Activity for TimvH

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If you are really happy with PLCnext engineer, then just use that. There is probably also something in CODESYS that cannot be done in PLCnext engineer. But if you are forced to make something like this in CODESYS, then maybe just use CFC instead of FBD.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    A standard string is actually a list of bytes that represent the ASCII code for each character. The following part of code will give you the ASCII code of one of the characters in the string: byChar := sInput[i];

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Go in Windows to this location. Right click on this file and go to properties. Is it in Read-only state? Then CODESYS cannot open in Write mode.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    A branch is a branch (doesn't grow back to the tree). But what you are trying to do is use several XORs. See attachement.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Nice puzzle for a Saturday afternoon :-). Here my suggestion: VAR sInput : STRING := 'R123'; byChar : BYTE; sOutput : STRING; i: INT; END_VAR sOutput := ''; IF LEN(sInput) = 0 THEN RETURN; END_IF FOR i := 0 TO LEN(sInput) - 1 DO byChar := sInput[i]; sOutput := Concat(sOutput, TO_STRING(byChar)); END_FOR

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The Modbus Master example must work. We have used this several times on multiple projects. See https://forge.codesys.com/prj/codesys-example/modbus/home/Home/

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You can enable "Sync Producing" in the configuration of the CANopen Manager. Then this manager will send a SYNC message every interval you set. Depending on your PDO configuration, the CAN nodes can send a PDO on every Sync (cyclic-synchronous). If this is not possible, then as alternative you can send a low level CAN message with COB-ID 16#80.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Do you mean VAR_TEMP? https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_vartypes_var_temp.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    This is not possible. Possible solution could be: CASE var1 OF 10: CASE var2 OF 10:; 20:; END_CASE 20: CASE var2 OF 10:; 20:; END_CASE ELSE ; END_CASE

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Most likely your IP address is set to 172.... because you use a VPN connection to your device. Probably best to use the other Ethernet interface for your modbus communication.

  • TimvH TimvH modified a comment on discussion Runtime πŸ‡¬πŸ‡§

    It seems you have 2 network interfaces. Did you try eth1? Did you already configure the IP address for this interface in Linux? If yes, then maybe undo this. - or only set eth0 in the Nic configuration without anything else (so no IP address, because this is already set in Linux). For more information about the Nic settings, see (probably already read it?): https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_obj_deploy_control_sl_configuration.html PS, if you only want to run CODESYS Control...

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    It seems you have 2 network interfaces. Did you try eth1? Did you already configure the IP address for this interface in Linux? If yes, then maybe undo this. For more information about the Nic settings, see (probably already read it?): https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_obj_deploy_control_sl_configuration.html PS, if you only want to run CODESYS Control SL, you don't necessarily need the Virtual PLC variant. You could also install and run the CODESYS Control SL Runtime...

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    RS485 doesn't seem very logical to use in VPLC's in my opinion. I also don't know if this is supported.... But for TCP/IP, I think you still need to configure the Nic settings. See the attached png. In my case enp6s0. When changing this setting, restart the VPLC. What is really nice, is that you don't have to configure the IP address setting in Linux. By setting the Nic to a certain IP address in the CODESYS instance configuration, this is automatically done for you. I only tested this with EtherCAT,...

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Should work by using the property Dynamic bitmap - Bitmap version. Change the value of the variable you linked to this property after you updated the image. See: https://content.helpme-codesys.com/en/CODESYS%20Visualization/_visu_elem_image.html

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    We have also used the Roboto font without any problems, but possibly your company modified it a little bit? Maybe you can try the original ones from Google: https://fonts.google.com/specimen/Roboto

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_pragma_attribute_instance_path.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Open the CODESYS Installer (from the menu Tools). Go to Browse. Search for: help ... Select the CODESYS Offline Help which you would like to install. (probably you have to close CODESYS to install it and reopen it after installation).

