaces. Did you try eth1? Did you already configure the IP address for this interface in Linux? If yes, then maybe undo this. - or only set eth0 in the Nic configuration without anything else (so no IP address, because this is already set in Linux). For more information about the Nic settings, see (probably already read it?): https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_obj_deploy_control_sl_configuration.html PS, if you only want to run CODESYS Control...

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    It seems you have 2 network interfaces. Did you try eth1? Did you already configure the IP address for this interface in Linux? If yes, then maybe undo this. For more information about the Nic settings, see (probably already read it?): https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_obj_deploy_control_sl_configuration.html PS, if you only want to run CODESYS Control SL, you don't necessarily need the Virtual PLC variant. You could also install and run the CODESYS Control SL Runtime...

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    RS485 doesn't seem very logical to use in VPLC's in my opinion. I also don't know if this is supported.... But for TCP/IP, I think you still need to configure the Nic settings. See the attached png. In my case enp6s0. When changing this setting, restart the VPLC. What is really nice, is that you don't have to configure the IP address setting in Linux. By setting the Nic to a certain IP address in the CODESYS instance configuration, this is automatically done for you. I only tested this with EtherCAT,...

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Should work by using the property Dynamic bitmap - Bitmap version. Change the value of the variable you linked to this property after you updated the image. See: https://content.helpme-codesys.com/en/CODESYS%20Visualization/_visu_elem_image.html

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    We have also used the Roboto font without any problems, but possibly your company modified it a little bit? Maybe you can try the original ones from Google: https://fonts.google.com/specimen/Roboto

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_pragma_attribute_instance_path.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Open the CODESYS Installer (from the menu Tools). Go to Browse. Search for: help ... Select the CODESYS Offline Help which you would like to install. (probably you have to close CODESYS to install it and reopen it after installation).

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The RTE will take the RTE license. The HMI will take the HMI license. For the Application Based Licenses, the Runtime will take the smallest which is required. So if you have an application running EtherCAT and no visualization, only the Control with support for EtherCAT is used. If you have another runtime which requires the visualization, it will take the smallest Control license which is required and available + the smallest visualization license which is required.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I see, you want to initialize the FB. To be able to initialise it like you described, you need to add the FB_Init method to your FB. (right click on the FB, select add object --> method). Then press the arrow down, to select the FB_Init (overwrite default implementation). In the VAR_INPUT section of this method, add the variable --> Tag : STRING; Then in the code section of this method add: THIS^.Tag := Tag; // copy initial value to local variable in FB Search Google if you want to know more about...

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    I had a similar situation recently where this didn't work, but read to the end to see the solution. The reason is that CODESYS only downloads visualisations (dialogs) if they are part of the project or linked to the project. In your case the dialog is not loaded onto the controller. But the solution is pretty simple: Double click on the Visualization Manager in your application. Select the Tab "Visualizations". Here you can see that your dialog is not "checked". Do this manually and load your project...

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Only idea I have is that new textlists are not loaded with an online change. When you add them, maybe you always have to do a full download first.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Really not clear what you are trying to do, but isn't a Struct enough? So add an object of the type DUT to the Application. Then create a structure TYPE ST_Sensor : STRUCT sName : STRING; uiNumber : UINT; END_STRUCT END_TYPE Then in you application add an instance of this Structure stSensor1 : ST_Sensor := (sName := 'my sensor', uiNumber := 1); or use it like this stSensor1.sName := 'my sensor';

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    IF you create an ENUM {attribute 'qualified_only'} {attribute 'strict'} TYPE E_IO : ( FIRST := 0, SECOND := 1 ); END_TYPE You should be able to access the array items like: IOCard_OUTPUT[E_IO.FIRST]

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    IF you create an ENUM {attribute 'qualified_only'} {attribute 'strict'} TYPE E_IO : ( FIRST := 0, SECDOND := 1 ); END_TYPE You should be able to access the array items like: IOCard_OUTPUT[E_IO.FIRST]

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    IF you create an ENUM {attribute 'qualified_only'} {attribute 'strict'} TYPE E_IO : ( FIRST := 0, SECDOND := 1 ); END_TYPE You should be able to access the array items like: IOCard_OUTPUT[E_IO.FIRST]

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If you have a Windows system (RTE), then why not run the CODESYS HMI as separate controller. This could easily be moved to another PC if required. In the HMI you could also still use the Symbolic Var access as part of the Data Source Manager, although maybe OPC is the preferred way to make it more future proof. Or what about the Remote Target Visu. Then you can reduce the load of the main controller, while still only having to create one application including Visualization. This is now also supported...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You could create a DUT of the Type Union and add an array of 2 bytes + an Int. Then write the byte values in the array of the Union and read the Int. Or VAR iInt : INT; byHigh : BYTE := 2#1111_1111; byLow : BYTE := 2#1111_1111; END_VAR iInt := TO_INT(byHigh*16#100 + byLow);

