Activity for snhatton

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    What type of PLC are you using?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    What type of PLC are you using?

  • snhatton snhatton posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Did you check the access rights of the visualization elements in question?

  • snhatton snhatton posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    You could try using the VUM_UserGroup struct from the VisuUserManagement library. I haven't tried this, but there is a variable for tAutoLogout to set the logout time.

  • snhatton snhatton posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    You can change the node id by adding the following to /etc/CODESYSControl.cfg: [CmpOPCUAProviderIecVarAccess] CustomNodeName=MyPLC123 Then restart the runtime and the new Node name will appear with the connection. I don't know if it's possible to remove the |var| from the name. I hope this helps!

  • snhatton snhatton posted a comment on discussion Runtime πŸ‡¬πŸ‡§

    Good afternoon, After changing the security settings to: CommunicationPolicy: POLICY_BASICSHA256SHA256 CommunicationMode: ALL Activation: Activated UserAuthentication: ENABLED Then generate a new certificate on the device for the OPC-UA server from Security Agent->Device->OPC UA Server. Restart the runtime using tools->Update Raspberry Pi->Stop->Start for the changes to take effect. It may take a minute for the runtime to start. Initiate the connection from the UA server side. You should see a pop-up...

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    One option could be to use a trigger variable to execute your trace and then toggle that variable from a step within a test case.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    There is a tool called test manager that is part of the Professional Developer's Edition of CODESYS. I would take a look at this tool for your testing purposes. There is a free 30-day trial so you can evaluate if the tool will meet your needs before investing in the license.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Yes, you can use the CODESYS ControlWin V3 Soft PLC. However, if simulation is enabled on the device this will disable all communication, so you need to turn off simulation to view the visualization in a web browser. In simulation mode, all IO and communication is disabled for standalone testing. In addition, make sure to set the start visualization in the WebVisu object in the application tree. I hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Have you tried using the persistence manager which uses the file system of the controller to store persistent variables?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Does this help: https://pimylifeup.com/raspberry-pi-static-ip-address/#:~:text=1%20To%20begin%20setting%20up%20a%20static%20IP,go%20ahead%20and%20restart%20the%20Raspberry%20Pi.%20. Following those instructions, it is possible to configure the ip address as static.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Good morning, Yes, this is a known bug that has been reported. For now, the only workaround is to open the function block instances from the device tree. Regards, -Shawn

  • snhatton snhatton posted a comment on discussion Forge πŸ‡¬πŸ‡§

    Can you try the command "Download Missing Libraries"?

  • snhatton snhatton posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Here is some information about formatting different variables types: https://content.helpme-codesys.com/en/CODESYS%20Visualization/_visu_placeholder_with_formatting_sequence_in_a_string.html I hope this helps!

  • snhatton snhatton posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Hi There, For my understanding: are you trying to display the contents of a text list in an alarm message based on the id? For example, you could maintain a text list of common alarm messages, and then display based on which message is true?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I think more information is needed to help solve the issue. Can you list the exact steps to reproduce the issue? What version of Codesys are you using? Did you add a persistentVars object to your project? I would recommend browsing all instances of the retain variable to see all possible writes to the variable in question.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Have you seen this project: https://forge.codesys.com/prj/codesys-example/responsive-desi/home/Home/ ?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The analog sensor referenced in the video looks to be available here: https://ooip-foundation.proboards.com/board/4/ooip-input-objects. Have you looked at the OOIP example project from Gary's website?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You can try a source upload, but like the other user mentioned, this is dependent on the source code being downloaded to the controller. To do so: go to file->source upload and add the device by IP address.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    The SysTimeRtcConvertUtcToDate function does this for you and applies the output to RTS_SYSTIMEDATE struct. This is part of the SysTimeRtc library.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You should also check the security settings as shown in the attachment. The reason there are two is because one resolves to the host name, and the other resolves to the host IP. Have you looked at the log? Are there any messages regarding the OPC-UA component?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I was able to duplicate this same issue with Visualization 4.4.0.0 and experienced the same results as you. After saving and closing the project and then reopening, the visualization is marked as modified with an orange rectangle. However, when doing a compare, the message reveals that the two commit objects are the same. This seems like a bug and I will investigate further.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi There, The workflow with persistent vars object is to first declare variables either in a POU or a global variable list with the option PERSIST, RETAIN, and PERSIST RETAIN. After the variables are declared, then in the persistent vars object, you would activate the "Add all instance paths" command by right-clicking in the declaration area of the persistence vars object. Alternatively, you can use the Application Composer - Persistence Manager module. Here is the help file: https://content.helpme-codesys.com/en/CODESYS%20Application%20Composer/ac_pm_overview.html....