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The RTE will take the RTE license. The HMI will take the HMI license. For the Application Based Licenses, the Runtime will take the smallest which is required. So if you have an application running EtherCAT and no visualization, only the Control with support for EtherCAT is used. If you have another runtime which requires the visualization, it will take the smallest Control license which is required and available + the smallest visualization license which is required.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I see, you want to initialize the FB. To be able to initialise it like you described, you need to add the FB_Init method to your FB. (right click on the FB, select add object --> method). Then press the arrow down, to select the FB_Init (overwrite default implementation). In the VAR_INPUT section of this method, add the variable --> Tag : STRING; Then in the code section of this method add: THIS^.Tag := Tag; // copy initial value to local variable in FB Search Google if you want to know more about...

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    I had a similar situation recently where this didn't work, but read to the end to see the solution. The reason is that CODESYS only downloads visualisations (dialogs) if they are part of the project or linked to the project. In your case the dialog is not loaded onto the controller. But the solution is pretty simple: Double click on the Visualization Manager in your application. Select the Tab "Visualizations". Here you can see that your dialog is not "checked". Do this manually and load your project...

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Only idea I have is that new textlists are not loaded with an online change. When you add them, maybe you always have to do a full download first.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Really not clear what you are trying to do, but isn't a Struct enough? So add an object of the type DUT to the Application. Then create a structure TYPE ST_Sensor : STRUCT sName : STRING; uiNumber : UINT; END_STRUCT END_TYPE Then in you application add an instance of this Structure stSensor1 : ST_Sensor := (sName := 'my sensor', uiNumber := 1); or use it like this stSensor1.sName := 'my sensor';

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    IF you create an ENUM {attribute 'qualified_only'} {attribute 'strict'} TYPE E_IO : ( FIRST := 0, SECOND := 1 ); END_TYPE You should be able to access the array items like: IOCard_OUTPUT[E_IO.FIRST]

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    IF you create an ENUM {attribute 'qualified_only'} {attribute 'strict'} TYPE E_IO : ( FIRST := 0, SECDOND := 1 ); END_TYPE You should be able to access the array items like: IOCard_OUTPUT[E_IO.FIRST]

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    IF you create an ENUM {attribute 'qualified_only'} {attribute 'strict'} TYPE E_IO : ( FIRST := 0, SECDOND := 1 ); END_TYPE You should be able to access the array items like: IOCard_OUTPUT[E_IO.FIRST]

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If you have a Windows system (RTE), then why not run the CODESYS HMI as separate controller. This could easily be moved to another PC if required. In the HMI you could also still use the Symbolic Var access as part of the Data Source Manager, although maybe OPC is the preferred way to make it more future proof. Or what about the Remote Target Visu. Then you can reduce the load of the main controller, while still only having to create one application including Visualization. This is now also supported...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You could create a DUT of the Type Union and add an array of 2 bytes + an Int. Then write the byte values in the array of the Union and read the Int. Or VAR iInt : INT; byHigh : BYTE := 2#1111_1111; byLow : BYTE := 2#1111_1111; END_VAR iInt := TO_INT(byHigh*16#100 + byLow);

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    If you are not using any specific Raspberry Pi functionality, then probably the "universal" Control Linux ARM SL is the approriate runtime to run on the Pi. For the license it doesn't matter which runtime version you choose, because this is not hardware based anymore, but application based. Best is to use the latest version of CODESYS. To determine which license you need, double click on your device, go to the tab License metrics.... Generate the code for your application and see which license you...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You have declared the function block in a function and call the instance also from a function. This is not correct, because a function is initialised with every call. The http client function block should be declared as Global Variable if you want to cal it from a Function, but probably it is better to declare it in a Program and also call the instance of the http function block from the same Program.... The variables of a Program are not initialised with each call.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If your Control Win is the Modbus "Master" then your configuration should be something like: Modbus_COM (Serial port) - Modbus Master (this is the Control Win SoftPLC actively setting up the communication) - Modbus Slave (this is then your WAGO 750-315) You need to add channels to the Modbus Slave configuration to inform the master which variables to read/write from the Wago module. The way you configured it now, the Control Win is also a slave. PS, don't forget to put the PLC (Control Win) in R...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You cannot create an array of Programs. Create a Function Block for this purpose instead of a program. You can create an array of FB instances and call each instance in a loop.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    First of all you need to enable "Use unicodestrings" in the Visualization Manager. This function returns a pointer to a WSTRING (not STRING). To get this wstring value, do something like this: VAR myWstringVariable : WSTRING(255); END_VAR myWstringVariable := myResult^; // this is dereferencing the pointer to the WSTRING.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    https://content.helpme-codesys.com/en/CODESYS%20Git/_git_using_scripting.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    With new runtimes, the access outside the runtime folder is protected. See: https://forge.codesys.com/forge/talk/Engineering/thread/3da9ded84e/