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    If you are not using any specific Raspberry Pi functionality, then probably the "universal" Control Linux ARM SL is the approriate runtime to run on the Pi. For the license it doesn't matter which runtime version you choose, because this is not hardware based anymore, but application based. Best is to use the latest version of CODESYS. To determine which license you need, double click on your device, go to the tab License metrics.... Generate the code for your application and see which license you...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You have declared the function block in a function and call the instance also from a function. This is not correct, because a function is initialised with every call. The http client function block should be declared as Global Variable if you want to cal it from a Function, but probably it is better to declare it in a Program and also call the instance of the http function block from the same Program.... The variables of a Program are not initialised with each call.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If your Control Win is the Modbus "Master" then your configuration should be something like: Modbus_COM (Serial port) - Modbus Master (this is the Control Win SoftPLC actively setting up the communication) - Modbus Slave (this is then your WAGO 750-315) You need to add channels to the Modbus Slave configuration to inform the master which variables to read/write from the Wago module. The way you configured it now, the Control Win is also a slave. PS, don't forget to put the PLC (Control Win) in R...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You cannot create an array of Programs. Create a Function Block for this purpose instead of a program. You can create an array of FB instances and call each instance in a loop.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    First of all you need to enable "Use unicodestrings" in the Visualization Manager. This function returns a pointer to a WSTRING (not STRING). To get this wstring value, do something like this: VAR myWstringVariable : WSTRING(255); END_VAR myWstringVariable := myResult^; // this is dereferencing the pointer to the WSTRING.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    https://content.helpme-codesys.com/en/CODESYS%20Git/_git_using_scripting.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    With new runtimes, the access outside the runtime folder is protected. See: https://forge.codesys.com/forge/talk/Engineering/thread/3da9ded84e/

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    I think, that if you set the timebase to T#0s, that it will be reset. But you can also make your own ramp down with a Timer (make sure the PT time is not T#0s):

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I think, that if you set the timebase to T#0s, that it will be reset. But you can also make your own ramp down with a Timer:

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The string_Util_Intern is not the library I referred to. With a CONCAT function (also with the string util library) a search is done for the NULL character. If you concatenate 20000 characters to one string, then the longer the string, the longer it takes to find this NULL character.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Create a (global) array of Messages: aMessage : ARRAY[0..NR_OF_MESSAGES-1] OF CAN.RxMESSAGE; Then add each received message to the array. IF UserVarGlobal.g_countMsg_RPMset < NR_OF_MESSAGES THEN aMessage[UserVarGlobal.g_countMsg_RPMset] := Message; UserVarGlobal.g_countMsg_RPMset := UserVarGlobal.g_countMsg_RPMset + 1; END_IF

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See: https://forge.codesys.com/prj/codesys-example/element-collect/home/Home/ This contains an application "OnlineChangeSafeLinkedListExample". What you should do is create a new interface which has your "Priority" property. Then your FB should extend the base element function block and implement your own interface: E.g. FUNCTION_BLOCK MyElement EXTENDS COL.LinkedListElementBase IMPLEMENTS I_MyInterface Then the __QUERYINTERFACE does the magic to check if your "element" also implements your interface....

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The new (UTF8) string library is faster and can handle large strings. https://content.helpme-codesys.com/en/CODESYS%20String%20Libraries/_strlib_start_page.html PS, in CODESYS, the maximum string length is not 255 characters. The String functions of the standard library are limited to strings of 255 characters. But you can use other (memory) functions to handle strings larger than 255 characters.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    https://forge.codesys.com/prj/codesys-example/file-utilities/home/Home/

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Their is quite a detailed explanation in the help: https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_codesys_modularization.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See: https://content.helpme-codesys.com/en/CODESYS%20FAQ/_faq_start_page.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The message means that you (CODESYS) tries to open the function block, but this is not possible because the library which contains the FB is compiled. You either get this when you try to manually open the function block (while editing the application), but it could also happen that an exception occurs in the running application and CODESYS tries to show the location where it occured. If it happened in an FB of the compiled library, it cannot show this and you could get this message too.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See: https://content.helpme-codesys.com/en/CODESYS%20Examples/_ex_canopen_canopen.html SDO example: SegmentedAndBlockWriteExample: Writing if an object of any length via SDO (segmented transfer or block transfer) by means of CiA405.SDO_WRITE_DATA This help page also contains a link to a demo project.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You could use the Modulo function to get the minute part from the total minutes: Minutes := TotalMinutes MOD 60;

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Your function block instance is not called, so the code is not executed to set the light on when the button is pressed.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If it is a BOOL, then use: ...Error_Active := ALARM BOOL: ALARM INT: STATE

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Do you mean this: https://content.helpme-codesys.com/en/CODESYS%20Communication/_comm_use_dynamic_opc_ua_server_comm_settings.html

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Probably best to call the FB continuously. So something like this could solve it: IF xOpenLatchSettingDialog THEN xOpenLatchSettingDialog := FALSE; fbOpenLatchSettingsDialog.xExecute := TRUE; END_IF IF fbOpenLatchSettingsDialog.xDone OR fbOpenLatchSettingsDialog.xError THEN fbOpenLatchSettingsDialog.xExecute := FALSE; END_IF TopLeftDialog.iX := 100; TopLeftDialog.iY := 23; fbOpenLatchSettingsDialog( itfClientFilter:= VU.Globals.OnlyTargetVisu, sDialogName:= 'visu_AlarmLatchSettings', xModal:= TRUE,...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Minimum version is 3.5 SP19 Patch 3. See https://store.codesys.com/en/codesys-git.html But you could ask your PLC vendor if it is possible to program their PLC's which have Runtime version SP16 with development version 3.5 SP19 or higher (should normally be possible, but with Safety PLC's there could be some regulation limitations).