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    This may be possible by setting the BY variable to a variable of your enumeration, and then setting an instance of your DUT to the value of X. Such as: FOR j:= 0 TO 100 by x DO myDut := x; x := myArray[j]; END_FOR I hope this points you in the right direction. Please let me know if you have further questions.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Good afternoon. You can set your invisibility property to an expression. For example, in this visualization, the image will only be visible when PLC_PRG.p is not equal to 1.ng width=50%]]. This property is below the State variables in the properties tab. I hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    With the recent google security updates disabling access to third party apps unless you are a google workspace admin, I was unable to find a good example of a PLC acting as a POP3 Mail Receiver. Does anyone in the forge community have a good example of this? Thanks in advance. -Shawn

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    With the recent google security updates disabling access to third party apps unless you are a google workspace admin, I was unable to find a good example of a PLC acting as a POP3 Mail Receiver. Does anyone in the forge community have a good example of this? Thanks in advance. -Shawn

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Oleg, I'm glad you were able to find help from Beckhoff! I can't speak to your exact experience, only wanted to highlight the best way to get ahold of us at support. If, in the future, you have any issues please do not hesitate to contact us. Regards, -Shawn

  • snhatton snhatton modified a comment on discussion Forge πŸ‡¬πŸ‡§

  • snhatton snhatton posted a comment on discussion Forge πŸ‡¬πŸ‡§

    Talk Topic about project #class-based-sfc

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Dear @Boldive, Thank you for your response. We appreciate your feedback and understand your frustration with the phone support experience. We would like to inform you that we have a dedicated ticket system in place to ensure efficient and timely customer support. Our ticket system allows us to track and address customer inquiries effectively. To access our ticket system, please visit our website at: https://www.codesys.us/codesys-support.html. Our support team continuously monitors the support ticket...

  • snhatton snhatton posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Rather than using a trace, you can use a trend. This will insert a trend recording manager object into your application, and a separate task for execution of the trend. This object also gives you much more control over the graph. After inserting, right-click the graph, and select 'Insert elements for trend recording". This will pop up a dialog allowing you to automatically add an link graph control elements to your visu. I hope this helps!

  • snhatton snhatton posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    According to the release plan here: https://www.codesys.com/the-system/codesys-release-plan.html visualization updates are expected around the middle of June. I would expect updates to VisuUserMagmtDialogs as well. I hope this helps! For confirmation, I'm using 3.5.19.0, with the latest library updates, and my version is still 4.2.0.0.

  • snhatton snhatton posted a comment on discussion Visualization πŸ‡¬πŸ‡§

    Have you looked into the visuDialogs library? You could use this to open a file browse dialog set to the default directory of the HTML help file, and dynamically modify the path for each alarm instance. I hope this helps point you in the right direction.

  • snhatton snhatton posted a comment on discussion Automation Server πŸ‡¬πŸ‡§

    Hello, I noticed that your project does not have a OPC UA server for configuration of attribute access. For configuring symbolic access to the instances in your program, I believe you would need to add the instances to the OPC-UA server symbol set so that it resembles the screenshot: I hope this helps! -Shawn

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello, quick question: when you start the raspberry pi runtime you should see the status of the ssh commands issue to the raspberry pi. Are you seeing that codesyscontrol is already running in the message "Standard output: codesyscontrol already running"?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    My approach/recommendation would be: create a function block designed to pair with the visualization dialog pop-up. Declare a string variable inside of the function block to store the value of the user input. Set this variable as VAR PERSISTENT RETAIN. You will either need to add a persistentVars variable list to manage the persistent data, or you will need to use the application composer persistence manager. Application composer is a licensed product, but the persistence manager plug-in is free...

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello, Please take a look at the scripting engine reference documentation: https://help.codesys.com/webapp/ScriptDeviceObject;product=ScriptEngine;version=3.5.17.0 There are methods described here that allow you to add, update, plug, insert, etc. device objects. Of course, you will need to know and provide the identify information of the type of device you are trying to add, however, this should get you started. Please let me know if you have any more questions or concerns. Thanks! -Shawn

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi There, another option to consider is using the APInstaller.CLI command line interface to automate installations. Here is an example of how you can add a new build to Codesys Installer: PS C:\program files (x86)\CODESYS\APInstaller> apinstaller.cli --createInstallation --channel default --generation 3.5.19.0 --installationName InstallationFromCLI --product CODESYS --bit 64 --patch 0 --hotfix 0 --build 0 --destinationFolder "c:\program files\codesys 3.5.19.0\" Please keep in mind that you need to...

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi There, another option to consider is using the APInstaller.CLI command line interface to automate installations. Here is an example of how you can add a new build to Codesys Installer: PS C:\program files (x86)\CODESYS\APInstaller> apinstaller.cli --createInstallation --channel default --generation 3.5.19.0 --installationName InstallationFromCLI --product CODESYS --bit 64 --patch 0 --hotfix 0 --build 0 --destinationFolder "c:\program files\codesys 3.5.19.0\" Please keep in mind that you need to...