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    I think, that if you set the timebase to T#0s, that it will be reset. But you can also make your own ramp down with a Timer (make sure the PT time is not T#0s):

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I think, that if you set the timebase to T#0s, that it will be reset. But you can also make your own ramp down with a Timer:

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The string_Util_Intern is not the library I referred to. With a CONCAT function (also with the string util library) a search is done for the NULL character. If you concatenate 20000 characters to one string, then the longer the string, the longer it takes to find this NULL character.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Create a (global) array of Messages: aMessage : ARRAY[0..NR_OF_MESSAGES-1] OF CAN.RxMESSAGE; Then add each received message to the array. IF UserVarGlobal.g_countMsg_RPMset < NR_OF_MESSAGES THEN aMessage[UserVarGlobal.g_countMsg_RPMset] := Message; UserVarGlobal.g_countMsg_RPMset := UserVarGlobal.g_countMsg_RPMset + 1; END_IF

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See: https://forge.codesys.com/prj/codesys-example/element-collect/home/Home/ This contains an application "OnlineChangeSafeLinkedListExample". What you should do is create a new interface which has your "Priority" property. Then your FB should extend the base element function block and implement your own interface: E.g. FUNCTION_BLOCK MyElement EXTENDS COL.LinkedListElementBase IMPLEMENTS I_MyInterface Then the __QUERYINTERFACE does the magic to check if your "element" also implements your interface....

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The new (UTF8) string library is faster and can handle large strings. https://content.helpme-codesys.com/en/CODESYS%20String%20Libraries/_strlib_start_page.html PS, in CODESYS, the maximum string length is not 255 characters. The String functions of the standard library are limited to strings of 255 characters. But you can use other (memory) functions to handle strings larger than 255 characters.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    https://forge.codesys.com/prj/codesys-example/file-utilities/home/Home/

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Their is quite a detailed explanation in the help: https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_codesys_modularization.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See: https://content.helpme-codesys.com/en/CODESYS%20FAQ/_faq_start_page.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The message means that you (CODESYS) tries to open the function block, but this is not possible because the library which contains the FB is compiled. You either get this when you try to manually open the function block (while editing the application), but it could also happen that an exception occurs in the running application and CODESYS tries to show the location where it occured. If it happened in an FB of the compiled library, it cannot show this and you could get this message too.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See: https://content.helpme-codesys.com/en/CODESYS%20Examples/_ex_canopen_canopen.html SDO example: SegmentedAndBlockWriteExample: Writing if an object of any length via SDO (segmented transfer or block transfer) by means of CiA405.SDO_WRITE_DATA This help page also contains a link to a demo project.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You could use the Modulo function to get the minute part from the total minutes: Minutes := TotalMinutes MOD 60;

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Your function block instance is not called, so the code is not executed to set the light on when the button is pressed.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If it is a BOOL, then use: ...Error_Active := ALARM BOOL: ALARM INT: STATE

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Do you mean this: https://content.helpme-codesys.com/en/CODESYS%20Communication/_comm_use_dynamic_opc_ua_server_comm_settings.html

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Probably best to call the FB continuously. So something like this could solve it: IF xOpenLatchSettingDialog THEN xOpenLatchSettingDialog := FALSE; fbOpenLatchSettingsDialog.xExecute := TRUE; END_IF IF fbOpenLatchSettingsDialog.xDone OR fbOpenLatchSettingsDialog.xError THEN fbOpenLatchSettingsDialog.xExecute := FALSE; END_IF TopLeftDialog.iX := 100; TopLeftDialog.iY := 23; fbOpenLatchSettingsDialog( itfClientFilter:= VU.Globals.OnlyTargetVisu, sDialogName:= 'visu_AlarmLatchSettings', xModal:= TRUE,...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Minimum version is 3.5 SP19 Patch 3. See https://store.codesys.com/en/codesys-git.html But you could ask your PLC vendor if it is possible to program their PLC's which have Runtime version SP16 with development version 3.5 SP19 or higher (should normally be possible, but with Safety PLC's there could be some regulation limitations).