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I don't know the details of jsonArrayWriter, but the common behaviour for an xExecute input is that the FB starts on the trigger that it gets TRUE. In your case xExecute is never FALSE, so it is never triggered again to start the jsonArrayWriter. So change the condition from TRUE to a variable which you set to TRUE with the "xFirst". Then when the jsonArrayWriter is done (xDone), or has an error (xError), then set this variable to FALSE.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If you use 3.5 SP10, then Git is not supported. SVN will work fine, but with this version you do need a USB key, because software licenses are not supported with this version. Off course you can work without SVN (or Git), but especially if you work with multiple developers on one project, it will save you a lot of time and you can keep track of all changes and improvements much easier. So how much is this worth to you?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    What we are trying to explain is that, yes CODESYS creates the software, but Epis decides how they implement it on their hardware, which runtime version they use and they decide which functionality they support. So it is always a combination of the two. What CODESYS provides is a runtime with options for e.g. visualization or softmotion. Epis could add this softmotion license as default to their controller, but if they don't then CODESYS provides another option with a single license in a "Wibu CodeMeter"...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Maybe also good to know that you could use the CODESYS installer to switch between gateways. - open the CODESYS installer - Select the (hamburger) menu - Select Settings - Select Services Then select the Gateway you would like to use.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Most likely related to the Device Diagnostics functionality. Double click on your device (PLC), go to the tab "PLC settings". Enable the advanced option "Enable diagnosis for devices". Build your application again.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You should only open de COM port once and then leave it open. This hCom should not keep on incrementing. (off course when you are done communicating, you need to close the COM port)

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    In your project you selected the "CODESYS Control Win V3" as device, but the device you want to connect to is a "CODESYS Control Win V3 x64". Those are not the same. If you double click on the device during the network scan, you will get information that these are not the same, but that you can change the type in your project to the x64 bit type. Another option is to "right-click" on the device in the device tree of your project and select "update device" then select the x64 type.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See the attached pdf with some notes (screenshots) which I prepared for one of our customers to help them get going. Hopefully this helps for you too.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Add the object "POU for Implicit Checks" to your application, then select "Bounds check". This will create a function which is automatically called each time an array is write accessed. In the function you can handle "out of bounds" situations. By default it will be limited to its lower or upper bound.

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Use e.g. the condition: TCP_Connection_0.xActive AND NOT(TCP_Write_0.xDone)

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I don't know the root cause... But what could help to continue when it seems to hang, is stop the CODESYS (communication) Gateway. Go to the Windows SysTray, find the icon for the Gateway and then stop it and start it again. This will interrupt the connection between CODESYS and your controller.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You should ask IFM to provide you with the correct version of their controller packages. Then after you have installed this, you can select the correct version of the controller by right clicking on it in the device tree, update device, enable the option "Display all versions" and then select the version which matches your controller. Alternatively you can ask IFM to provide an update package which can update the runtime version on your controller to 3.2.0.0.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Are you 100% sure you created a boot application?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Not sure, but maybe it related to the style. Go to the Visualization Manager in your project and see if a style is selected, or choose another style to see if this helps.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Are you using the Control Win SL (installed together with the development environment of CODESYS)? If yes, you might want to consider using the CODESYS RTE instead. This has real-time capabilities (running on separate core(s)). But to be able to use this, you have to install the CODESYS Ethernet driver for your network interface to be able to let the RTE access the network port also in realtime. See: https://store.codesys.com/en/codesys-control-rte-sl-bundle.html https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_windows_rts_v3.html...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Are you using the Control Win SL (installed together with the development environment of CODESYS)? If yes, you might want to consider using the CODESYS RTE instead. This has real-time capabilities (running on separate core(s)). But to be able to use this, you have to install the CODESYS Ethernet driver for your network interface to be able to let the RTE access the network port also in realtime. See: https://store.codesys.com/en/codesys-control-rte-sl-bundle.html https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_windows_rts_v3.html...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    This is almost always related to previously working with an additonal monitor. If you have placed CODESYS on that monitor, later start your laptop again and open CODESYS without that monitor, then Windows still places it in the previous position, but then it is not visible. So the solution by cehermanstad can be used to move it to the main screen to make it visible again. PS, another way to move it, is by pressing SHIFT and then right-click on the icon in the task bar, then select move. You can then...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I'm not sure, but maybe you have to configure the 750-652 first with the WAGO-IO-CHECK software to set it in RS485 mode?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You have selected the new Ladder editor. This only has these items in the toolbox.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The IoT library contains a Web Socket library. Maybe this provides your required functionality. See https://store.codesys.com/en/codesys-iiot-libraries-sl.html