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello, I hope you are doing well. Here is a similar discussion topic posted in Forge that I think can help you: https://forge.codesys.com/forge/talk/Engineering/thread/aa5f2f9294/. I hope this helps! Regards, Shawn

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I think the IoDrvModbusTCP library would work for you. From here you can write IEC code to connect to and configure your modbus devices without having to manage the device tree. Hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Yes, this is possible and there are a few options. Automation Server is an option, and invoking the python scripting commands is another option. Python scripts can be used to access different CODESYS components including logging in and downloading. To run a script from the command line without opening the IDE you can do the following: code CODESYS.exe --Profile="CODESYS V3.5 SP18 Patch 4" --noUI --runScript="C:\SomePythonScript.py" Here is the scripting guide for using python with CODESYS: https://content.helpme-codesys.com/en/ScriptingEngine/ScriptProjects.html...

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Can you provide more information on which protocol you are using? If OPC-UA, you will need to add a symbol configuration to your project and assign symbol access in the symbol configuration to expose variables over OPC-UA.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    In most cases, it depends on the library that is missing as libraries can be developed and utilized outside of the CODESYS store, and not all libraries are available at a web URL. In the case of a CODESYS published library, you can find the library in the store or in CODESYS installer by using the "BROWSE" functionality after selecting "CHANGE" for the specific instance. If you send me library names and versions, I can help further.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Which PLC are you using? Some vendors manage their own RTC and have specific ways of setting the clock.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    You can disable this by modifying the cmpLog settings in the CODESYSControl.cfg file (usually found in C:\ProgramData\CODESYS\CODESYSControlWinV3x64\<unique id="">) to this. This should filter out open/closed connections: </unique> code [CmpLog] Logger.0.Name=PlcLog ;Logger.0.Filter=0xFFFFFFFF changed logger filter from 0xFFFFFF to 0x1F to filter out open/close connections logger.0.Filter=0x1F Logger.0.Enable=1 Logger.0.MaxEntries=100000 Logger.0.MaxFileSize=500000 Logger.0.MaxFiles=3 Logger.0.Backend.0.ClassId=0x0000010B...

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi Wayne, would you be willing to share a portion of your project? It's difficult to troubleshoot the issue without understanding the application.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello Mozed, Can you use a program like WinSCP to move the CODESYSControl.cfg file into your local windows directory, modify the file, and then move back using WinSCP?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello, is splitting the communication from Modbus TCP and Ethernet I/P into two separate scanners an option?

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello Ivan, For direct CODESYS support please contact us at: https://www.codesys.us/codesys-support.html. From there you can purchase a support ticket and will get connected directly to a CODESYS support engineer. Hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi there, I would take a look at the SysProcess library which allows you to execute OS commands from IEC code. I hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello, Sometimes the install is interrupted when anti-virus software is enabled. Can you try doing a full uninstall, turn off any antivirus software and try the install from Codesys installer. Make sure you run this as administrator. You can also start a custom event logger in windows to help you identify what the issue is. I've attached a screenshot with the configuration options. Please let me know if you have any questions or concerns. Hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello, yes if you add 'Lib2' inside of 'Lib1' only Lib1 is required to install both libraries. Hope this helps! -Shawn

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi there, Whenever you add a communication device to a project, implicit function blocks are created, which you can then use throughout your IEC program. Please see the attached picture for an example. This example is for modbus, but works similarly for other communication protocols. I hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hi there, You should be able to right click on the CC100 and choose add device. From there, Ethercat Master should be an option. Be sure you've installed the package from: https://www.wago.com/medias/WAGODSP-v2.0.0.2.zip?context=bWFzdGVyfGRvd25sb2Fkc3w1Nzk5MjA2NjV8YXBwbGljYXRpb24vemlwfGg2Ni9oZDYvMTM3MjQyNDAxNTA1NTgvV0FHT0RTUC12Mi4wLjAuMi56aXB8ZmYxN2VmYjcyODViOTJhYWNjYjA5OGY4ZDVjNDM3MWQ3MzBlZGVjMTM3MzBkMjZhYTNlZTM4ZjYwYWFhYWRmYw&attachment=true. Hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Hello! This is a known bug and as far as I know there is not an option to enable this. An alternative method of making on online change without stopping the controller is to "logout", make the change offline, and then choose option "login with online change". This allows you to merge the online change without changing state of the controller. Hope this helps!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    I would like to help you out. Can you include more information such: exact steps to reproduce the error, where you are seeing the error, which version of Codesys you are using? If you can upload a project archive I would be happy to take a look.

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Wonderful! Glad you got it working!

  • snhatton snhatton posted a comment on discussion Engineering πŸ‡¬πŸ‡§

    Good morning @Dagi89, I've attached an example for your consideration. The attached example saves a formatted csv file every 5 seconds and is based on the CSV Utility example located in: C:\Users\<user name="">\CSV Utility SL\1.0.2.0. </user> The csv file is limited by number of lines that can be written and file size. The program Sequential_Add_Values is where the CSV fields are defined. The program Sequential_Save will save the csv, or create a new csv if the file size is exceeded. I hope this...

1