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I don't know the details of jsonArrayWriter, but the common behaviour for an xExecute input is that the FB starts on the trigger that it gets TRUE. In your case xExecute is never FALSE, so it is never triggered again to start the jsonArrayWriter. So change the condition from TRUE to a variable which you set to TRUE with the "xFirst". Then when the jsonArrayWriter is done (xDone), or has an error (xError), then set this variable to FALSE.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    If you use 3.5 SP10, then Git is not supported. SVN will work fine, but with this version you do need a USB key, because software licenses are not supported with this version. Off course you can work without SVN (or Git), but especially if you work with multiple developers on one project, it will save you a lot of time and you can keep track of all changes and improvements much easier. So how much is this worth to you?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    What we are trying to explain is that, yes CODESYS creates the software, but Epis decides how they implement it on their hardware, which runtime version they use and they decide which functionality they support. So it is always a combination of the two. What CODESYS provides is a runtime with options for e.g. visualization or softmotion. Epis could add this softmotion license as default to their controller, but if they don't then CODESYS provides another option with a single license in a "Wibu CodeMeter"...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Maybe also good to know that you could use the CODESYS installer to switch between gateways. - open the CODESYS installer - Select the (hamburger) menu - Select Settings - Select Services Then select the Gateway you would like to use.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Most likely related to the Device Diagnostics functionality. Double click on your device (PLC), go to the tab "PLC settings". Enable the advanced option "Enable diagnosis for devices". Build your application again.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You should only open de COM port once and then leave it open. This hCom should not keep on incrementing. (off course when you are done communicating, you need to close the COM port)

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    In your project you selected the "CODESYS Control Win V3" as device, but the device you want to connect to is a "CODESYS Control Win V3 x64". Those are not the same. If you double click on the device during the network scan, you will get information that these are not the same, but that you can change the type in your project to the x64 bit type. Another option is to "right-click" on the device in the device tree of your project and select "update device" then select the x64 type.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    See the attached pdf with some notes (screenshots) which I prepared for one of our customers to help them get going. Hopefully this helps for you too.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Add the object "POU for Implicit Checks" to your application, then select "Bounds check". This will create a function which is automatically called each time an array is write accessed. In the function you can handle "out of bounds" situations. By default it will be limited to its lower or upper bound.

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Use e.g. the condition: TCP_Connection_0.xActive AND NOT(TCP_Write_0.xDone)

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I don't know the root cause... But what could help to continue when it seems to hang, is stop the CODESYS (communication) Gateway. Go to the Windows SysTray, find the icon for the Gateway and then stop it and start it again. This will interrupt the connection between CODESYS and your controller.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You should ask IFM to provide you with the correct version of their controller packages. Then after you have installed this, you can select the correct version of the controller by right clicking on it in the device tree, update device, enable the option "Display all versions" and then select the version which matches your controller. Alternatively you can ask IFM to provide an update package which can update the runtime version on your controller to 3.2.0.0.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Are you 100% sure you created a boot application?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Not sure, but maybe it related to the style. Go to the Visualization Manager in your project and see if a style is selected, or choose another style to see if this helps.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Are you using the Control Win SL (installed together with the development environment of CODESYS)? If yes, you might want to consider using the CODESYS RTE instead. This has real-time capabilities (running on separate core(s)). But to be able to use this, you have to install the CODESYS Ethernet driver for your network interface to be able to let the RTE access the network port also in realtime. See: https://store.codesys.com/en/codesys-control-rte-sl-bundle.html https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_windows_rts_v3.html...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Are you using the Control Win SL (installed together with the development environment of CODESYS)? If yes, you might want to consider using the CODESYS RTE instead. This has real-time capabilities (running on separate core(s)). But to be able to use this, you have to install the CODESYS Ethernet driver for your network interface to be able to let the RTE access the network port also in realtime. See: https://store.codesys.com/en/codesys-control-rte-sl-bundle.html https://content.helpme-codesys.com/en/CODESYS%20Control/_rtsl_windows_rts_v3.html...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    This is almost always related to previously working with an additonal monitor. If you have placed CODESYS on that monitor, later start your laptop again and open CODESYS without that monitor, then Windows still places it in the previous position, but then it is not visible. So the solution by cehermanstad can be used to move it to the main screen to make it visible again. PS, another way to move it, is by pressing SHIFT and then right-click on the icon in the task bar, then select move. You can then...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I'm not sure, but maybe you have to configure the 750-652 first with the WAGO-IO-CHECK software to set it in RS485 mode?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You have selected the new Ladder editor. This only has these items in the toolbox.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The IoT library contains a Web Socket library. Maybe this provides your required functionality. See https://store.codesys.com/en/codesys-iiot-libraries-sl.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    It is part of the IoT library. See: https://store.codesys.com/en/codesys-iiot-libraries-sl.html

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    if you just want to show the currently logged in user in the visualization, then just create a field with text %s and as text variable VisuElems.CurrentUserName

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Yes, it is possible to set breakpoints and use step into / step over (also in Ladder diagram). Yes, the PLC will actually stop, so be carefull with this. How a PLC works is that at the start of the execution of the Task, the Inputs are read, then the code is being executed and then the outputs are written. So if you set a breakpoint, you will not see your analog inputs changing, because the task cycle is interrupted and the inputs and outputs are not refreshed. For detailed information, see: htt...

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    It depends on your application which CPU speed and RAM size you need. If you think the Control Standard S license is sufficient then my guess is that your selected PC has no problem running your application. There are no more "hardware" based single licenses available anymore, only application based licenses. So this "Raspberry Pi" restriction for home automation is not applicable anymore. For more information see: https://store.codesys.com/en/howto_applicationbasedlicenses

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The Epis controller should support the CodeMeter driver to be able to access the license containers on the CODESYS Key.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    To prevent ambiguous use of this enumeration value. Let's say another ENUM is available in your project or in another library which has an enumeration value AM_WRITE, then it is not clear which AM_WRITE you want to assign. By this qualified access to the SysFile.AM_WRITE, it is completely clear for the compiler.

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Maybe the CODESYS HMI is a good solution. https://store.codesys.com/en/codesys-hmi-sl-bundle.html Run this on the remote main control station. In the HMI application you can add the data source manager and to this manager you can add Data sources. A data source has a reference to the PLC you want to connect to and can get access to the variables of the PLC application. You can then use these variables in the visualization of the HMI application.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I had a similar error "Invalid ERR Ack input". What you need to do is link an variable from the "non-safe" PLC to the Group IOs of the POU in the Safety app. * Add a POU to the SafetyApp (probably already done, otherwise you don't get this error) * Right click on this POU - select properties * Go to the Group IOs tab * Link a variable to the Err.Ackn. input I don't know about the Size of zero, I didn't get this error. Were you able to fix this?

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I'm not sure what you are trying to do, but getting the CurrentUserGroupID like this will not work, because there could be multiple Visualization Clients and each can have a different user that is logged in. Also when you go online with CODESYS and open an Visualization, this is counted as a client. Probably this is the reason you see it changing. What you can to is "iterate" over all clients and then see which user is logged in on which visualization Client. For this you need to add the Visu Utils...

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    You can use the (open source) FTP client in Forge. This works on 64 bit systems. See: https://forge.codesys.com/prj/ftp-client/code/HEAD/tree/ As this is open, the idea is that when you use it and make improvements to the source code, that you also commit this in a branch so others can also benefit from it.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    copy paste?

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    I think you want to implement client side scripting? Maybe creating HTML5 objects is an option, because the JavaScript is executed on the client side. See html5

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    What maybe helps is the Visu Dialog ST demo project: https://store.codesys.com/en/visu-dialog-st.html This has an application IECOpenDialog where dialogs are opened using the VU.FbOpenDialogExtended function blocks. The fbOpenConfigurationDialog call has a reference (interface) to the "close listener" FB of which it's method is automatically called when the dialog is closed. This way you can create specific function blocks for each dialog when it is closed and do what you want with the data that...

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    I'm not really sure what you are trying to do, but maybe you are referring to using the CmpCharDevice library? When you "open" the connection to a device, you can pass flags. What helped me is to set the non-blocking flag. I'm not sure if this is what you are referring to, but maybe it helps: dFlags: DINT := CmpCharDevice.ACCESS_MODE.O_RDONLY + DINT#4000; // see details for flags: http://linux.die.net/man/2/open, + DINT#4000 is for non-blocking hDevice := CmpCharDevice.CDOpen(szFilename, dFlags,...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    https://en.wikipedia.org/wiki/Modbus

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Maybe there is a better way, but a long time ago I created a test application that worked like this: With a button I opened the dialog and I added a "Input configuration - OnDialogClosed" "Execute ST-Code" action to this same button which called the following Function when the dialog was closed: F_OnFileDialogClosed(pClientData); Below this Function which handled the result: // This function is called from the visualization when the dialog is closed. FUNCTION F_OnFileDialogClosed : BOOL VAR_INPUT...

  • TimvH TimvH modified a comment on discussion Engineering πŸ‡¬πŸ‡§

    In the example project, you can see that a CAN.CANAreaReceiver is used which has an VAR_IN_OUT reference to a RECEIVER_AREA structure. This structure has a dwIdStart and dwIdEnd to filter a range of ID's and process them through the referenced msgProcessor.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    In the example project, you can see that a CAN.CANAreaReceiver is used which has an VAR_IN_OUT reference to a RECEIVER_AREA structure. This structure has a dwIdStart and dwIdEnd to filter a range of ID's and process them throught the reference msgProcessor.

  • TimvH TimvH posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    On a PC with the Control Win, this is probably related to the fact that the CAN drivers are not loaded. Go to the folder where your Control Win Configuration file is: - E.g. C:\ProgramData\CODESYS\CODESYSControlWinV3x64\E1FA7ABE - Open the CODESYSControl.cfg - Remove the semi-colon in front of the CAN driver you want to use (section ComponentManager). - Set the component ID to the next number in the list (e.g. Component.8) - Save this file and restart the Control Win.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    For a demo application related to date/time, see: https://forge.codesys.com/prj/codesys-example/date-and-time/home/Home/

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You will need a USB to RS485 converter to connect the PC to the Modbus RTU Slave Device. In Windows this converter will be recognized as Serial COM poort (e.g. COM2, or COM3, see the windows device manager to find this out). Select this port in your CODESYS application. On the PC you need to use the CODESYS Control Win (SoftPLC) to run your application. It will not work in simulation mode, because then the Modbus Communication will not be activated.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Maybe select the local gateway instead of the gateway on the remote device?

  • TimvH TimvH posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    You need to start the application, see the "start" option at the top left (next to close simulation).

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Maybe the following helps: https://forge.codesys.com/prj/codesys-example/modbus/home/Home/

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Look all the way at the end of the link below. This provides a way to use arrays with various lengths: https://content.helpme-codesys.com/en/CODESYS%20Development%20System/_cds_datatype_array.html

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You are trying to make something very simple really complex, but my best guess is that the order of execution is: - initialize FB (x becomes 1) - Load persistent (x is 1) - start application (x remains 1) PS, It could also be that your "persistent" variables are not stored correctly and that, at startup, the value is always 0. Did you add this variable to the Persistent Variable list? And did you make sure that this works correctly on the device you are using? So maybe the execution order is: - load...

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    It is a naming convention. Nothing else. Most often you see this being used for the local (private) variables of a Function Block. It comes mainly from C++ / C# to not mix them up with (public) properties. Probably best is to search for C++ naming conventions to get more information.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    go to the library manager of your project click on Add Library (top left corner) type in CAA Memory - you will see it in the list. If not, and you don't have the latest version, maybe you have to select Advanced first. then double click it to add it to the library manager of your project. Then you can use the functions from it in your project.

  • TimvH TimvH posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Maybe you should not use SIZEOF, but LEN. Because SIZEOF means you will get the memory size of your string variable (e.g. maximum 80 characters), but LEN will give the actual length of the string.

1 >